Specific maintenance equipment
The Contractor shall supply all maintenance sets required for the fire detection apparatuses and particularly:
- detector exchangers to avoid the use of a ladder,
- detectors testers to allow periodic performance
check of the different fire detectors,
- Any other testers and test methods recommended
by Manufacturer.
Cables
Cables used for fire detection system shall be
fire-resistant according to IEC 331.
FIRE FIGHTING
MEANS
As aforementioned,
the fire fighting means will consist of automatic and manual systems.
- Automatic systems are those in which as soon as
a fire is detected, an automatic response is actuated without human
intervention.
However, automatic
systems shall be designed in such a way that they can be manually actuated or
manually disabled by specialized workers when required.
- Manual systems are those in which a manual
intervention is always required.
Automatic systems
shall be provided for the following installations in accordance with the
COMPANY requirement (refer to clause 1.2):
- main control room:
- computers room:
- electrical rooms, i.e. switchgear rooms, MCC,
local control rooms:
- cellars of above electrical rooms: (*),
- cable galleries: automatic water spray fixed
system.
- main and auxiliary transformers: water deluge,
- fuel skid blocks:
- gas turbine hot parts, i.e. hot bearing and
combustion chamber(s) areas: CO2 system
- crude-oil tanks floating roof sealing: foam
- Warehouse: fuse plug water spray system or
"sprinkler" type system
- Steam Turbine, Heat Recovery units and
associated equipment
(*)NB: When
there is no open communication with the bottom part of any switchboard, i.e. there
is no open cable recess through the ceiling, the cellar of electrical or technical
room may be considered as a cable gallery. In that case, the system will be replaced
by a sprinkler system, principally if, in addition, the cellar is large.
Manual systems shall
be provided for the following:
- crude-oil tanks over the floating roof: foam,
- diesel-oil tanks and main sludge tank upper
internal part: foam,
- crude-oil, diesel-oil tanks, and main sludge
tank shell external part: water deluge,
- crude-oil, diesel-oil tanks, and main sludge
tank dike areas: foam,
- unloading area, metering, and fuel pumping
stations: foam,
- black start diesel gen. set: foam,
- all other areas, outdoor and indoor: water
hydrants, foam hydrants, hose reels, portable extinguishers.
- Etc.----