3.14 LOW CURRENT SYSTEMS

Related Documents



-           Drawings and general provisions of contract, including general and supplementary  conditions.

-           General provisions for electrical work section.

-           The requirements of this section apply to fire alarm system. The contractor shall coordinate with   

             mechanical systems specification



DESCRIPTION OF WORK



Works Covered under this section include providing a fire alarm system in the whole areas



-         Work includes a complete fire alarm system in the buildings and providing all materials, equipment, accessories, services and tests necessary to furnish and install a new multiplexed, analogue addressable fire alarm system   of the non-coded type. Provide supervised wiring, all operations, and hardware, as described herein and shown on plans. The system to consist of, but not be limited to the following:

*        Main Fire Alarm Control Panel FAP

*       System printer at .F.A..P.

*        Power Supplies.

*         Addressable manual fire alarm stations

*         Fire bridge interconnection

*        Addressable area photoelectric / Ionization smoke detectors 

*        Addressable ducts smoke detectors.

*        Addressable area detectors 

*        Emergency generator monitoring.

*        Monitor zone addressable modules (for non - addressable initiating devices)

*        Control zone addressable modules.

*        Interface unit with fire fighting control panel

*        Public address interface unit.

*        Central station operation.

*        Visual monitoring / status of items at the FAP.

*        Conduit and wire.

*        Approved fused cut - out panels.

*        Manual and automatic silence of all paging and / or sound system (s)

*        Battery and battery / inverter (UPS) back -up operation.

*       Special tools which shall be required for the dismantling of detectors for periodic cleaning in accordance  

         with the manufacturer instructions.



 - The fire alarm system is to be installed for addressable initiating and control   circuits with hard -wired signaling circuits utilizing conduit, tubing and wire serving all peripheral devices such as manual stations smoke detectors etc.

- Obtain and deliver a final certificate of approval to the owner from the fire department for all fire alarm and smoke control work under this contract.

-   It is the responsibility of the contractor to produce all written requests to the fire department for  inspections if the fire alarm system and associated equipment written requests to be produced in a fashion to ensure inspection when equipment is fully operational be in accordance with this specification. Contractor to gain final approval in an expedient manner

-   Contractor to be responsible for all fire alarm equipment after completion of work and prior to any inspection with written report given as proof of condition of the system. All system devices and their circuits to be in first class operating condition after completion of work.



WIRING:



-         All fire alarm equipment and wiring must be installed  in conformce with the National Electrical Code

-         All low voltage wiring for the systems must be installed in  true class form with the "return" portion of the circuit  home run in separate piping. Class A return for more than one circuit may be contained in a common pipe. Class "A" return pipes must be labeled as such with lettering, directional arrows or other method to differentiate from the other circuit pipes.

-         Cables shall of fire resistance type according to NFPA

-‏      All raceways are  to be concealed in hung ceilings or run in  concealed areas to minimize exposure in public corridors and  spaces.

-         All components of the fire alarm be U.L. listed by one manufacture

-         After the completion of the installation of the fire alarm system, the contractor shall perform a complete demonstration test of all systems and devices to the satisfaction of the Owner and their consulting engineer. When the system has been accepted, the licensed electrical contractor for this project shall sign the department of buildings fire alarm inspection and testing.



QUALITY ASSURANCE




-         The submitted components must be U.L. listed factory mutual approved in the name of the organization.

-         Standards compliance : comply with requirements of all applicable  local codes, NEC, U.L., NFPA, and NEAMA Standards  pertaining to fire alarm, life safety systems

-         The following standards are to be included and recognized as part of specification for performance and quality of installation and equipment:

-        NFPA 70 National Electrical Code

-         NFPA 72A Standard for the installation, maintenance and use of protective signaling systems.

-         NFPA 90A Air Conditioning and Ventilating System.



SUBMITTALS:



       List of all types of equipment and components provided including model numbers, mounting accessories and quantities.

-         Description of operation of the system as described herein, to include all exceptions , variances or substitutions listed  at the time of bid.

‏-         Calculations to support size of standby batteries,   manufacturer' printed product data, catalog cuts and  description of any special installation procedures .



_      Provide shop drawings as follows:

*        Large scale drawing of Fire Command Station

*        large scale drawing   showing all equipment locations and receway runs.

*        Large scale drawing of  the addressable fire alarm control panels and fire command station.

*        Complete riser diagram showing all equipment and size,   type and number of all conductors and conduits.

*        Peripheral device connection details showing all module and device wiring details.

-        Provide sample of various items, when requested .



OPERATION:



A.     Activation of any manual pull station, duct smoke detector,  heat detector, area smoke detector,  to provide the following automatic  operations:

‏ ‏-        Sound a pulsing audible signal at the fire alarm control panel. Pressing alarm acknowledge key on the fire alarm control panel silence the audible signal during the alarm condition. Subsequent alarm conditions shall again sound the audible signal.

-         Flash the general alarm LED  indicator on the fire alarm  control panel pressing the alarm acknowledge key on the  fire alarm control panel shall continuously light the  general alarm LED indicator during the alarm condition.  Subsequent alarm conditions shall again flash the  general alarm LED indicator.

-         Display a general alarm indication and system status summary   (numbers of alarm, supervisory and /or /trouble conditions) on the fire alarm control panel liquid crystal display (LCD)

          Pressing the alarm acknowledge key shall display, for 30 seconds, the individual device display, to include the "alarm" status and custom label for the addressable device reporting the alarm condition. At the end of the 30 second period, the general alarm indication and system status summary shall again be displayed. The individual device display may be recalled at any time by repressing the alarm acknowledge key or until the alarm condition is reset to normal.

-         Enter the custom label for the device  reporting the alarm condition with time   and date of occurrence into the fire alarm control panel historical alarm log for future recall.



In Case of Fire Alarm

-         upon verification of any smoke or heat detector alarm signal or upon receipt of any signal from a detector, manual   alarm call station shall initiate an alarm signal. Initiate an alarm signal to sound on the floor of alarm, the floor above and the floor below, as indicated in the riser diagram.

        In case of general evacuation, sound the alarm signal throughout the building. The alarm signals may be silenced the alarm control panel silence switch. Subsequent alarm by using conditions shall resound the alarm horns.



*        Operate control relay to release all magnetic locks on doors (if needed)

          This shall be through the main security control station.(not included in this contract)

*        Automatically shut down all supply and return/exhaust fans of air recirculation systems serving the building,      (co-ordinate with mechanical contractor)

*       automatically close all fire dampers in the building serving the floor in alarm and give indication of status (open/closed) of damper position.

*        Recall all automatic elevators to the ground/entry level if designated by the local authorities through elevators control system.

*        Automatically silence all paging and/or sound system (s  ).

*        In case of evacuation, emergency alarm massage shall be announced through the sound system in the relevant sound system zones.

*        Re-automatic elevators to the ground/entry level if designated.

*        Send an alarm signal to a central station monitoring facility to dispatch the fire department.

*        Automatically release all electrical door locks in escaping routs through the main security station (whish is not included in this contract).

*        Visually annunciate the individual addressable device reporting the alarm condition or the software defined group of addressable devices, which includes the addressable device reporting to alarm condition, via an individual or "group" alarm LED indicator. The visual indication shall remain on until    alarm condition is reset to normal.

*        Activate remote printer to printout a hard copy record of alarm activation to include the time , date and custom label for the device reporting the alarm condition

-         System supervisory operation for abnormal conditions:

*        The following equipment or devices associated with the fire alarm system shall be supervised for normal and abnormal conditions: ‏‏

-         fire pump power failure and phase reversal

-        Emergency generator running and  failure to start

-         Activation of any items from the above automatically;

*      Sound an audible signal at fire alarm control panel. Pressing the supervisory acknowledge key on the fire alarm control panel shall silence the audible signal during the abnormal condition. Subsequent conditions shall resound the audible signal.

*        Flash the general supervisory service LED indicator on the fire alarm control Panel. Pressing the supervisory acknowledge key on the fire alarm control panel shall continuously light the general supervisory service LED indicator during the abnormal condition. Subsequent abnormal conditions shall again flash the general supervisory LED indicator.

 *       Display a general supervisory  indication and system status summary (numbers of alarm, supervisory and/or trouble conditions) on the fire alarm control panel liquid crystal display (LCD). Pressing the supervisory acknowledge key shall display, for 30 seconds, the individual device display, to include the" abnormal"  status and custom label for the supervisory device reporting the abnormal condition. At the end of the 30second period, the general supervisory indication and system status summary shall again be displayed. The individual device display may be recalled at any time by repressing the supervisory acknowledge key or until the abnormal condition is restored to normal.

*        Enter the custom label for the zone reporting the abnormal condition with time and date of occurrence into the Fire Alarm Control Panel historical trouble log for future recall.

 *       Visually indicate  a general supervisory, abnormal condition at  the FAP, via one general supervisory, abnormal LED indicator. The visual indication shall remain on until the abnormal condition is restored to normal., date and custom label  for the device reporting the abnormal condition. Activate the printer to printout a hard copy record of  the abnormal activation to include the time, date and  custom label for the device reporting the abnormal condition.   





SYSTEM SUPERVISION:



-         Fire alarm system to be electrically supervised to automatically detects and reports trouble conditions as follows:

*        The fire alarm system wiring (except control wiring between fans and dampers, etc. and their control zone addressable module.) shall be electrically supervised to automatically detect and report trouble conditions to the fire alarm control panel.

*        Any opens or grounds on monitor zone addressable module alarm initiating supervisory or status monitoring circuit wiring and any opens, grounds or shorts across addressable data communications, alarm signal or alarm light wiring shall initiate a system trouble condition.

*        System addressable devices shall be supervised for placement, dusty level and normal operation. Removal of an addressable device or the failure of its internal electronic circuit shall initiate a system trouble condition, the system from its normal programmed standby configuration shall initiate a trouble condition.



Trouble conditions shall automatically:


I .       Sound An audible signal at the fire alarm control panel pressing the trouble acknowledge key on the fire alarm control panel shall silence the audible signal during the audible trouble condition. Subsequent trouble signal shall resound the audible signal. The audible trouble signal shall also resound at programmable time intervals to remind the system operator that the trouble condition(s) still exists

II .      Flash general system trouble LED indicator on the fire alarm control panel. Pressing the trouble acknowledge key on the fire alarm control panel continuously light the general trouble LED indicator during the trouble condition. The visual indication shall remain on until the trouble condition is restored to normal. Subsequent trouble conditions shall again flash the general trouble LED indicator.    

III    Display a general trouble indication and system status summary (numbers of alarm, supervisory and/or trouble conditions) on the fire alarm control panel liquid crystal display (LCD) and CRT  display. Pressing the trouble acknowledge key shall  display, for 30 seconds, the individual device or  circuit display, to include the "trouble" status and custom label  for the addressable device or circuit reporting the trouble condition. At the end of the 30 second period, the general trouble indication and system status summary shall again be displayed. The individual device/circuit display may recalled at any time be repressing the trouble acknowledge key or until  the trouble condition is restored to normal.

           

IV       enter the custom label for the device or circuit reporting the trouble condition with time and date of occurrence into the fire alarm control panel historical trouble log for future recall.



V .     Activate the remote CRT to show the trouble activation to include the time, date and custom label for the device or circuit reporting the trouble condition. Activate the remote printer to printout a hard copy record of the trouble condition activation to include the time , date and custom lable for the  device or circuit reporting the trouble condition.   



QUALIFICATIONS OF MANUFACTURER:



-         Manufacturer to train not less than 5 operators of console, with personnel on job instruction provided by competent engineer representing manufacturer.

-         Manufacturer to provide each operator with complete printed operating instructions and brief sub-system description in manual or handbook from.

-         Manufacturer to train operators to maintenance of console printers and other equipment, inclusive of replacing paper, tapes and bulbs.

-         Manufacturer to furnish letter stating that operators have completed training operation of system.



COORDINATION:  



-         Contractor to coordinate with mechanical contractor installation of duct mounted smoke detectors and motor controls.

-         Contractor to coordinate with sprinkler contractor and mechanical section for interface with Fire Fighting Control Panel.

-         Contractor to coordinate with elevator contractor for interface with elevators control system.

.         Contractor to coordinate with architect general locations of device and appearance.

 


 


ACCEPTABLE MANUFACTURERS




-         NOTIFIRE                              USA          ‏ ‏

          Simplex.                               USA

         Cooper- menvier                      USA









MATERIAL: 



-         Wire & conduit:

         Provide in accordance with system requirements as stated on the drawings and by the manufacturer in accordance with all-applicable codes and authorities having jurisdiction and installed in conduit throughout.



EQUIPMENT:



          Basic system equipment addressing and operating capabilities,

-         The addressable fire alarm system shall provide an individual multiplex data address for each addressable manual fire alarm station, addressable area smoke duct smoke detector, addressable heat detector, Monitor Zone addressable module and control zone addressable module...  etc

-         The fire alarm control panel shall provide standard 72, addressable data communication circuits to provide connection of and communication with the addressable devices, as required by the specifications and/or as shown on? the drawings. In order to permit future additions, no more than 80% of the addresses available on any single addressable data communications (loop) circuit shall be utilized.

-         Addressable data communicate between the fire alarm control panel, addressable interface circuit modules and addressable devices shall be digital transmissions, which shall consist of? Multiple 11 bit with start, data, and parity and stop bits. Address, parity, framing and check sum tests must be passed for any message to be considered valid. Each NFPA 72, Style 6 (class A, four-wire) addressable data communication circuit shall be capable of communicating with an addressable device up to 375 wiring meters distant and with a total up to 1,500 meters of wiring in all branches.

-         Detector bases shall be of standard type allowing any point of the detector to be plugged into any base.

-         Detectors shall include alarm indicators and provision shall be made the connection of remote visual indicators where required.

-         Detectors shall have built-in screen to prevent the entry of insects

-      The fire alarm system is to be programmable multiplex system in configuration which may connect multiple satellite addressable fire alarm control panels (AFACP) to the main fire Alarm control panel(FAP)This arrangement permits the satellite units to receive  signals from individual detectors process the information and report to the Main Fire Alarm Control Panel. The satellite panels using "Star" connection "Radial" class "A" utilizing data  Transmission cable.‏The data transmission cable between FAP and all the AFACP's shall be completely supervised for short circuits and open circuits.





Fire Alarm Control Panel(s):



          The fire alarm system control panel(s) shall incorporate all control, alarm, relay , necessary modules and components in surface mounted cabinets. The operating controls and zone/supervisory indicators shall be located behind locked steel door/Plexiglas window assemblies, with keys made available only to fire department and other authorized operating personnel.All control modules shall be labeled, all zone locations shall be identified, and the panel shall be provided with a set of permanently mounted operating instructions. The panel set door and frame assembly shall be steel. The panel shall contain system power supplies, data bus conductors, battery charger and all necessary function modules and components, including but not necessary limited to the following:







*      Master Controller Module:



          A panel shall be provided to act as central processing, indicating and control location for the fire alarm system and shall include:

-         Solid state, microprocessor based, central processing unit (CPU) which is full redundancy to process all system data and generate all system automatic alarm functions. Any addressable device or conventional hard-wired alarm initiating, supervisory or status monitoring circuit may be software programmed to

 Activate any system control relay or signaling circuit. All control-by-event programming, custom LCD display labels and alarm codes shall be stored in ono-collie solid state memory, which shall be on-site programmable.

-        Four levels of access to system control and software functions. Level 1 shall be the lowest level of access and shall not require a pass code. Levels 2,3 and 4 shall require a pass code of up to ten digits, with level 4 being the highest (most restricted) level of access. System software shall permit up to 20 individual pass codes to be programmed into the system.        

-         Solid state memory for alarm and trouble historical logs. Each log , alarm or trouble, shall be capable of storing up to 300 events with the time  and date of occurrence.

-         A module placement supervisory circuit through the data conductors.

-       80 character, alphanumeric, backlit, liquid crystal display (LCD).

-         System alarm LED indicator with alarm condition acknowledges button.     ‏‏

-         System supervisory condition LED indicator with supervisory condition acknowledge button.

-         System trouble condition LED indicator with trouble condition acknowledges button.

-        System power on LCD indicator              

-         System alarm silence button.

-         System reset button

-         Central alarm disconnects switch with "activated" LED indicator.

-         Four programmable control switches with "activation indicators.    

-         Alarm/trouble audible signal

-         Display action and data entry/control key pads.

  -       System Meter Module:

  -      The system meter module shall provide visual indication of system voltage and supervisory current. The meter module shall contain a voltmeter from 0 to 50-volt D.C for indicating system voltage. The module shall be readily disconnected for ease of servicing and placement supervised via its connection to the Master Controller Module.



-         Addressable Interface Module:    

          The addressable interface module(s) shall provide one addressable data communication circuit to enable the fire alarm control panel to communicate with the addressable devices. Each addressable data communication circuit shall provide NFPA standard 72, style 6 (class A, four-wire) supervised operation, a single open or ground fault shall not impair a circuit's operation. Addressable data communication circuit wiring shall be supervised for opens in the circuit shorts across the pair and ground faults. An addressable data communication circuit fault shall initiate a system trouble display and audible trouble signal at the fire alarm control panel. Faults on one addressable data communication circuit shall not impede operation of other circuits. The module all to be readily disconnected for ease of servicing and shall the Master controller module supervise placement. Provide available spare space in the FAP for a minimum of two future addressable interface modules.



-         Indicating Appliance Signal Circuit Module:

           The indicating appliance signal circuit module(s) shall provide two or six independently controllable alarm signal circuits. Each alarm signal circuit shall be configured for NFPA 72,style Z (class A, four-wire) supervised operation monitoring for opens, shorts or ground faults. When wired in the class A, four-wire configuration, a single open or ground fault shall not prevent the activation of the alarm signal devices. When a circuit fault is detected, the module shall light the general trouble LED on the master controller module and initiate a system general trouble condition. An individual fuse on the module shall protect each signal circuit.



-         Auxiliary Control Relay Module:

         The auxiliary control relay module(s) shall provide relays and their bases, complete with terminals for contractor wiring, for control of external equipment functions. Each module shall provide eight independently, controllable, single-pole, double-throw (SPDT) relays. Each relay shall also be provided with a supervised, status monitoring circuit to monitor the status of the controlled device (status contacts provided by others). The module shall be readily disconnected for ease of servicing and shall the master controller module supervise placement.

-         Communication Module:

           The module shall provide two communication ports with ASCII out put (adjustable baud rate) for operation of system printers and/or cathode ray tubes (CRT'S).



-        Backup Battery  :

           The fire alarm system shall be provided with battery backup capability .The batteries shall provide 24 hours of normal standby operation and 5 minutes of normal ‏‏alarm operation at the end of the 24-hours standby period. The batteries shall be monitored and high/low voltage supervised by the master controller module.

         

       Peripheral Devices:

The following material to be supplied and installed as shown on the drawings or stated in the BOQ





          System Printer: Desk-top type and shall provide the following operational capabilities:

          -permanent hard-copy record of all pertinent detail system activity. Included on this record shall be all unscheduled status change events, all operator acknowledgments of these events and all operator control commands into the system about the time and date of all occurrences.

-         The system printer record all alarm, supervise trouble condition by address number and custom label. The custom label, of up to 40 characters and spaces, time and date of alarm, supervisory or trouble condition activation shall be printed out in a language text so that the  source of the condition is clearly understood without referring the directory. Printout by address or code number only shall be as considered functionally equivalent.

-         The custom label (location message), of up to 40 characters and  spaces, for a specific device or circuit shall correspond to that displayed on the  fire alarm control panel liquid crystal display.



*        Addressable Manual Fire Alarm Station:

          Double action (lift cover and pull alarm lever), non- coded type manual station, of cast metal construction, with normally open, single-pole, single-throw general alarm contacts. The manual station shall include an addressable module which shall consist of printed circuit board with discrete for monitoring the station alarm contacts. When operated, the alarm lever shall remain in its "down" position to indicate its operation, when alarm contacts closed until the station is reset. The station shall be reset by opening the front, resetting lever and closing the station front. The station shall be tested by opening the station front and then returning same to normal. It shall be necessary to open the station to replace the break rod. A spare break rod shall be furnished with each station.



*        Analog Addressable Smoke Detectors:

          Photoelectric, two-wire, and smoke detector, shall be calibrated and adjusted for sensitivity at the manufacturer's factory to U.L. standards. Coverage area is to be 80 m2 at least when the detector installation height is 3 m. Each detector shall utilize solid state components and be equipped with a fully regulated LED light source for long life reliability, mesh insect screen, a power-on LED indicator and magnetically activated test detector electronics shall be completely shielded to protect against false alarm from EMI and RFI. Detectors shall be listed for U.L. Standard 268. Detectors shall be surface mounted, addressable base assembly with alarm LED indicator and screw terminals for all connections. The addressable base shall respond to polling signals from the Fire Alarm Control Panel and shall report the detector status. Base assemblies shall provide detector twist/lock capability. The detector may be adjusted by software for different sensitivity levels and 8 different verification times, which may be changed by time of day program.



*        Analog Addressable Heat Detect:

  

          Shall be two-wire combination rate of-rise alarm function and fixed temperature element heat detector. Activation of the rate-of-rise or fixed temperature alarm functions shall be self-restorable when the ambient temperature stabilizes. Each detector shall utilize solid state components and shall be listed for U.L. Standard 521. Detectors shall be provided with surface mount, addressable base assembly with an alarm LED indicator and screw terminals for all connections. The addressable base shall respond to polling signals from the Fire Alarm Control Panel and shall report alarm or trouble status changes. Base assemblies shall provide detector twist/lock capability.

          Detectors operate on the bi-meta principle. The bi-metallic disc assembly, should be protected from accidental damage, but remains sufficiently open to the air to be triggered when the temperature of the   later coincides with the predetermined setting of the device. At such moment the sensor disc "snaps over" and closes a pair of gold-plated contacts, there by activating the alarm.  The sensor disc assembly and the contacts are fully enclosed, so Dirt, dust or moisture cannot impair their functioning.  Protected area for heat detector under normal value of environment should not be less than 60 square meters with ceiling height of 3 meters.

         

*        AnalogIonization Smoke Detector:

          The Ionization smoke should be sensitive to small particle size range for aerosols, dusts and fumes; the range in microns is 0.01 to 1.0. Detector consists of two ionization chambers and one source together with the necessary related amplification circuits. The air within the chamber is made electrically conductive (ionized) by bombardment of the nitrogen and oxygen particles with alpha particles emitted by minute source of radioactive material. A voltage applied across the ionization chambers causes a very small current to flow as the ions travel to the electrode of opposite polarity. One chamber is substantially closed to the atmosphere and provides compensation for long term variations in temperature and humidity. The other chamber is open, and when visible or invisible combustive particles enter the chamber they attach themselves to the ions and cause a reduction in mobility and thus a reduction in current flow. The reduced flow change of the electrode voltage which reaching a pre-determined level, results in an alarm.



*        Bells:

          Area bell is an audible warning of dangers such as fire, these bells are suitable for flush, surface or plaster depth mounted ‏‏ ‏

-         Bells can be set to produce of three distinctive sound permitting the use to three sounders for different purposes in the same area.. Bells shall have facility frequency adjustment to break   through various background noises. Heavy duty weatherproof housing frequency range 600-5000Hz. Operation of the sounder unaffected by high humidity industrial or dust .Bell sound output is to be 96 db at 10 ft. at least



*        Monitor Zone Addressable Modules:        

          Shall be individually addressable alarm  initiating/supervisory circuit board(s) and shall consist of printed circuit board with discrete circuitry for monitoring normally open, dry contacts using NFPA 72,Style D (Class A, four-wire) circuit supervision. The monitor shall respond to polling signals from the Fire Alarm Control panel and shall report alarm initiating/supervisory circuit status changes to it. The monitor shall include a field programming capability for the assignment of its individual address number and clamp-type terminals for making wiring connection. The monitor shall draw its power from the Fire Alarm Control Panel via a separate power circuit. The monitor shall be furnished for flush mounting or surface mounting.    



*        Control Zone Addressable Modules         

          Shall be individually addressable control relay and shall consist of printed circuit board with discrete circuitry for controlling one individually addressable control relay with Double-Pole, Double-Throw contacts.  The control shall respond to control signals from the Fire Alarm Control Panel. The control shall include a field programming capability for the assignment of its individual address number and clamp-type terminals for making wiring connections. The control shall draw its power from the Fire Alarm Control Panel via a separate power circuit



*        Control-Monitor Module Units    

          The control-monitor module units are simply an interface between the conventional type detectors located in an area and the addressable fire alarm panel. The unit shall be capable of monitoring the number of the detector located in its relevant area and hence report to the fire alarm control panel the status of area. It shall be also capable of controlling any equipment located in this area that might be required to be controlled through the fire alarm control panel individually (e.g. bells).






   *   The Fault Isolator Device

           Shall detect and isolate a short - circuited segment of a fault-tolerant loop.

-         The device shall automatically determine a return to normal condition of the loop and restore the isolated segment. of a fault - tolerant loop         

-         Devices  shall be placed every 20 devices to limit the number lost in the event of a short - circuit

-         Circuit as shown on the drawings.

-        End of line resistor shall used in the flats zones





Unit Price

*        Provide, as part of written bid proposal, a unit price for each of the peripheral devices as described above.

*        All Unit prices are to reflect the current prices of specified equipment and remain as the purchase price for a minimum of one year from the date of contract bid as assigned by the engineer.

*        Bids for this contract will not be accepted without unit prices in written proposal form.



INSPECTION:



          Examine areas conditions under which fire alarm system is to be installed. Notify Owner in writing of conditions detrimental to proper completion of the work. Do not proceed with work until unsatisfactory conditions have been corrected.



INSTALLATION

         

Install fire alarm devices, wiring and main equipment as indicated, in accordance  with manufacturer's written instructions,   requirements of applicable Standards, and NECA's "Standard of  Installation , and in accordance with recognized industry practice to ensure that the installation complies with requirements and serves intended function. Coordinate as necessary to interface installation of fire alarm system with other work. Protect all equipment from dirt, moisture and construction debris, subsequent and during installation until project is accepted by Owner.. Contractor to furnish all conduit, wiring, out let boxes, junction   boxes, cabinets and similar devices necessary for a complete installation. All wiring types as recommended by the manufacturer installed in conduit throughout or as approved by the local Fire Department. Junction boxes to be painted fire department red for identification.



All final connections between system equipment and the wiring shall be made under the supervision of a trained manufacturer's technical representative.



          Wiring within component enclosures and terminal cabinets: All wiring shall be installed in a neat and workmanlike manner and shall be trained parallel with or at right angles to the sides and back of any enclosure or cabinet. All circuit conductors broken, spliced, or connected in any enclosure, cabinet, mounting or junction box shall be connected to terminal blocks with each terminal cabinet shall be installed where any pad lugs or with approved pressure type terminal blocks.

          A terminal cabinet shall be installed where any circuit tap is made and must be painted fire department red. All wiring within the enclosure shall be readily accessible without removing any component parts.



          System Field Wiring: Field wiring shall be solid copper sized as required. Wiring connecting the power supply shall be minimum No. 12 AWG size conductors. All conductors shall? be installed in rigid heavy metal conduit or electrical metallic tubing run surface or concealed and as required by applicable codes. Each conductor used for the same specific function shall be distinctively color coded.Wiring for the fire systems shall be installed as herein described and separated from any other wiring systems.

          CLEAN UP Upon completion of the installation, all debris created by the   installation shall be removed from the premises or disposed of as directed by the Owner,





 FIELD QUALITY CONTROL



          Upon completion of installation of fire alarm system and after system has been energized, test equipment to demonstrate compliance with requirements.  Correct or replace defective equipment, and retest.

          A factory trained technician to supervise the final connections, tests and adjustments of all equipment upon completion. Each device to be tested by the manufacturer's representative, in the presence of the owner's representative; a test report completed in triplicate,and signed by the owner's representative to indicate that he witnessed the testing of the system. A copy of the test report shall be posted adjacent to the fire alarm control equipment and enclosed in a glass directory stainless steel   frame.



          Upon completion prior to all acceptances, perform complete system tests as follows:

-         Actuate all manual and automatic alarm and monitor initiating devices one at a time and verify proper operation.



Verify  ‏:  

         a.‏            Operation of all signaling and indication system as specified including prozone identification and labeling at the fire alarm control panel.

          b             Fan shut-down and smoke purge sequences

          c .           Transmission of alarm to security office

          d .‏           Manual control of items as specified

          e.           Class and type of wiring                            

          f-            Automatic operations of specified items.



-         Verify operation of standby power sources as follows:

          a-            Remove primary power and check for battery operation as specified

          b-            Remove primary power and check for automatic switchover to secondary source.

          c-            Check for proper sequence and priorities.

Submit 5 copies of test data and results, signed by test personnel.

Correct or adjust items not found acceptable by authorized representative.

Repeat tests indicate corrects items.



GUARANTEE


            

All components, parts and assemblies supplied by the manufacturer to be guaranteed against defects in materials and workmanship for a period of 12 months from owner and fire department acceptance. Equipment manufacturer to have a local branch office staffed with trained, full-time employees who are capable of performing testing, inspection, repair and maintenance services for the life of the system. Contractor to guarantee all wiring to be   free from inherent mechanical and electrical defects for one year. The manufacturer to furnish a one-year maintenance contract, free of charge to the owner, effective from the date of installation for maintenance and inspections of the manufacturer's equipment; with a minimum of two inspections during the contract year. A local manufacturer service department which stocks standard parts to be available to the owner. If required, maintenance is to be performed during normal working hours, at no cost to the owner, for a period of twelve months from the completion date of the installation, unless damages caused by misuse, abuse or accident.





         SERVICE AND MAINTENANCE the equipment manufacturer shall make available a fully equipped service organization, capable of guaranteeing an on-site service response time within 12 hours to a service request call. Site service shall available 24 hours per day and seven days per week. Part of this contract, the contractor shall receive from the equipment manufacturer and turn over to the owner to the following system spare parts:

-         50% spare of each type of fuse

-         30% spare of each type of lamp (excluding LED type)

-         10% spare of each type of alarm initiating device.

-‏         10% spare of each type of alarm signaling or indicating device.



3.14.2 TELEPHONE SYSTEM


3.14.2.1Description of Work

Provide a telephone system as specified and as shown on the relevant drawings. The telephone system shall include the supply and installation of PABX, operator consoles, call accounting system, cables, terminal cabinets, and conduits….etc.

Telephone outlets shall be provided as shown on drawings.

3.14.2.2 Codes

The following list identifies organizations that publish codes, standards and manuals referenced herein. The latest editions of these documents at the time of contract award shall apply .

1.         ISO                               International Organization for Standardization                                                      1 Rue de Varembe

CH-1211 GENEVE 20

2.CCITT                                     International Telegraph and Telephone Consultative Committee, International Telecommunication Union,
CH- 1211 GENEVE 20









3.14.2.3            Quality assurance:

Manufacturer:

The system manufacturer shall be one of the firms well know as system manufacturer of similar type, size and quality as required and as specified here in. The manufacturer shall have similar systems operating in a satisfactory condition for at least 10 years. The list of approved manufacturers in this section indicate the minimum quality and standard of equipment that will be acceptable. Equipment of unlisted manufacturers having equivalent repute and standard shall be considered by the Engineer on an equal basis. In this respect the Engineer’s decision shall be final and not subject to any justification whatsoever.

Approval of a manufacturer does not necessarily constitute approval of any particular one of his products as conforming to Specification. It shall be the contractor's responsibility to ascertain that the approved manufacturer is capable of supplying the required systems in full conformity with the Specification and the Drawings.

Equipment from approved manufacturers will not be accepted unless such manufacturer has a local organization maintaining an adequate staff of specialists qualified in the systems for engineering assistance, maintenance or repair. Repair and maintenance service must be available on demand or contract basis.

Installer


The system installer shall have a previous experience to install such system. The installer record must show at least three similar systems of similar size and quality, which had been installed, with no technical problems.

Submittals


Product Data: The Contractor shall submit product technical data for telephone equipment and network.

Samples           :  The Contractor shall submit product technical telephone cables, frames, sockets, and sets…. etc.

Shop Drawings: The Contractor shall submit detailed workshop drawings illustrating all technical data required for complete installation.

Detailed wiring diagrams for the system including internal wiring of individual components.

Actual wiring layout and cable routing, with indication of actual position of all outlets, boxes, devices. etc… as well as equipment layout .

No equipment for witch shop drawings are required shall be ordered or installed unless all such drawings have been reviewed and approved by the engineer.

"As -Built" Drawings:

"As-Built" Drawings shall be submitted as called for in the Tender Documents at no extra cost for the contractor.

INSTRUCTION MANUALS:

Provide the Engineer with three complete sets of instruction manuals and schematic and wiring diagrams covering operation, maintenance and supply of spare parts opera for the system. These shall be in English

INSTRUCTION IN THE USE OF EQUIPMENT:

All equipment and all operating components and controls shall be demonstrated to the owner's personnel so that they fully understand the proper operation of the systems Instruction manuals and wiring diagrams shall be submitted prior to this demonstration.

1.4.2.3  GENERAL REUIREMENTS

All work related to the telephone system shall conform to the requirements of the public Telephone Authority system, with which the Contractor shall acquaint himself.                                                      

Workmanship and materials in connection with the telephone system shall be to the applicable requirements of the various sections of the unless otherwise specification, specified or shown on the Drawings

The telephone equipment supplier shall be the authorized distributor of the approved manufacturer and must maintain a local staff of specialists for engineering assistance, maintenance and repair.

The telephone system should be the latest model in design currently produced by the manufacturer.

SCOPE OF WORK

The work covered under this Section of the Specification shall include but not be limited to, the following: Main Distribution Frame (MDF), Electronic Private Automatic Branch Exchange (PABX), operator consoles, battery and charger, telephone sets, telephone terminal cabinets and boxes, telephone outlets, complete network and wiring installation and complete installation including all accessories required for a complete working system ready for service of the premises.



3.1.4.2.5 PABX SPECIFICATIONS

General

The PABX shall be solid state, pulse code, Modulation, electronic stored program controlled, time division multiplexes switching.

The PABX shall be of the modular, plug-in type, fully tested at the factory All components shall be located in compact accessible cabinets

The PABX shall have:-

Internal (extension) lines                   : as shown on the drawing

External (trunk) lines                         : as  shown on the drawing

Operator Console                             : TWO

The PABX shall be flexible and shall be easily expanded without modifying or obsoleting any part of the existing installation.

The system should provide complete redundancy of the common controls. This includes the processors, common control, and memory units' hard disk and switch matrix.

Construction: -

The PABX shall be of the metal cabinet design, with hinged doors and completely dust-proof.

All metal surfaces internal to the equipment and not normally visible from the exterior shall be suitably protected against corrosion.

All external metal surfaces shall be treated, prior to finishing, with metal spray galvanizing, plating, or other approved surface treatment and shall then be primed or otherwise treated to provide a first class base for Duct- Enamel or a similar finish.

The PABX cabinets shall contain all the switching equipment such as the controls, connecting sets, service panel, service terminal and speech path network.

All semi-conductor devices shall be encapsulated in hermetic packages The system shall be designed in such a way that very low humidity shall not damage the semi-conductor devices The devices shall be protected against any static discharges.

For printed circuits boards, the laminated material shall preferably be of epoxy glass filament The conductor width and spacing shall guarantee a high quality product, reliable under extreme circumstances, at the chosen voltages and currents Adequate protection against corrosion of copper conductors shall be applied.

Where plugs and sockets are used, reliable pressure connectors shall be provided.

The PABX shall have the maximum flexibility for expansion of facilities and also amendments to facilities This shall be done without interruption of service.

All control functions shall be performed by LSI microprocessors and mini processors.

The peripheral functional units, such as the connecting sets and line system, shall utilize complementary MOS or C-MOS circuit components.

All circuits shall be accommodated on one-or two row plug-in card modules and connected electrically to one or two-row, nodule frames via multi-contact plugs. The module frames shall be interconnected via multi-contact plug-in cables which shall be accessible from the rear and housed in cabinets

Faulty plug-in cards shall be replaceable without any interruption to the remaining equipment.

The capability shall be provided for station numbers to be assigned to lines at the time of installation in accordance with a customer-desired numbering plan and to permit reassignment while in service to permit personnel moves without renumber changes. The numbering system shall utilize a three or four digit numbering plan which shall be changeable without hardware or wiring alterations.

Grade of service: -

Incoming traffic                           :     P = 0. 01

Outgoing traffic                             :    P = 0 .01

Internal traffic                                :    P = 0.01

Traffic capacity per line = more than 0.16 Erlang.

System Characteristics:-

The PABX shall be capable of interfacing with the local PTT Protection shall be provided for all station loops and central office trunks against over-current.

The PABX shall be in full compliance with CCITT recommendations and shall have at least the following specification :-

Switching technique                              :all solid state digital switching using PCM and time division    multiplex

Extension lines impedance                    : 600 Ohms

Trunk lines impedance                           : 600/90 Ohms

Insertion loss                                        : less than 0 6 db at

: 800 Hz, less than 15

                                                            : Db between 300 and 3400 Hz

Cross-talk attenuation                            : more than 75 dB

Extension loop limits                             : 1200 Ohms including

           : Telephone set.

Leakage impedance                              : More than 20 k ohm

Traffic capacity                                     : more than 0 16 Erlang

            : per extension

Power requirements                               : 220 V + l0% A.C.

Primary Power                                        : Single-phase, 50 Hz.                          

Battery                                                  : 48 V.D.C nominal, +- 12%.

The system shall be designed to operate in the following environment

Ambient room temperature                     : 0 to 50 degree

 Relative humidity                                  : 10to90%

 Ancillary    Equipment :-

Diagnostic maintenance console and printer: this shall be provided and installed near the PABX. This panel shall be used for the input and display of user data, test and management functions and shall be protected against misuse by means of a keyword Faults shall be indicated on this panel.

3.14.2.6 SYSTEM FEATURES AND CAPABILITIES

A1        Abbreviated Dialing (speed Calling)

Possibility for the extensions and operators to make external calls by dialing short codes which are automatically translated to the appropriate number.

A2        Inward Calls (Incoming Calls)

These shall be handled either by the operators or by specific extensions programmed for direct-in-lines or by the wanted extensions through in-dialing facility.

A3        Direct-In-Lines

One of the trunk groups can be programmed for direct in-traffic 1.e calls on these lines are then routed to predetermined extensions or to group of extensions ir-respective of whether the exchange is switched for night service or not.

A4        Group Hunting

A group of extensions can be called by a, 2 or 3 digit number. Incoming calls are routed to a free extension in the group, either with sequential hunting or evenly distributed to the extensions or to a common bell.

A5        Automatic Call Back

This facility allows the extensions to be automatically called back when the wanted extension becomes free.

A6        Call Waiting Tone

This facility allows the extension to send audible tone to the busy extension as indicate that a new call waiting.

A7        Call Diversion/Follow Me

Possibility for extension to direct their incoming calls either to common answering point or individually to pre-assigned extensions and could be affected directly or on no answer or on busy.

A8        Call-Pick Up

Possibility for an other extension to answer calls to any other extensions.

A9        Night Service

Night service means all incoming calls shall be routed to either common extension or to group of extensions or to common bells or individually to pre-assigned extensions. Night service ms activated when all operators have marked their consoles "un-attendant"     In the meantime automatic switch over to night service takes place if a call has not been answered within 60 seconds. Common and individual night service can be combined.

A10      system Dialing

The system shall allow push button DTMF dialing, decadic dialing, as well as digital dialing

All        Flexible Extensions Class of Service

It will be possible to assign any of the above mentioned facilities as well as any of the following class of services to any extension without any limitation.

-           Allowed for all types of external calls (open)

-           Allowed for external calls within limits of trunk call discrimination programmed.

 -          Allowed for external calls via operators.

 -          Not allowed to make any external calls.

A12      Music on Hold

Possibility to send music for waiting calls or parked calls by using external music source.

A13      Last Number Redial

Possibility for extension to redial the last dialed external number using simple procedure.

A14      Paging system Interface

Possibility to interconnect the proposed system with wireless paging system.



3.14.2.6 ATTENDANT CONSOLE FEATURES

The PABX shall be provided with the attendant console having at least the following characteristics:-

The operator console shall be of a type integrated with the P.A.B.X.

Equipped with a light weight handset and cradle, which can be mounted on either side of the console body. The jacks provided shall be also suitable for connection of handset and/or headset.

A tilt and swivel base complete with keyboard provided with various types of push buttons for control of such functions as break-in (BKI), conference (CONF), night operation (NT) aothers

Designed to take full advantage of the PABX system's flexibility and to provide the attendant with everything to most efficiently handle even the heaviest traffic and have complete control of all calls at all times A quick glance should identify the nature of a call (e 9 whether an incoming call is internal or external, or special service) Visual indication of the busy or free condition of station lines via LED lamps shall be included.

Able to operate in a load sharing mode with other future console.



3.14.2.7 REUIRED ATTENDANT FEATURES

The attendant shall be provided at least with the following facilities: -

-           Be able to check the status of any Individual trunk or extension Line.

-           Ring when free for external call transferred to a given busy extension.

-           Automatic return to operator if an extension does not answer an outside call within 30 seconds.

-           Automatic return to operator of a transferred outside call, if an extension remains busy for 30 seconds.

-           Timed remainder: the attendant shall be automatically alerted after 30 seconds when an internal or outside call on the console ms waiting.

-           The transfer of an incoming call to the wanted extension shall be made by a pushbutton key set.

-           Priority: to interfere in established communications for special announcements or transfer of incoming international calls A warning tone shall be sent to both conversing parties.

-           Splitting to consult privately with one party on a call without the other party hearing.

-           To connect any internal extension or outside trunk line with any other internal extension. In particular, to place an outgoing call for a station user who reached the attendant, without requiring the station user to hang up.

-           Conference: to establish a multiparty conference connection between six conferees.

-           Attendant control of extension access    to restrict any extension from access to trunk lines or to any other extension.

-           Controlled restriction: to prevent selected station lines or groups of lines from originating and receiving This feature is used to temporarily disconnect lines. when activated, calls are routed to the attendant.

·                                                Display of held calls details.

·                                                Category calls waiting indication.

·                                                Total calls waiting indication.

·                                                Serial call.

·                                                Call by name.

·                                                Do not disturb set-up cancel and check.

-           Trunk groups: trunk lines shall be divided into groups. Such groups shall include (a) trunks for receiving external calls, (b) trunks for outward dialing (c) trunks for attendant's use etc. The attendant shall be able to divert any trunk line one group to another to cater for heavy traffic within one trunk group, also to access any idle trunk line in any group, all executed by push-button controls on the console.

-           Listed directory number (LDN) service incoming trunk calls to the PABX via the assigned listed local telephone directory number shall be directed to the attendant the attendant will complete these calls.

            Night station service: arrangements to route calls normally directed to the attendant, to a reselected station or group of stations within the system when night service is activated. From this station transfer to other wanted stations shall be possible. The routings to wanted stations shall be assigned on a flexible basis by the attendant and will remain in effect every after night until changed.

3.14.2.8 STATION FEATURES

The PABX shall be designed to provide, but not necessarily be limited to the following station features:

Station-to-station calling: the station user shall be able to directly dial other stations within the PABX system without the assistance of an attendant.

Direct outward dialing (DOD):  A PABX station user shall be able to gain access to the exchange network without the assistance of the attendant by dialing an access code and receiving a second dial tone the user may then proceed to dial the desired exchange network number.

Executive override (break-in):  a station user shall be able to enter an existing two-party busy station connection. This intrusion is proceeded by a warning tone If person called the called released his line, he is automatically called releases his line, he is automatically called back.

Automatic diversion: Calls destined to a station will be routed to another station designated during activation, whenever the called station is either busy or does not answer.

Automatic call back:  if the internal extension called is busy, this facility makes it possible to dial a digit and to hang up. The two telephones are automatically called back as soon as they are simultaneously free.

Inquiry Call a telephone user in conversation with the outside can put his communication in hold, dial an internal number to request information and then take back the first communication. The conversation shall be secret.

Call transfer: enables any extension on the installation to directly an external communication to another extension without going through the operator.

Single-digit dialing: a station user shall be able to call any of a reselected group of stations by dialing single digit codes

Manual service: selected stations shall be automatically routed to the attendant position, for connection, when the station user goes off-hook for service Dial tone shall not be provided to these stations and connections to other extensions or to trunk lines shall be made by the attendant.

Dial access to attendant: Station users within the switching system shall be able to reach the attendant by dialing a single digit. The attendant may complete these calls to trunk facilities or station lines.

Conference (meet me):    enables six parties to have conference through their telephone sets. One of them may be external.

Privacy: Provides the station user with security against any audio intrusion on calls (e .g. camp -on tone, override etc.)

Line lockout with warning:  provides 10 seconds of warning tone and then holds the line out of service when a station line remains off-hook for longer than 10 seconds without dialing The hold out-of service shall be released when the station goes on-hook.

Through dialing: at the discretion of the attendant, station users complete dialing after the attendant connects them to a trunk line.

Splitting a station user shall be able to consult privately with one party on a call without the other party hearing.

Internal call transfer: a first internal correspondent may be put into HOLD, a second one called to make an inquiry and then the first one may be taken back again or transferred to the second party.

3.14.2.10           Administration Extension Group

The directory numbers of extensions of this group shall be "3 or 4" digit number.

Some of these service quarters shall provide with digital display telephone showing the number of the calling extension, calling name and language.

3.14. 2.12          Message Waiting

All room telephones shall be equipped with message waiting lamp.

Message from front office, from administration or from voice mail system will alert the telephone lamp.

The patient via simple procedure shall be in contact with those who set up these messages.

3.14.2.14.          Do Not Disturb (DND)

Possibility to inhibit , incoming calls to the room telephone the DND function can be in or cancelled from patient telephone, PABX operators, or from front office terminal.

Activation of this function should not block the telephone from initiating any type of calls.

In case of urgency the operator can by-pass this function and transfers these urgent messages.



3.14.2.15 PMS Interface:

The telephone system shall be interconnected with the property management system (PMS) through full bi-directional communication interface.

The PMS interface shall provide full integration with the software
 (S/W) of PMS.

3.14.2.16 Call Blocking

The system shall allow total or partial restriction on patient to patient calls during nighttime.

3.14.2.19           BILLING SYSTEM (option)

The system should be able to report all calls made from each internal line periodically

Information should include number dialed, duration, date, time of call and cost at the administration company rates.

3.14.2.20           COMMON CONTROLS:

The system should be distributed processor technique. Switching equipment and rectifiers The redundancy shall be of the "Hot Standby" type with no interruption of service or loss of calls.

3.14.2.21           SYSTEM FAIL TRANSFER

This system shall support 8    SFT circuits as a minimum which will switch exchange lines through the dedicated extensions in case of PABX failure.

3.14.2 22           POWER:

Normal power available is 220 V, single phase 50 Hz.

Power supply system shall consist of a rectifier and batteries provided to supply continuous DC power to the PABX The batteries shall be floated on the load side of the rectifiers and kept continuously charged.

Rectifier:

The rectifier shall be solid state and of sufficient capacity to supply the required power to the PABX and maintain the batteries in a fully charged condition. The quality of the output voltage shall be within the required limits of the PABX.   The shall include input and output circuit-breakers, alarms for over-temperature, loss of input power and low battery voltage, input voltmeter and ammeter output voltmeter and ammeter.

Batteries:

The batteries shall be sealed lead acid and shall be provided with all necessary hardware and wire for interconnection .A suitable mounting rack shall be provided for battery installation.

Outage Time:

The power supply fed via batteries shall permit eight hour of continuous operation without loss of features or a reduction in system capacity in case of failure of normal power.

Recharge:

Following the restoration of normal power the batteries shall be returned to 90% of full charge in 12 hours.

3.14.2.23           MAIN TELEPHONE TERMINAL CABINET

The terminal cabinets shall be of free-standing type and shall have capacity of cults for extensions 1000 pairs for the cabinet all circuits for extensions and trunks shall be fully protected against over-voltage and over-current.

Terminals shall be identified by numbered tags corresponding to the respective lines or extensions. The contractor shall submit the proposed numbering scheme for prior approval by the Engineer.

All internal and external lines shall be connected "plugged" into the terminal cabinets No soldering shall be required.

3.14.2.24           TELEPHONE NETWORK

Telephone equipment wiring shall be completely segregated from any other system.

Permanently fixed wiring of the telephone network shall comprise color coded PVC insulated copper conductors 0 6 mm diameter, pulled inside PVC conduits, or PVC insulated and sheathed cables on cable trays or inside trucking as appropriate Multi-pair cable assembly shall be covered with binder tape, an extruded PVC belt, spirally wound copper shielding tape (or aluminum foil of equivalent section) and on overall PVC sheath.

Two-pair telephone cable shall be used for final connection from terminal cabinets to the telephone outlets For flats four-pair telephone cable shall be used for final connection from terminal cabinets to the telephone outlets.

Console set shall be installed with concealed wiring and shall be wired directly from the main distribution frame via multi-pair cables. The range shall be at least extendable to 100m without any special equipment. The multi-pair cable shall be of 0.6 mm standard telephone distribution cable type.

Wiring shall be arranged and connections made on solder less screw type terminal strips of high insulation phenolic material using non-ferrous screws and connectors inside easily accessible boxes and shall allow ease in sectionalization and checking of the system for maintenance and repair.

3.14.2.25 TELEPHONE TERMINAL CABINENTS

Telephone terminal cabinets shall have a general purpose, lockable type enclosure for surface or concealed mounting at locations as indicated on the drawings. Telephone terminal cabinet's sizes arte indicated in the telephone schedule.

Telephone cabinets shall be dust proof and shall be designed to hold the terminal elements, such as screw terminal strips, the jumpering wires and the split up ends of incoming installation cables and conduit terminating therein.

Screw type pressure terminals shall    be mounted in a mounted plastic body. Two captive screws shall be arranged in the two mounting holes of the body. The nickel-plated brass terminals shall be designed for screw connection on one side and soldering terminals shall be tinned Screw connections and/or soldering terminals shall accept conductors with diameters between 0.3 and
1 mm.

Telephone cabinets shall consist of a back box, 20 mm wood shall be backboard bolted-on frame, door lock. Enclosure made of galvanized sheet steel, painted grey.

3.14.2.26 TELEPHONE SOCKETS

All telephone sockets shall be type RJll the cable connection to the RJll socket shall be screw type all telephone outlets indicated on the drawings shall be doublex socket.

16.14.2.27 APPROVED MANUFACTURERS

-           MITEL                           (CANADA, U K)

-           Northontelecom             (CANADA, U K)

-           SIEMENS                     (GERMANY)

Or approved equal.

3.14.2.28 EXECUTION

Examine conditions where telephone network system is to be installed. Notify in writing of conditions detrimental to proper completion of the work do not precede with work until unsatisfactory conditions have been corrected.

3.14.2. 29 INSTALLATION

Install telephone raceway system and raceway system as indicated, in accordance with manufacturer's written instructions, requirements of applicable Standards, requirements of the telephone company and in accordance with recognized industry practices to ensure that installation complies with requirements and serves intended purpose.

Coordinate as necessary to interface installation of the telephone raceway system.

Limit bends in conduit for Telephone Company wiring between junction boxes, pull boxes, cabinets, or other cable access points to no more than two 90° bends maintain a minimum radius of 1 meter for all runs other than branch runs to outlets.

Provide power supply for telephone rooms, telephone closets, and public booths.



3.14.2.30 FIELD UALITY CONTROL

Upon completion of telephone raceway system, test system to demonstrate compliance with requirements. When possible, field-correct defective equipment, then retest to demonstrate compliance Replace equipment which can not be satisfactorily corrected.

GURANTEE

All components, parts and assemblies supplied by the manufacturer to be guaranteed defects in materials and workmanship for a period of 12 months from owner acceptance.

Equipment manufacturer to have a local branch office staffed witrained, full-time employees who are capable of performing testing, inspection, and repair and maintenance services for the life of the system.

Contractor to guarantee all wiring to be free from inherent mechanical and electrical defects for one year. The manufacturer to furnish a one-year maintenance contract, free of charge to the owner, effective from the date of installation for maintenance and inspections of the manufacturer's equipment, with a minimum of two inspections during the contract year. A local manufacturer service department, which stocks standard parts to be available to the owner. If required, maintenance is to be performed during normal working hours, at no cost to the owner, for a period of twelve months from the completion date of the installation, unless misuse, abuse or accident causes damage.

SERVICE AND MAINTENANCE

The equipment manufacturer shall make available a fully equipped service organization, capable of guaranteeing an on-site service response time within 8 hours to a service request call. Site service shall be available 24 hours per day and seven days per week.

SPARE PARTS

The contractor shall submit a recommended list of spare as recommended by the manufacturer indicating the unit price for each item. The spare parts shall be suitable for at least three years of operation.



  Computer Network



            Scope Of Work

- Supply from only one manufacturer , Install& test- using fluke tester-  a data network in 

  the building.

- All the computer outlets will connected with UTP CAT6 cables.     

- The computer network shall cover all data outlet location shown on the drawings   and 

  shall be in accordance to the system manufacturer recommendation, any  proposed  

  deviation shall be clearly stated by the contractor in the tender.

All cables shall be terminated and labeled on patch panels placed in the 42'' data rack  in the Low current  closet and in the other side will be terminated and labeled through termination box with coupler.



            The Passive Components Requirements:



-          The components such as patch panels, patch cords , face plates and cables shall be UTP CAT6 type.

      -    All cables shall be terminated on one main cabinet, which   will  also have the active  &   passive

            components .

-          The patch cords – pre assembled patch cords - which connect the face plate with the  PC Workstation   & also connect  the patch panels to the switches are patch  cord of   lengths 1 & 3 meters.

-          42'' metal rack complete with 4 fans, 2 power strip ,earthing kit & cable guide

    

·              Cables Shall Be Of The Following Specification:



-          For indoors cables running in conduits, cables shall be get filled buffer tubes.



-         The indoor fiber optics cables specs 62.5/125 4c indoor/outdoor non metal.



·              The Active Components Requirements:

-      The active components are switches with fiber optics ports which  support  1000MB 

      Per second speed.

-      The NIC cards also must support 1000 MB per second speed.



·              Approved manufacturer

             For passive components 

·              Avaya           USA

·              Nexanes       France

·              3M                 USA

             For active  components 

·              ceisco          USA

or equal approved



GUARANTEE REQUIREMENTS




The supplier guarantee all operating equipment and material specified Here in to be suitable and proper for the use included and without Charge make replacement of any operating equipment or material which on return to the manufacturer or this representative, within for period of not less than five years, from date of commissioning proves upon examination to be defective in material or workmanship .








3.14.4 SOUND PUBLIC ADDRE SS& EVACUATION SYSTEM

3.14.4.1 GENERAL

The contractor shall supply and install a completely integrated central background music/paging system as herein specified and as shown in the plans .The system will provide background music and public paging in corridors and public areas, basement floors, and other areas as shown in the drawings.

This work shall include all material, equipment and labor necessary to make the system complete in every respect and ready to operate.

To ensure system quality, system shall be as shown on the riser diagrams

All equipments shall be UL listed and of modular 19" rack mount type.

All work shall be carried out in accordance with internationally accepted practices.

The System wiring shall be completely separated from any other system.

The drawings issued with the specification indicate the approximate location of all apparatus The exact and final location shall be subject to the prior approval of the Engineer.

Provide with the tender a schedule of all equipment to be supplied with a recommended layout of the system.

The contractor shall forward his compliance with this specification item by item and any section that he wishes to amend or cannot comply with, shall be clearly defined.

System shall be specially designed for paging in specified areas and shall consist basically of the following:

-           Two electro chime units with microphone

-           Metal racks which shall incorporate

-           Preamplifiers

-           Power amplifiers

-           Main distribution panel

-           Loudspeakers

-           Wiring and accessories necessary for excellent operation of the system.

3.14.4.2 Quality assurance:

-           Manufacturer

The system manufacturer shall be one of the firms well know as system manufacturer of similar type, size and quality as required and as specified here in The manufacturer shall have similar systems operating in a satisfactory conditions for at least 10 years The list of approved manufacturers in this section indicate the minimum quality and standard of equipment that will be acceptable Equipment of unlisted manufacturers having equivalent repute and standard shall be considered by the Engineer on an equal basis.   In this respect the Engineer's decision shall be Final and not subject to any justification whatsoever.

Approval of a manufacturer does not necessarily constitute approval of any particular one of his products as conforming to Specification. It shall be the contractor's responsibility to ascertain that the approved manufacturer is capable of supplying the required systems in full conformity with the Specification and the Drawings.

Equipment from approved manufacturers will not be accepted unless such manufacturer has a local organization marinating an adequate staff of specialists qualified in the systems for engineering assistance, maintenance or repair. Repair and maintenance service must be available on demand or contract basis.

Installer

The system installer shall have a previous experience to install such system The installer record must show at least three similar systems of similar size and quality which had been installed with no technical problems.

Submittals

The Contractor shall submit samples from loudspeakers, cables, boxes ….. Etc

Product Data: The Contractor shall submit product technical data for telephone equipment and network.

Shop Drawings: The Contractor shall submit detailed workshop drawings illustrating all technical data required for complete installation

Detailed wiring diagrams for the system including internal wiring of individual components.

Actual wiring layout and cable routing, with indication of actual position of all outlets, boxes, devices. etc….. as well as equipment layout.

No equipment for which shop drawings are required shall be ordered or installed unless all such drawings have been reviewed and approved by the engineer

"As-Built" Drawings:

"As-Built" Drawings shall be submitted as called for in the Tender Documents at no extra cost for the contractor.

INSTRUCTION MANUALS:

Provide the Engineer with three complete sets of instruction manuals and schematic and wiring diagrams covering operation, maintenance and supply of spare parts for the system. These shall be in English.

Voice message unit shall also be installed to be used for emergency message storage and broadcasting

A microphone compressor preamp shall provide uniform volume level and maximum "talk power" for voice paging.

An adjustable time clock switch shall automatically turn off power during early morning hours to the central background music/paging system rack Emergency announcement control will bypass the timer.

All amplification equipment shall be solid-state No vacuum tube powered equipment shall be considered acceptable.

All rack mounted amplifiers shall be interconnected by means of normal through jacks for quick circuit access and ease of testing, as well as for rapid amplifier substitution in the event of failure. A standby distribution amplifier shall be rack mounted and powered for this purpose.

Two high quality FM/AM tuners, a background heavy duty music tape player, and compact disk player (6 disks) shall be used.

Each amplification channel shall include: separate low and high frequency tone equalization, control of distribution volume level   and oral and visual means of monitoring program level and quality.

In the event of an emergency announcement, relating to fire, or other life safety consideration, all distribution zones shall automatically drop their program sources and transmit the emergency announcement.

Two relay power supplies shall be interconnected by means of steering diodes for fail-safe operation. Either supply shall be rated to handle the entire system emergency relay load.

A Switch panel shall be provided at the central background music/paging system rack to isolate the individual vertical feeder pairs and the public area feeders from the system. Switching shall be accomplished by means of a 2 pole, 3 positions lever switch designated "off-normal-test"

Channel feed isolation switch (one per channel) shall permit pre-setting and adjusting a channel prior to distribution.

3.14.4.3 SYSTEM PERFORMANCE SPECIFICATIONS

FM-AM Tuner :                                     

       FM frequency response                  20 Hz to 15 KHz + 1 dB

FM harmonic & I.M.distortion          3% MAX

FM usable sensitivity (mono)          12.8 dBf  (1 microV, 75ohm)

FM selectivity                                 65 DB alternate channel

FM s/n ratio (mono)                        77dB

AM frequency response                  20Hz to 8000Hz + ldB

AM selectivity                                55 dB

Tape player for double cassette playing

Frequency response                       50-8 KHz at 3-3/4 IPS

                                                     50-15 KHz at 7-1/2 / IPS

Unrepetitive program duration         16 hours at 3-3/4 IPS

Operations :                                   Continuous repetition with automatic reversal at both ends

                                                     of tape reel

Signal to noise ratio                       50dB (Dolby NR : off)

                                                     60dB (Dolby NR : on)

Distortion                                       Less than 3%

WOW and flutter                             Less than 0 1%

Mixer Pre-Amplifier

Frequency response                       20Hz to 20 KHz +- ldb

Noise:                                            75 dB below rated output

Distortion:                                      less than 5% THD at+8 dBM

Signal to noise ratio with tone

Controls centered and master

Volume min                                                90 db

And with master volume max                      77 db

­Output power                                             +4 dBm, +20 dBm (max)

Inputs                                                        Eight inputs each 100mv/10 k ohms

Outputs                                         Main talanced and AUX.

Output

Controls                                                Eight input gain controls / 1 master gain control base tone, treble tone

Complete with A/C protection by internal fuses

Distribution Channel Power Amplifier

Frequency response                       40 Hz to 16 KHz -+ 3dB

Noise level                                     83 dB rated output

Out put                                          360 W RMS, 100V

Distortion                                       Less than 1% at rated

                                                     output, 1KHz

Signal/Noise ratio                           At least 80dB

Complete with fault detection circuit

CD player

Frequency response                       20-20000Hz       -+ 0 ldB

S/N ratio (EIAJ)                              100 dB

Dynamic range (EIAJ)                     94 dB

Channel separation (EIAJ)               93 db

Alert signal unit

Signal                                            2-tone alert

Frequency                                      440HZ & 554Hz in sequence

Sounding time                                cycle length 5 to 45 sec adjustable

Output level                                   280 mV peak/peak

Voice Message unit

Semiconductor memory type

Frequency response                       80 - 4000Hz

Storage Messages                         up to 4 messages

Total Time                                      43 seconds

Speaker Back-Box

Speaker back-box shall be a completely sealed plywood enclosure

Line Matching Transformer

Frequency response                       60 Hz to 15 KHz + ldB

Primary impedance                         3 3K ohms for 100V systems, 3w

Secondary impedance                    8 ohms



Decorative Loudspeaker Grille:

None-resonant, metallic, 40% open finish and styling to be coordinated with architect.

All items of equipment shall under any normal circumstances of operation be capable of withstanding any surges which might be produced by sudden re-establishment of mains or standby power supplied after a power failure.

Heat limits as specified and guaranteed by the manufacturer shall under no circumstances be exceeded. Louvers and vents shall be provided to this effect.

The two sides and the rear doors of the rack shall be capable of being opened to permit in site servicing and the rack shall be located such that at least one meter of free space around it is available for this purpose.

Connecting Cable:

One twisted pair shielded with overall plastic jacket into P V.C. conduit The conductor shall be tinned copper conductor of 1.5 mm cross section area minimum.

The voltage drop shall not exceed 10% of the drive level at any point of the distribution network.

Loudspeakers:

The loudspeaker shall be of ceiling type and shall be specially designed for public address applications. They shall be installed as specified and as shown on the drawings.

The loudspeaker shall have 1.7K ohms impedance at 100v, 6w

The loud speaker shall produce a sound pressure level of 90 dB at a frequency of 1000 Hz at a distance of 1 meter with an input power of lw.

The loud speaker shall have at least the following technical specification:

Power handling capacity for ceiling type:      5 W

Power output selection                              5,3 or 1.5 w

Input voltage                                              100 V

Frequency range                                        100 to 20000 Hz.

Projector loudspeaker for parking area with 12w power output

Frequency range 65-15000 Hz. sound pressure level 92dB/W/m

At 1 KHz

Zone selection modules

Zone selection modules, shall be installed at the equipment rack, through which the zone selection can be performed from the paging disk. The unit shall be suitable for 20 zones individually and all zones selection.

Electro-Chime Unit:

Their unit shall be a metal microphone desk of latest design It shall incorporate the following:

20 illuminated zone push-buttons plus one all-call.

1              electronic chime with one monitor speaker with attenuator

2              Illuminated lamps chime and microphone.

1 gooseneck-mounted microphone head with ON/OFF switch and chrome-plated type handle.

all necessary switches, controls, relays and connectors to operate the system satisfactorily.

The microphone head shall be of rugged construction and shall be specially designed to provide excellent paging. It shall have at least the following specification:

Type                                              dynamic

Polar pattern                                  directional

Frequency range                            100-15000 Hz

Front to rear ratio                           greater than 15 dB.

Sensitivity                                      0 15 mV/UBar

Equipment rack:

A standard and handy metallic rack shall accommodate all system equipment and shall be mounted on a pedestal with runners. The rack unit shall also be provided with one blank panel for each type of system equipment and shall be fitted with a lockable front glass panel.

The rack shall be equipped with fans for ventilation such that the temperature inside the rack shall not under any condition reach the max.

Operating temperature of the equipment.

Monitor Panel:

The monitor panel shall be installed at the rack to monitor the out put of all the equipment installed at the rack.

Approved Manufacturers:

-    Philips              (Holand)

-    RCF                  (ITALY)

-    TOA                  (Japan ONLY )

or approved equal

3.14. 4.4 PERSONNEL TRAINING

Building Operating Personnel Training: Train Owner's building personnel procedures for starting up, testing and operating the system and auxiliary equipment. Furnish three operator's manual providing installation and operating instruction.

3.14.4.5 GURANTE

All components, parts and assemblies supplied by the manufacturer to be guaranteed defects in materials and workmanship for a period of 12 months from owner acceptance.

Equipment manufacturer to have a local branch office staffed with trained, full-time employees who are capable of performing testing, inspection, repair and maintenance services for the life of the system.

Contractor to guarantee all wiring to be free from inherent mechanical and electrical defects for one year. The manufacturer to furnish a one-year maintenance contract, free of charge to the owner, effective from the date of installation for maintenance and inspections of the manufacturer's equipment, with a minimum of two inspections during the contract year. A local manufacturer service department, which stocks standard parts to be available to the owner. If required, maintenance is to be performed during normal working hours, at no cost to the owner, for a period of twelve months from the completion date of the installation, unless misuse, abuse or accident causes damage.

3.14.4.6 SERVICE AND MAINTENANCE

The equipment manufacturer shall make available a fully equipped service organization, capable of guaranteeing an on-site service response time within 8 hours to a service request call. Site service shall be available 24 hours per day and seven days per week.

3.14.4.7 SPARE PARTS

The contractor shall submit a recommended list of spare as recommended by the manufacturer indicating the unit prices for each item the spare parts shall be suitable for at least three years of operation.



3.14.6  CLOSED CIRCUIT TELEVISION C.C.T.V     SYSTEM



16.16.6.1     GENERAL



Provide a C.C.T.V system as specified and as shown on the relevant drawings.



Description of work

Work includes the supply and installation all materials, equipment, accessories and all necessary ancillary equipment requirement required for complete installation and testing.


Submittals

Product data: The contractor shall submit product technical data for all equipment and network.

Samples:  The contractor shall submit samples for cables, boxes ….. Etc.



Shop drawings: The contractor shall submit detailed work shop drawings illustrating all technical data required for complete installation.



-      PRODUCTS

GENERAL


This specification section covers the supplying, delivering to site, erecting, connection up, testing commissioning performance testing, demonstrating and handing over in working order of the complete CCTV installation .


The CCTV equipment and installation shall be supplied and in stalled in accordance


Will all applicable BS, EC, DIN and UL (underwriters' laboratories) standards.


The video signal produced by cameras shall be in accordance with the EIA standard.


                  The contractor shall be responsible for the final location of all the cameras to give    optimum coverage of  the areas to be surveyed.



The contractor shall be responsible for suitable bracktry to fix cameras in their final locations.



The final location, fixing methods, camera housing and color finishes shall be subject to approval by the engineer.



The CCTV system shall be protected against all electrical interference.

The system shall provide maximum operational simplicity to enable quick and effective use in an emergency.



The system shall be modular to facilitate future expansion, in particular the addition of extra cameras.



The contractor shall provide and install all power supplies necessary for correct operation of the CCTV system. The power source provided for the entire CCTV system is to be 220/50HZ all supplies shall be the same electrical phase.

The CCTV system shall consist of the following components:

        I )    A   color fixed dome cameras .

       I I )    Camera housings supported be suitable bracketery .

      I v )    Multiplex video recording .

        v )    DVRs and Control equipment

 

The control and monitoring components shall be built into the security console, located in the locations shown on the drawings. All control and monitoring components shall be designed for mounting into a 19 inch standard rack and shall consist of modular, unit type assemblies to facilitate removal, maintenance and system expansion.

 


CAMERAS

The cameras shall be of the solid-state, charge coupled device ( CCD ) type and white pictures  Tube cameras shall not be accepted for type camera data schedule .


technical specification


       Pick up tube:                                          4CCD

       Minimum TV lines                                  420

       Minimum Illumination                             0.1 lux

       Standard Illumination                             30 lux

       Geometric Distortion                              None    

MOUNTING BRACKETS

Fixed Camera Brackets

All cameras which are not installed on a pan / tilt unit shall be mounted on a vertically and horizontally adjustable wall or ceiling mounting bracket which shall permit a minimum of + 30o/- 60o (vertical and +-45o (horizontally) site adjustment.

The camera bracket shall be made of non-corrosive material finished in a color subject to the approval of the engineer.



Pan / Tilt Units

The pan / tilt unit shall be designed to carry the combined weight of the camera and the associated ancillary equipment.

The pan / tilt unit shall be renewable a counter–balance weight to ensure smooth movements, free of backlash.

The pan / tilt unit shall use retractable cables to prevent any wire fatigue during pan operations.

The pan / tilt unit shall be renewable telemetry control and preset positions.

The angular travel of the pan / tilt unit shall at least be as follows:

Pan                                   6o per second

                           Tilt                                    per second 

The pan / tilt unit shall be constructed of non–corrosive material finished in a color subject to the approval of the engineer and shall require minimal maintenance during its rated lifetime.

Housings 

Cameras shall be provided with housings as detailed on the camera schedules.

All cameras in external and semi – covered locations shall be provided with a weatherproof housing, complete with sunshield, 75 watt heater and wash / wiper

 (Self parking).

Cameras housings to public areas, in particular the podium, shall be aesthetically pleasing and shall be of a type approved being the engineer.

Lenses

Fixed lenses shall all be 1/3” format. Pan, tilt and zoom lenses shall all be 1/3” format.

Lenses shall have a focal length selected be the contractor to give optimum coverage of the areas to be surveyed. Lenses shall be exchanged during Testing and commissioning at no extra to the contract if required be the engineer

Zoom lenses shall be fitted with a neutral density spot filter.

CONTROL AND MONITRING

Switching and control systems

A   microprocessor based switching and control system shall be provided for control of all system functions.

A   keyboard with dedicated control, operating and programming function keys / indicated shall be provided as the operator interface to the system. The keyboard shall be built into the security console.

The central processing unit shall provide independent sequential programs for each monitor.

Programs for each monitor. The operator shall have the facility to modify the sequential via any of the monitors.

·         Split screen facilities shall be incorporated such that 1, 4, 8 or 16 cameras can be displayed on the same monitor. The facility to run sequential programs within split screens shall be provided

·         An electronic zoom facility shall be provided to aid detail viewing of fixed camera pictures.

·         Password / PIN protection of system access levels shall be provided.

·         Upon power failure, the data stored in the central processing unit shall be protected for at least 2 hours with an internal constantly charged NICXAD battery.

·         Camera renewable action shall guarantee roll – free switching anywhere in the system.

·         Facilities for an a later date without modifications or additions to control systems shall be provided.

Monitors

1 number monitors shall be provided at the security console, 17 inches diagonally and.

The monitors shall be of high quality and attractive styling, with front panel operating controls. Reliable solid state circuitry shall provide a stable picture.

Technical specification for the monitor.

§  Capable of displaying black and white pictures.

§  Resolution 700 lines minimum.

§  Amplifier band width 8 MHZ or better.

§  DC restoration

§  Synchronization internal/external.



Suitable monitor support bracket shall be provided to ensure integration of monitor support bracket shall be provided to en-sure integration of monitors into the security console with due regard to ergonomics.



Digital Video recorder (DVR)

 Multiplex recording facilities shall be provided, allowing user selected cameras


   To be recorded simultaneously, up to16 cameras The individually, simulating real time recording.



          Number high quality time lapse recorders shall be providing.



   The time lapse DVR shall provide the following basic feathers:



-       Minimum six programmable recording duration periods.

-       Video missing and recording of time, date, camera number, alarm Data and recording mode.

-       Internal time, date generator.

-       Alarm activated recording selectable for 3 or 12 hours mode.

-       Tape search functions in both directions.

          Technical specifications:

              -       Recording time                960 hours minimum

              -       Type format                     1 /4 VHS cassette

     -       Video S/N ratio                34  db or better

                         CCIR standard (625 lines, 50 fields)


                      Horizontal resolution   better then 330 lines



Wiring

  • Video transmission shall be by means of co-axial cable. Control signal Transmission shall be by means of shielded 2 pair twisted cables.
  • The contractor shall supply and install all trunking/conduits associated   with the CCTV system wiring.
  • The cables shall terminate at each camera location in a two compartment Heavy duty metal enclosure with fixed cable termination units for video and for the power supply derived from an emergency distribution board.
  • The enclosure shall be suitably sized to allow for any additional equipment    E.g. Transformers for low voltage operated cameras.
  • The enclosure shall be provided with removable lids fixed by captive screws and suitably renewable.
  • All termination shall be clearly identified.
  • Cabling from the enclosure to the CCTV units shall be in flexible metal conduits.



     Testing and commissioning



After completion of the wiring and installation equipment. The entire C‏CTV system shall be tested, inspected and commissioned by the manufacturer and subsequently handed over to the engineer in a fully operational condition and mode.

 

The manufacturer and contractor shall,  on completion,  issue a certificate to confirm  the compliance in all respects of the installation with the relevant international  standards and codes of practices.



  The entire CCTV system shall be tested to ensure:

i)          Satisfactory operation.

ii)         All controls operate in accordance with the specification.



Insulation tests at 500V dc insulation to earth and between conductors shall be made, and earth continuity and earth loop impedance tested, all in accordance with current IEE Regulations.



The contractor shall submit with his tender a priced offer from an acceptable specialist company for a renewable checking,  testing and maintenance service contract for the system(s) to be in- stalled. This offer shall include details of the minimum frequency of checking and testing allowed for,  and the costs of all parts which may require renewal.



Full training shall be provided to center security staff in operation of the equipment and to engineer in programming of the system of 2 days on site demonstration and training shall be included in the Tender.



Approved manufacturers 



           -      PHILIPS                     (HOLLAND)

           -      American Dynamic     (U.S.A)

           -      TOA                            (JAPAN)

        or approved equal.



16.16.6.3   EXECUTION



INSPECTION


 


Examine areas and conditions under which CCTV system is to be in-stalled and notify in writing of conditions detrimental to proper completion of the work.  Do not proceed with the work until un-satisfactory conditions have been corrected.

INSTALLATION

Install complete CCTV system, including associated control devices as indicated, in accordance with manufacturer’s written instructions, requirements of applicable standards, and in accordance with recognized industry practices to ensure that installation complies with requirements and serves intended function.



Coordinate with other work as necessary to interface installation of CCTV system with other work.



Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer’s published torque tightening values for equipment connectors.



FIELD QUALITY CONTROL


Upon completion of installation and after system has been energized, demonstrate capability and compliance of CCTV system with requirements. Where possible, correct malfunctioning units at site then retest to demonstrate compliance; otherwise, remove and replace with new units, and retest.

Building operating personnel Training:  Train owner’s building personnel in procedures for starting up, bypassing and operating CCTV system.

Furnish three operator’s manuals providing installation and operation instructions for each item in CCTV system.                                                           







END OF THIS SECTION