POWER PLANT
COATING MATERIAL AND APPLICATION:
The Contractor should use only coating
materials that meet the requirement of this specification.
Unless otherwise accepted, all field coats of a system must be products of one manufacturer.
The preferred application method for the coating
systems specified as airless or conventional spray equipment.
Where spray equipment is required, the equipment, adjustments, and air pressure shall conform to the manufacturer's recommendation and shall be subject to approval by the Company/Engineer.
Where the application by brush or roller is required due to special circumstances, the Contractor shall apply in writing, separately for the Company/Engineer's approval.
Regarding storage of paint and coating material
as well as mixing and application, the Contractor shall follow the application
instructions of the coating manufacturer.
The colors of the different coats shall differ
sufficiently for control purposes.
The specified dry film thicknesses are minimum
requirements.
Therefore, sufficient wet film thickness per coat shall be applied to obtain the specified dry film thickness after drying or curing. The contractor has to follow the manufacturer's instructions and shall use wet film as well as dry film thickness gauges.
Drying time between coats shall conform to the
manufacturer's recommendations and shall be strictly followed.
QUALITY CONTROL AND INSPECTION:
Quality control and inspection by the Company/Engineer will not release the Contractor from his responsibility for the correct performance of the work.
The Contractor is responsible for taking liquid
samples of the paint and coating materials during the construction period, and
to retain these samples at the Jobsite for reference in the event of coating
failure. Retained samples must be kept at least until the warranty period has
expired.
For quality control and inspection after erection the following instruments and standards,
which should be in a
satisfactory working condition, shall be used for testing:
- Swedish
Standard SIS 05 5900
- Kean Tator
surface comparator
- Material
thermometer
- Surface
temperature gauge
- Sling
psychrometer
- Non-destructive dry film thickness gauge
Wet film thickness gauge
- Non-destructive
pinhole detector (for tank linings and immersed surfaces
The Contractor is responsible for preparing a daily record of the painting work.
The record shall indicate the locations and types of surfaces coated, the name of products applied, type of surface preparation, and dry film thickness per coat.
The record should also include information about air temperature, steel temperature, and relative humidity.
The contractor will supply the Engineer with a copy of each daily record on a weekly basis.
GUARANTEE:
The guarantee period for the complete painting and corrosion protection shall be five years after the Engineer's and Company's final inspection and acceptance.
For defining a possible failure of corrosion
protection, the standards for the degree of rusting of anticorrosive paints should
be used. If the degree of corrosion is above this standard, the Contractor is
responsible for repairing and/or repainting those areas, which failed.
For guarantee control purposes test patches
must be applied in the presence of the Contractor, Company/Engineer, and Coating
Supplier. Test patches have to be identified and recorded.
The Company/Engineer's approval for the number, size, and location of test patches will be required.
Test patches shall be the basis for clarification of responsibilities between the Contractor and Coating Supplier in case of defect or failure.
COLOR SCHEDULE
After award of the contract, the color schedule for the plant will be compiled, in accordance with the specifications, by the A contractor for approval by the Company/Engineer.
Pipes and valves shall be identified by painted
bands of the identification color for the fluid transported.
All identification colors shall be in
accordance with German Standard RAL 840HR or equivalent.
Flow direction arrows shall be painted in the
vicinity of branching-off connections, at the inlet branch connections
downstream of each valve and at points, which will be indicated by the Engineer
on-site.
All equipment and installations shall also be
marked with identification numbers.
No comments:
Post a Comment