SYSTEM DESCRIPTION &
SPECIFICATION
|
|
|
AIR PRESSURE WATER TANK:-
Hydro-pneumatic tank, horizontal, carbon steel of
welded construction, 2000 liters gross volume, designed & manufactured in
accordance to receive specifications, for up to 12 bar. g working pressure,
hydraulic test at 15 bar for a duration of 24 hours (leak-free but not constant
pressure).
Materials for shells & domed ends: commercial
steel 37.2
Diameter 2070 mm
Overall length over domed ends = 6600- mm.
Thickness for shell = 16-mm.
Thickness for domes ends = 20-mm.
Clearance at bottom 400 mm.
Thank shell be painted internally with
anticorrosion, after sandblasting, cleaning, one layer primer anti-corrosion
coating with epoxy thickness 200 microns.
Thank shall be painted externally with anticorrosion,
after sandblasting, cleaning, one layer primer anti-corrosion coating with
epoxy thickness 80 microns, final anti-corrosion coating with epoxy 80 microns.
The tank shall be fitted with:-
- Steel supports.
- Permanently attached lifting
lugs.
|
1-1
|
|
|
|
- Access Manhole with sealed
flanged cover ( 500 mm I.D. PN16 )
- Drain connection 3”
flanged PN16
- Water level gauge
connections – 2 Off – 2” flanged PN16.
- Combined Inlet/Outlet water connection
- 4” flanged PN16.
- Spare water connection – 4”
flanged.
- Inlet compressed air connection - 2” BSP.
- Safety relief valve connection – 2” flanged PN16.
- Spare connection – 2”
flanged PN16.
- Pressure gauge connection
– ½” BSP
- On/Off Pressure switch
connections – 3 Off - ½” BSP
- High (Alarm) Pressure
switch connection – ½” BSP
- NDT reports on the shell
welds ends welds, nozzles & branches welds shall be provided as
well as the hydraulic test report
|
1-1 cont.
|
Fittings & mountings:-
Drain valve – 3” Flanged.
Water inlet/outlet gate valve – 4” flanged.
Inlet air valve – 2”.
Check valve for air inlet – 2”.
Safety relief valve – 2” inlet screwed connections in/out, set at
10.5 bar.g. lift pressure.
Dial type pressure gauge 0 – 16 bar.g. With cock. SPDT pressure
switches – On/Off.
SPDT pressure switch – High-Pressure Alarm.
|
1-2
|
|
Level Gauge:-
Intra Automation GmbH ( Germany ) ITA3.0, Magnetically activated sight
level gauge with top & bottom flanged connections on 1870 mm center to
center distance, complete with level switches ( Eight PCs.) for the following
functions:-
Switch no.1 = high water level alarm.
Switch no.2 = pump #1 off.
Switch no.3 = pump #1 on
Switch no.4 = pump #2 off
Switch no.5 = pump #2 on.
Switch no.6 = pump #3 off.
Switch no.7 = pump #3 on.
Switch no.8 = low water level alarm.
Isolating upper valve for the level gauge – 2”
Isolating lower valve for the level gauge – 2
|
1-3
|
|
|
|
|
WATER SPRAY FOR TRANSFORMERS 25
WVA
§Deluge
value station DN 100, for pneum. Release, complete with all necessary values,
globe values, and trimmings as drip value, manual release value, and pressure switches, incl. Sets of pneumatic actuation system at the deluge value station, consisting of diaphragm value, and all connection parts.
|
2
|
|
§Set of spray nozzles, consisting of :
-
Spray nozzles, DN 20, K = 20
-
Spray nozzles, DN 20, K = 50
-
RD nozzles 1/2 x 6.6
|
|
|
§Set of detection sprinklers, consisting of :
-
MX sprinkler 1/2 x 93
|
|
|
§ELECTRICAL EQUIPMENT FOR TRANSFORMERS 25 MVA
|
|
|
§Transformer detection panel micro- processor – a controlled, programmable, system with LCD- display and individual fire and
fault indication for each zone.
Capable to supervise
4 automatic alarm lines, extendable up to 12
alarm lines for
connection of heat detectors as well as push buttons
|
|
|
§ Power supply unit with integrated backup power
batteries are included for interruptible emergency power supply, charging
supervision of 2 built-in gastight batteries 12 V, capable to supply power
24 H.
|
|
|
§ Audible alarm heavy-duty weatherproof housing,
producing a two-tone alarm, for surface mounting, protection class IP54, acc.
To DIN 40 050
|
|
|
§ Rate-of-rise and fixed temperature detector for
transformer heat detectors.
|
|
|
§ Manual release push button
|
|
|
JOKEY PUMPS:-
|
3
|
|
§
Electric driven vertical jockey
pump 100 L/min at 10 bar, complete, together with electric motor 4 KW, 2900
rpm, 380 V, 50 HZ, IP 44
§
Ball value DN 40, PN 10,
screwed.
§
check value DN 40, PN 10,
screwed.
§
Pressure gauge 0-16 bar.
§
Stop value 1/2 "
§ Controller for automatic start and stop of jockey
pump and air compressor 380 VAC, control voltage 220VDC, complete with a set
additional electrical equipment in the controller, controlling for standby
conditions of the compressor and jockey pump.
|
|
|
AIR COMPRESSOR:-
§
Compressor with air receiver,
complete with switch for automatic start and stop of compressors and solenoid
arrangement for pressure less start of compressors, with a set of connection
equipment between compressors and air supply pipe and
§
Pressure gauge 0-16 bar
§
Stop value 1/2 "
§
Ball valve 3/4 "
§
Check value 3/4"
§
Pressure reducing valve
|
4
|
|
PRIMING TANK,
500L equipped with:
§
Float value, DN 25
§
Level switch, compel
§
Complete connection pipe device
for dry running protection of jockey pump
§
Ball value 2"
|
5
|
|
MANIFOLD
DN100 with 4 branches DN 100
for deluge value stations, galv., with support.
|
6
|
|
Guarantee
Tables
Fire
fighting equipment
For the
power transformer
------------------------------------------
§
Manufacturer Minimax
§
Quantity of water to extinguish fire in transformer 2000 L/MIN
§
Capacity of water tank 15
m3
§
Service pressure 10
Kg/cm2
§
Time range for extinguishing of fire in one transformer 60-90 sec.
§
Duration of water sprinkling
5 min.
No comments: