Tiger™ Case Studies
There are over 750 incidents that Tiger has helped to identify and
resolve. Many of these problems were previously unknown or did not readily lend
themselves to rapid diagnosis. In most cases the problems were unknown to the
operators and each represented a potential incident, resulting in unscheduled
down time and loss of revenue.
It has been noted that on sites where Tiger is fitted with its remote access
capability, the engineering level of the operational staff can be lowered as the
knowledge based system is continually offering solutions to identified
problems. This, plus the facility for skilled staff to connect to the system
through a modem and give instant advice to site engineers, reduces down time
significantly.
Tiger has assisted with over 750 incidents.
Below is a summary of 10 incidents, detailing the situation, how Tiger was used to assist with the
situation and the benefits that resulted. Together they represent the wide
range of Tiger's capability. Not
only do these examples describe real incidents, but they also give an overview
of the wide range of areas in which Tiger
can provide assistance.
Faulty Controller Card
The customer phoned the Tiger team and asked for assistance with
a problem on the gas turbine. Intermittently large numbers of alarm messages
were being generated on the distributed control system. The Tiger team connected remotely into Tiger at site, and confirmed through the
Tiger diagnostics that there was
an intermittent fault generating a wide range of diagnostic problems.
By using the Tiger to get an overview, they could see the frequency and
duration of the intermittent fault, and verify a number of times when the fault
was occurring. The only signals to be affected were the in the contact input
DTBA for the <C> processor, hence the Tiger
team was quickly able to diagnose that the fault was a bad TCDA card causing a
large number of alarm fault messages from the Mark V controller at intermittent
intervals.
Without the facilities available in Tiger, the customer would have to go and
investigate the alarms generated by the Mark V controller and conduct an
investigation. Given the fault was intermittent, the customer would have to
wait until the fault occurred, or sift through the alarms printed out by the Mark
V controller.
In this situation, the gas turbine
continued to operate, so no downtime was incurred, however, through the use of Tiger, the Tiger team was able to reduce the diagnosis time by 3-4
hours, and facilitate sending a field engineer to site with the correct
replacement card to rectify the fault.
Sticking Bypass Valve
On this oil platform, the gas turbine is
always started on distillate fuel oil. The engineer on the platform had noticed
that the gas turbine was unstable during start-up. This problem had been
continuing for sometime. The engineer notified the Tiger team after another unstable start. Tiger remotely connected to the oil
platform and checked the diagnostic information collected during the start-up.
It was quickly determined that the liquid fuel oscillates between 0 and 5 MWatt
power levels.
Using the information available in Tiger and the remote support provided by
the Tiger team was able to
remotely diagnose that the problem was as a sticking bypass valve. This problem
would have been very difficult to diagnose on the platform in their environment
without Tiger, particularly for
the site engineer, who would have had to change a number of components and then
attempt another restart to see if the problem disappeared. These components are
not always available on the platform. If the turbine failed to start due to
these oscillations, which was a very high risk, then the platform would have
lost this power source. By being able to diagnose and correct the problem, the
use of Tiger's was able to avoid a
probable future trip and shutdown, which would cause at least 5 hours downtime
on the platform.
The remote diagnosis by the Tiger team was accomplished very
quickly. However, for an engineer to change out components and attempt a local
fix without the Tiger information
would have required 3-4 hours.
Faulty Gas Compressor
An oscillation of 1½ bar was detected in
the P2 pressure of the gas fuel system that was causing 5% swings in the gas
valve position. Fast load swings resulting from these fuel fluctuations can
cause long-term maintenance problems. Through the use of the information
available in Tiger, it was
determined that the gas valves were operating correctly (i.e. controlling the gas fuel flow for the
oscillating P2 pressure). The fault was in the associated gas compressor.
Determining When to Wash
Initial checks on the gas turbines
performance indicated that there was approximately 1 MWatt drop in the base
load output, when ISO corrected. This information was used as part of reviewing
the washing regime of the gas turbine and determining when to optimise the wash
intervals.
The information supplied via Tiger verified that it was appropriate
to conduct an offline wash at that time.
The loss of 1 MWatt power output would be
continuous and also depreciating if the unit continued to run. The use of the
information also allowed a planned offline wash saving 15 hours for an
unplanned shutdown of the unit.
Faulty Speed Ratio Valve
The Tiger
diagnostics indicated that the speed ratio valve was exceeding 42% open for the
running conditions and load. In addition, its associated servo was at negative
saturation. The information available in Tiger
showed that at full speed, no load, the servo was already at -18%, which is
outwith the specification of the servo. It was also shown that on a 40 MWatt
load, the valve would open to 100%, and the inlet pressure was not up to
specification. Using Tiger it was
established that the speed ratio valve's servo needed to be checked. By
detecting the problem early it saved a potential trip of the turbine and
allowed them to plan maintenance, potentially saving a 6 hour unplanned
shutdown.
Faulty Compressor Bleed Valve
Tiger detected that a fired shutdown changed to
a turbine trip when a compressor bleed valve did not open in the required time.
Such trips during shutdown affect the maintenance lifetime of the machine.
The customer was advised to investigate
the bleed valves and switch. The resolution to the problem was that it was the
switch that failed, which was replaced. It was also noted that the switch was
directly in line with some hot gases, this lead to the deterioration of the
switch.
Sticking Stop Valves
The daily check of the Tiger diagnostics detected that both the
gas fuel and liquid fuel stop valves were sticking for abnormal lengths of time
- the gas fuel stop valve was sticking for 5 seconds and the liquid fuel valves
were sticking for 10 seconds. The sticking of these valves can cause problems
in fuel transfers, including a gas turbine trip when a fuel transfer was
attempted and unsuccessful. The site was advised to change the appropriate fuel
valves.
This problem was again detected 10 days
later when during a fuel transfer to gas fuel; the speed ratio valve did not
open until approximately 1 minute after the signal was given by the servo. This
caused the fuel transfer to fail and the system remain on liquid fuel longer
than expected. It was shown that the cause of the sticking was because the gas
fuel stop valve stuck open for approximately one minute.
This incident was repeated 5 days later
where the gas fuel stop valve stuck open, which stopped the Stop Ratio Valve
from functioning, however the gas control valve continued to open, expecting a
supply of fuel. The gas control valve continued to open to 100%, then the gas
fuel stop valve closed, this caused a surge in fuel flow. This ultimately led
to the exhaust temperature rising to 585oC, which tripped the unit.
It was reported that the same incident
occurred the following day, but due to a low load it did not trip the unit. The
last incident, which tripped the unit, could have been avoided if the customer
had followed the recommendations to change out the appropriate fuel valves when
Tiger first detected the problem.
6-8 hours down time would have been saved if the customer utilised Tiger's early detection of the fault.
Incorrect Calibration of Lube Oil Header Temperature Switches
The gas turbine tripped on a high lube oil
temperature. The Tiger team used Tiger to remotely verify the fault and
determine that the trip should not have occurred. An oil header temperature
trip should normally be at 80oC, however, the trip occurred when the
temperature was only 63oC. It was rapidly established through a
remote to Tiger that the gas
turbine could be safely restarted, but that the lube oil header temperature
switches needed to be recalibrated.
Sixteen days later the gas turbine tripped
again on high lube oil temperature. Tiger
information was used to rapidly verify that the problem was the same as before,
that is, the sensors were incorrectly calibrated and it was an unnecessary
trip. Although the site had been told to recalibrate the sensors after the
first incident, they had not done so, showing that if they had acted on the Tiger data, they would have prevented a
trip.
Three months later the gas turbine tripped
again for high lube oil temperatures. Tiger
data was again used to verify that the cause of this was an incorrect
calibration of the switches and that the gas turbine could be rapidly restarted.
It was determined that an incorrect calibration procedure was being used. Tiger was used to rapidly verify the
cause of the trip, and confirm it was safe to restart the turbine, as well as
to identify that the site was not carrying out a procedure correctly.
Faulty Vibration Sensor
The daily check by Tiger indicated that one of the bearing sensors had a
momentary spike of 16mm per second. The site was advised that this had occurred
and the problem was monitored daily through Tiger.
Three weeks later the same transducer was
now spiking approximately once per hour with a magnitude of 8mm per second. The
site was advised that the sensor was faulty and needed replacement. This early
detection of the problem, monitoring its evolution, and advising of a correction,
prevented a potential high vibration trip.
Early detection by Tiger and remote diagnosis was used to verify that it was a
sensor problem and prevent an unnecessary trip.
Faulty Relay in Fuel Clutch Circuit
A phone call was made from site to the Tiger team requesting assistance. They
had just replaced the flow divider for the liquid fuel and wanted the Tiger team and engineers to monitor the
gas turbine on the subsequent start-up. Three attempts were made to start the
gas turbine, all of which failed.
The engineers, using Tiger, were able to observe that on all
three attempts, no fuel flow was achieved through the new flow divider. Through
discussion with the site they were able to guide the engineer to establish that
the cause was that the fuel clutch was not engaging due to a faulty relay in
the clutch circuit.
By using the engineering support available
at base to assist the person at site, they were able to identify the cause of
the failed starts much more quickly. The problem was a very obscure and
uncommon fault, and it is unlikely that the engineer on the platform would have
been able to identify it on his own in the situation.
Through the use of Tiger and the remote help of the engineers, they were able
to get the machine up between 12 hours and one day quicker.
Tiger is a Trademark of Intelligent
Applications Ltd
August 2001
For more information, contact:
Intelligent
Applications Limited
1
Michaelson Square, Livingston, West Lothian,
Scotland
UK, EH54 7DP
Tel: +44
(0)1506 472047 Fax: +44
(0)1506 472282
Email:
ia@intapp.co.uk WWW:
www.intapp.co.uk
|
No comments:
Post a Comment