SAUDI ELECTRICITY COMPANY- TECHNICAL SPECIFICATIONS FOR INTEGRATED SECURITY SYSTEM( sec.3....sec 11) - Mr.CON.

Mr.CON.

project management&development of factories

Breaking News

Wednesday, 11 August 2021

SAUDI ELECTRICITY COMPANY- TECHNICAL SPECIFICATIONS FOR INTEGRATED SECURITY SYSTEM( sec.3....sec 11)

 SAUDI ELECTRICITY COMPANY

SCOPE OF WORK AND TECHNICAL SPECIFICATIONS

FOR INTEGRATED SECURITY SYSTEM

SECTION 3.0       DESIGN CRITERIA

 

3.01        GENERAL

 

                The detail design and installation of various equipment and facilities of this PROJECT shall be developed utilizing the basic design criteria and the specification requirements provided in this section.

 

3.02        ENVIRONMENTAL CONDITIONS

 

                The material section and design shall comply with the below listed site environmental conditions.

                The outdoor environmental conditions of the construction site are harsh and corrosive due to the action of salt, dust, humidity, and sand.

 

3.02.1         The site outdoor environmental data is as follows:

 

·       Absolute maximum ambient temperature                                   60oC

 

·       Absolute minimum ambient temperature                                    -5oC

 

·       Average maximum ambient temperature                                   +45oC

 

·       Average minimum ambient temperature                                    15oC

 

·       Peak ambient temperature during summer period                   65oC

 

·   .   Temperature due to direct exposure to sunlight                       85oC

 

·       Maximum relative humidity                                                            100%

 

·       Maximum wind speed (westerly to north-westerly)                   60 kph

 

·       Yearly maximum rainfall                                                                104 mm

 

·      Dust concentration in air mg/ cubic meter

 

CASE

SAND STORM

DUST STORM

SETTING

CLEAR

3 m above grade

1350

41.3

6.2

0.21

8 m above grade

69

34.4

5.3

0.21

Duration (hr/yr.)

*15

134

1440

7171

 

* Note:   Assume sandstorm condition exist approximately 10% at the average 149 hr/yr storm period for this case


 

·   Annual dust road (grams) per cubic meter air handled

 

CASE

SAND STORM

DUST STORM

SETTING

CLEAR

3 m above grade

20.25g

5.53g

8.93g

1.51 g

8 m above grade

1.04 g

4.61 g

7.63 g

1.51 g

 

·   Particle size distribution

 

Particle Size

in Microns

% by Weight for

Sand and Dust Storms

% by Weight

for Setting

% Weight

for Clear

0.01 - 0.1

1.0

1.0

1.0

0.1 - 0.5

7.0

9.0

11.0

0.5 - 1.0

12.0

15.0

18.0

1.0 - 5.0

33.0

42.0

50.0

5.0 - 10.0

16.0

20.5

17.0

10.0 - 20.0

9.0

11.5

3.0

20.0 - 40.0

10.0

0.0

0.0

40.0 - 80.0

10.0

0.0

0.0

80.0 - 200.0

2.0

0.0

0.0

Total

100.0

100.0

100.0

 

·   Total annual dust hold (grams) per cubic meter is:

 

            36.22 grams at 3 m above grade

            14.79 grams at 8 m above grade

 

3.02.2         The site indoor environmental data are as follows

 

                    The indoor areas will be air-conditioned; however, the facility shall be capable of continuous operation during air conditioning failure with the following conditions:

 

·         Air Conditioned Temperature                       19 - 30oC

 

·         Air Conditioned Humidity                               50%

 

·         .Unconditioned Temperature Maximum     65 oC

 

·         .Unconditioned Temperature Minimum      0oC

 

 

3.03.       APPLICABLE CODES AND STANDARDS

 

                The system shall be designed and constructed in accordance with the stated requirements and the Security and Safety Directives (SSD) issued by the High Commission for Industrial Security listed bellow and attached:

 

                SSD-12                                  Security Communications System  

 

                SSD-16                                  Automatic Control Entry (ACS) System

 

                SSD-23                                  Automatic Control of Entry

               

                Royal Decree No. 2139     HCIS Requirements for ID Badging System

 

                    The supplied materials shall fully comply with the recognized industrial standards for design, construction, performance, reliability, and safety. These shall include but not limited to the applicable sections of codes and standards (last edition) published by any of the following bodies:

 

                Institute of Electrical and Electronic Engineer                               IEEE

 

                Institute of Electrical Engineer                                                          IEE

 

                American National Standard Institute                                              ANSI

 

                National Fire Protection Association                                               NFPA

 

                National Electrical Manufacturer Association                                NEMA

 

                International Radio Commutative Committee                                CCIR

 

                Other applicable documents are mentioned under section.

 

                Materials design certificates shall be issued by a known authorized authority as UL, FM, BASSEFA, etc.

 

                All materials for use in explosion hazardous (classified) location shall be supplied with type test certificates.

 

                In the event of conflict between the above listed standard, codes and regulation, and the stated requirements, the CONTRACTOR shall refer to the COMPANY to resolve it in writing.

 

*** END OF SECTION 3.0 ***

SECTION 4.0       SYSTEM DESIGN REQUIREMENTS

 

                The COMPANY Integrated Security System is a site wide security information system. This is composed of the following:

 

4.01        Fence Detection System    

 

             The purpose of the fence detection system is to alert the security that an in intruder has entered the perimeter security fence, or is within a predefined distance of the site boundary.

 

                The type of detection methods employed shall be function of climate, location, environmental conditions, and site terrain as detailed elsewhere in this document.

 

                                     

4.01.1         Vibration Detection Technology

 

4.01.2         Microwave Detection Technology

 

      Output from these systems shall be combined in the central processor and full alarms raised only for coincident events registered by the two systems. This alarm shall be displayed on console at the security control center and will be recorded by the system event logger.  Actual location where the alarm occurred shall also be displayed in the Console Monitor by means of GUI-type Interactive Site Map. Audible indication shall be made available as stated in the preceding specification. However, a pre-alarm (as a warning) shall be generated when a single system triggered an event and shall be logged.

               

                All sensors shall be linked to the DCCTV cameras to enable the security control center to observe (through the monitors) and record the video events (through Digital Software Recorder) the point of intrusion where the alarm is indicated. This event shall occur automatically and/or after an operator-initiated instruction from the security control room. The DCCTV system shall also have Digital Recording (DVR) capability to automatically record pre-alarm and post-alarm video events, which will be available for playback and re-recording (e.g. archiving or backup)   at a later time.

 

                All detectors shall have low false and nuisance rate (one false alarm per zone per month). The detection methods shall prevent alarms from small animals entering the detection zones, and those caused by weather effects such as sand drifts and wind. Alarms shall be activated if an attempt to climb and cut the security perimeter fence. False Alarm per zone per month shall conform to the HCIS/SSD Standard.

 

                The vibration detection cable must be made of dual fiber optic cables.    

 

                The communications link between fence intrusion detection system (fiber optic sensor and microwave) and control room shall be designed using “Dual Loop” fiber optic lines.

 

                The signal transmission delay from the sensors to the Control Center shall not be more than one (1) second.

 

The Fence Detection system shall be “fail safe”, i.e. any failure in the system component/cabling shall be enunciated in control room.

 

                The probability of detection of intruders shall not be less than 95%.

 

The maximum zone length for fence detection system shall not exceed 250 meters.

 

 

 

4.02        Digital Closed Circuit Television (DCCTV)

 

             This subsystem of Integrated Security System shall be composed of the following components:

            

                1.             Day/Night Color Cameras

               

                                          2.               digital video recording (DVR)      

 

               

3.       21-Inches TFT-LCD Color Flat Video Monitor Stations (02 numbers at Main Gate Security House).

4.     50-inches TFT-LCD Color Monitor inside the Security Control Room.

                                      

             The primary purpose of this subsystem is as follows:

               

4.02.1         To provide accurate indication, alarm information and video events (i.e. real-time, pre-alarm, post alarm, playback of recorded file, etc.) if an intruder enter within certain sections of security fence and any strategic areas.

               

4.02.2         To enable to have a continuous monitoring of any strategic area and full surveillance of the whole plant.

                               

Cameras shall be installed in dedicated camera poles, around inner side of COMPANY perimeter to satisfy requirement..

 

Camera shall be installed outside the Security Control Center Room in appropriate place to enable the Security Operator to oversee the access to the Control Room and UPS Room. In addition, Intercom System shall be installed between the Security Control Room Operator and outside the Security Control Room.

 

Two (2) Cameras each shall be installed in appropriate place in the Main Gate to enable the Security Operator to supervise the entrance and exit of people and vehicles, and to be displayed in separate monitor screens in the Security Gate Room. 

                               

Camera shall be installed in appropriate place in the Employee Entry/Exit of Main Gate to enable the Security Operator to entrance and exit of people to the plant.

                               

Digital Closed Circuit Television (DCCTV) system general design considerations are as follows:

 

Fence cameras shall be provided with high-resolution picture without geometric distortion, lag or image retention. All cameras shall be Day/Night Type, color camera and shall be able to adjust automatically for varying light intensity. It should cover the largest part of the

outside and inside of the fence at the nearest point of its range.

 

Day/Night Type, Auto-Focus with manual override, Color Cameras to be mounted in dedicated camera poles (provided by the CONTRACTOR). (Security Lighting Poles shall not be used).

 

 

Maximum zone length of 125 meters to be covered by one camera. 

 

A single zone shall be monitored by maximum two (2) cameras.

 

Minimum 10% screen height from the beginning of camera range for the picture of a man standing up at 125 meter.

 

Proper overlapping of coverage of adjacent cameras shall be considered to eliminate dead zone..

 

Day/Night Type, PTZ, Auto-Focus, Color Cameras will be installed in strategic areas (i.e. Inbound/Outbound of main gate, employee entry/exit shades, and outside security control room).

 

All Cameras shall have Image Stabilizer Feature to compensate the vibration caused by wind drift especially when it is zoomed-in to its maximum range.

 

50-inches TFT-LCD Color Monitors inside the Security Control Room shall be able to display images around COMPANY Plant perimeter fence, main gate, employee entry/exit shades, and hallway outside the security control room, parking lots, and the overall view of the plant.

 

In addition to the DCCTV monitoring stations inside the Security Control Room the CONTRACTOR shall also provide DCCTV monitoring stations; two each (2 Ea) 21-inches  Color Monitors at the Security Guard houses of gate at the employee entry/exit shades.

 

Full-Control of the security cameras (e.g. programming, PTZ control with 360 rotation, focus control, pre-positions, sequencing, single/multiple camera display, housing lens shield cleaning – washer and wiper, etc.) shall be done in the Security Control Center through the DCCTV System workstations (e.g. DCCTV system software, GUI software/ interactive map, DCCTV control keyboard, etc.).

 

Maximum ten (10) color monitors shall be designed for the DCCTV system considering only one (1) operator in the control room.

 

The DCCTV system shall be “fail safe”, i.e. any failure in the system component/cabling shall be enunciated in control room.

 

The DCCTV system shall possess a high reliable  motion Detection (VMD) features that provides reliable detection of intruders under a wide range of changing environmental conditions.

 

    The   digital video recording (DVR) System shall be capable of minimizing the probability of false and nuisance alarms caused by small animals, blown debris/papers, birds, clouds, sand storms, rain, moving trees, and wind induced camera pole movements.

 

 AND will record all video events such as alarms received from the DCCTV’s AND, fence detection system, and others.

               

AND also have capability to automatically record pre-alarm and post-alarm video events, which will be available for playback and re-recording for archiving or backup at a later time..

 

 

4.03        Access Control and Door Monitoring System.

 

        The function of this system is to monitor and record personnel and vehicle entry to and exits from the site, and to restrict staff areas of high security.

 

 

        4.03.1 Main gate Entry/Exit Doors.

                               

4.03.2 Security MONITOR  Room and UPS Room.

4.03.3. Turnstile System at Plant Main Gate and Inner Gate.

4.03.4 CONTROLL ROOM OF POWER PLANT.

       

          

        The existing Plant Control Room doors at both Control Room and Security Control Room shall be integrated to the new Access Control and Door Monitoring System to satisfy

       requirements. All doors of the Power Plant Control Room shall be provided with Smart card reader (inside and outside) and emergency exit button inside the control room.  

                               

   ANEW ACCESS CONTROL AND DOOR MONITORING SHALL BE INSTTAL  .           The Security Control Room should be in the  first floor with under ground connections. All processors with UPS should placed in suitable air conditioning room.

                               

        Entry to the areas shall be gained by showing the Smart card to the sensor    . Smart card reader shall raise an alarm if attempts are made to use a damage or tampered card or if the PIN is entered incorrectly. In these circumstances the turnstile or door monitoring system shall deny access to the site.

       

        Communications between the Access Control System Server at Security Control Room and the Remote Controller at Control Buildings, and Gates shall be through optical fiber cables to be provided and installed by the CONTRACTOR. The CONTRACTOR may utilize

 

       Existing communications duct bank and conduit system wherever available. Any additional duct bank and conduit requirements shall be done by the CONTRACTOR.

       

        The access control system shall be able to specify/configure “Duress State” on the card readers and provide different actions (e.g. alarm reporting, call a number, send an email, deny access, etc. Note: These actions shall be selectable/configurable on the system) to be carried out if the conditions set arise. The system shall raise corresponding “Duress Alarm” and carry out the selected/configured actions/options.                  

       

        Alarm raised and events logged by the card readers shall be displayed at the Security Control Room.

 

        “The access control system shall be designed such that the maximum two (2) turnstiles (card readers/keypad for entry & exit for each turnstile) are connected to single controller in stand-alone mode. This stand-alone mode controller should be able to cater the entire range of system card database.

       

        I.D./Access Control System shall be “fail safe”, i.e. any failure in system component/cabling shall be enunciated in control room.

       

        Integrated Security System shall have bilingual (English & Arabic) capability in the following:

 

        System menus/screen.

 

        Messages for display and print.

 

        ID card generation (ID Badging System) and printing at  pp#3  .

                                               

        The security personnel shall be able to generate (i.e. ID Badging Hardware & Software) and program the cards and set access privileges for varying levels of security of the site. Security shall also be able to program cards for predetermine expiry dates and times.

       

        In addition to the Access Control System’s workstations inside the Security Control Room the CONTRACTOR shall also provide Access Control System’s workstations; one each (1 Ea) with 21 inches TFT-LCD Color Monitors at the Security Guard house of main gate the employee entry/exit shades.

 

4.04        Security Control Room

 

        COMPANY new Industrial Security Building  shall be the location for the Security Control Center/Room. This shall employ the following:

 

                4.04.1         Main Computer

 

                4.04.2         DCCTV System Workstations and Command/Control Platform

               

                4.04.3         TFT-LCD Flat Color Video Monitors

 

                4.04.4         DVR

               

4.045          Printers

               

                4.04.6         Console Desk and Heavy Duty Chairs

 

        All transmission and communication lines to the system’s remote elements should use fiber optic cables. The existing communications duct bank wherever available shall be utilized for routing the cables. Any additional duct bank and conduit requirements shall be constructed by the CONTRACTOR.

       

        Graphic displays and event logs shall be grouped according to subsystem intruder detection, DCCTV, access control etc., and event type alarm, equipment malfunction etc. A summary log of all system events shall also be configured in a single display. The graphics (GUI) capability should be multi layered allowing the system to depict sub graphic of individual zones.

       

        Zones must be identified by different colors. Alarms should be enunciated by a flushing graphic at zone accompanied by an audible alert from the microprocessor.

       The graphic  screens should be bilingual .

       The operator  should have direct control for camera switching & PTZ functions  from the Graphics screens

       

        The system software must record and retain the following information and be printed as desired:

       

·         All alarm events; by date, time, zone and classification.

       

·         The automatic system self check by date, time, and results.

       

·         All information about the changes made to system parameters, and all the comments entered into the system by the operator.

 

        The system must permit command and control over the DCCTV system directly from the command and control platform. This control includes all PTZ functions, camera sequencing, frame times, monitor assignment, and camera enclosure lens shield cleaning (i.e. washer and wiper).

       

        The system will be configured to require that all alarm events be classified by the system operators; this information is then retained in the system history file.

       

        Operationally the routine would be as follows:

       

        DCCTV system is active and storing short duration pre-alarm video events (Note: pre-alarm video length shall be configurable between 0 – 2 minutes) on the DCCTV system’s buffer. These pre-alarm video events shall be refreshed/updated automatically, replacing the older pre-alarm video events in order not to congest the DVR buffer/hard disk.

 

An alarm was received (alarm may come from DVR of DCCTV system, fence detection system, access control system or fire alarm system. and enunciated both visually and audibly based on priorities defined.

       

The DCCTV system will display the video of area where the alarm originated. The DCCTV system shall automatically record the post alarm video events, including the pre-alarm video events of that area to the DCCTV DVR system’s hard disk and show a record status on the screen (Note: video filenames shall indicate identifiable details). The DCCTV system shall be able to continue monitoring the entire system and maintain its pre-alarm recording/updating of other locations/zones on the buffer, while recording video events on the hard disk for specific alarm events. 

 

The system must automatically log the date, time, zone in alarm, and hold this information in an active alarm queue.

 

Once the alarm has been investigated the operator is then required to classify this alarm event in order to release the alarm from the active queue. The operator selects the alarm to be classified and is furnish with a number of alarm cause selection from which to choose.

       

The system shall be able to continue monitoring the entire system while investigation for a specific alarm by the operator is going on.

 

The system shall have the capability to configure different priority levels for various alarm types, and shall have a facility to display pre-defined instruction/procedure to the operator in event of each type of alarm.

       

The system software must be bilingual (using both Arabic and English languages) and shall be furnished with flexible multi level password and pass-code access security features, and working files shall be archived on  , disc, DVR or other storage medium. DVRS should be provided with DVD writer for immediate storage and backup.System operators shall be provided with pass-codes to be used for logging on or off duty. System passwords are usually required to modify or changes significant system parameters, to enable or disable alarm points, perform system maintenance operations such as deletion of outdated history files or to make global changes in time, date etc.

 

The entire security system shall be equipped with state-of-the-art components diagnostic system and shall be presented in a manner that is easily deciphered, and equipped with an automatic diagnostic subroutine that can be set at a predetermined time to automatically interrogate and check/evaluate the status of the processor, communication lines, and equipment, critical devices and all power sources.

 

If a non standard condition is detected by the system then discreet graphic alert will be displayed and accompanied by an audible alert to gain the operators attention. The alert graphic must continue to be until the non standard condition has been resolved.

 

System display shall be menu driven with option selected by mouse or from the keyboard.

 

Workstation shall allow personnel to configure the system including display building, programming of site passes and system database.

        Heavy-duty printers shall be provided for printing a real time event and generating reports and screen dumps.

       

        A heavy-duty laser color printer capable of generating copy of frozen image from the DCCTV system shall also be provided.

 

        The system must be configured so that a back-up controller is always on line that can assume control of the entire security system in the events of a catastrophic failure of the primary controller. The back-up system must be continually updated by the primary controller so that all information is accurate and up to date.

         

        The Security Control Room shall be provided with Smart card reader (inside and outside) and emergency exit button inside the control room.     

 

4.05        Road Rising Arm Barriers:  

                       

        ANEW rising arm barrier gates at the plant main gate (in both direction entry & exit) shall be integrated with the   access control system. This will be equipped with both vehicle smart card reader and employee smart card reader.

 

        As the vehicle approaches the gate and/or the arm barrier, the vehicle card reader will read the card in front of the vehicle and at the same time the driver or operator of the vehicle will show his card to the smart card reader. These readers will process the information and if both the car and the driver/operator possess valid clearances to the area then the access control system should be able to grant them access to the facilities either automatically (i.e. the system automatically open the sliding gate or raise the road arm barrier) and manually (i.e. the access control system will give signal to the security guard to open the sliding gate or raise the arm barrier via a manual switch). Granting of access (entry/exit) by either automatically and manually shall be integral to the system’s software and shall be system’s configurable.

 

        Smarty and vehicle card reader shall raise an alarm if attempts are made to use a damage or tampered card and at the same time if one or both of the cards are invalid.

 

        Alarm raised and events logged by the card readers shall be displayed and printed at the Security Control Center.

       

        The barrier shall be equipped with a vehicle force entry sensors attached to a rising arm barrier.

        The barriers should have automatic reversal mechanism  if  it strikes on a vehicle so that it can reverse its direction.

        The barrier should have an Auto closure mechanism with adjustable time which can be programmed after the vehicle has passed over the sensor loop.

        The barrier should have a boom monitoring sensor which can give signal to Alarm monitoring system incase it is broken or loose. The boom monitoring should also have the facility to be  interlocked with the Crash Barriers for higher security.

       

         A safety loop, which is automatically controlled, shall be installed at the plant main gate.

 

        Manual override switch shall be installed inside the guard house to raise/close the arm barriers during emergency, and triggers the alarm in the Security Control Room.

 

4.06        UPS System

 

The system shall interface with local main power supply. The system is an essential service and shall be operational at all times. An uninterruptible power supply unit shall be provided by the CONTRACTOR to support the system in the event of failure of the site power supply. This shall be sized to provide up to four (4) hours support time.

 

UPS System shall be sized to accommodate a minimum of 20% additional power capacity for future expansion.

 

The UPS Room door shall be provided with Smart card reader (inside and outside) and emergency exit button inside the UPS room.

 

 4.07       Employee Entry/Exit Shade

Two (2) New Employee Entry/Exit Shade/Room shall be constructed by the CONTRACTOR under this PROJECT to house the Turnstile system, X-Ray System and accommodate post station for at least two (2) security personnel at the Plant Main Gate .

 

This shade shall be  high density polyethylene .

 

 

4.08     Fire Alarm System

 

The existing fire alarm system of PP3 Power Plant shall be integrated/interfaced to the new Security System.

 

The CONTRACTOR shall be responsible in checking and confirming the compatibility of the existing Fire Alarm System to be integrated to the new Security System. Any modifications, and additional materials needed for the successful integration of the Fire-Alarm System shall be provided by the CONTRACTOR as part of this PROJECT.

 

4 .9         Crash-Rated Main Plant Sliding Gate

 

New crash-rated linear sliding gate and its associated electromechanical components, motors and controls shall be provided and installed by the CONTRACTOR at Power Plant Main Gate.

 

The crash-rated sliding gate and auxiliary equipment shall be of proven design and the Manufacturer shall have a minimum of 5 years documented field experience for all major components and design features.

 

The gate design and specifications shall have successfully passed an actual full-scale crash test conducted by a qualified independent agency in accordance with D.O.S. Specification SD-SDT-0201 of K12/L3.0.

 

All components of the crash-rated sliding gate system shall be capable of working in various environmental conditions.

 

4 .10       Crash-Rated hydraulic barrier at Main Plant Gate

 

New crash-rated rising road barricade and its associated electromechanical components, hydraulic power systems, traffic/warning lights, and controls shall be provided and installed by the CONTRACTOR at    Power Plant Inner Gate.

 

 

The Crash-rated rising road barricade and auxiliary equipment shall be of proven design and the Manufacturer shall have a minimum of 5 years documented field experience for all major components and design features.

 

The gate design and specifications shall have successfully passed an actual full-scale crash test conducted by a qualified independent agency in accordance with D.O.S. Specification SD-SDT-0201 of K12/L3.0.

 

All components of the crash-rated flush mounted rising road barricade system shall be capable of working in various environmental conditions as specified in Section 3.02 of this document. The barricade should be made of Hot Dip Galvanized steel to extend the lifetime of the barricade and resist bad weather conditions.

 

Refer to Section 6.10 of this document for further specification details of the crash-rated rising road barricade.

 

        The proposed crash-rated flush mounted rising road barricade at the inner gate (in both direction entry & exit) shall be integrated with the new access control system similarly with the rising-arm barrier. Granting of access (free-pass and guard positions of barricade) may be either automatically (i.e. through access control system) or manually (i.e. through switch buttons by the operator/guard), shall be integral to the system’s software and shall be system’s configurable.

 

        Manual override switch shall be installed inside the guard house to raise/close the arm barriers during emergency, and triggers the alarm in the Security Control Room

 

*** END OF SECTION 4.0 ***

 

 

SECTION  5.0      SCOPE OF WORK

 

5.01        Project Description

 

The work to be performed under this Project consists of the design, supply, construction, installation, training and maintenance of New COMPANY Integrated Security System to be located     Power Plant consists of the following subsystem

 

5.01.1         Fence Detection System

 

i.          Fence Detection System shall employ two (2) types of detection system

 

                                Vibration Detection System

 

                                Microwave Detection System   

 

ii          This detection system shall cover the COMPANY perimeter fenced area of approximately ……. meters as illustrated on the attached drawings   .

 

 

                                 

 

5.02.1         DCCTV System

 

·          Digital Closed Circuit Television (DCCTV) System made of cameras, units,   Digital Video Recorder (DVR),  monitors, controllers, workstations, heavy-duty laser color printer    .

 

·         PTZ, Day/Night type, Color Cameras shall be installed around the inner side of the perimeter fenced area. These cameras shall be mounted (fixed oriented) on dedicated camera poles with an approximate height of 5.0 meters. The CONTRACTOR shall determine the actual quantity and location of cameras to be installed and ensure that all strategic areas are adequately covered.

 

·           Day/Night type, Color Cameras (mobile oriented).   cameras shall be installed at convenient locations in order to provide an overall plant monitoring facility for safety purpose.

 

·         A PTZ, Day/Night type, color camera shall be installed outside the Security Control Room to monitor the corridor and the entry door of the Control Room.

 

·         A PTZ, Day/Night type, color camera shall be installed in appropriate places in the  Gate vicinity, to monitor the inbound and outbound access of vehicles and employees to the plant and to be displayed in a separate monitor screen (inbound/outbound) in Security Guard House  gates.

 

·         A PTZ, Day/Night type, color camera shall be installed in the Employee Entry/Exit  gate, to monitor the entrance and exit of people on foot to the plant and to be displayed in a separate monitor screen (inbound/outbound) in security guard console desk at the Employee Entry/Exit of main gate.

 

 

5.02.2         Access Control and Door Monitoring System:

 

·         Access Control System consists of, Smart card readers, emergency exit buttons, ID Badging Facility including all hardware, software, and accessories.

 

·         The CONTRACTOR shall install the combination of both the Smart card reader and keypads on the following areas:

           

                Main gate (entry/exit)

                Security Control Room Door (entry/exit)

               MAIN CONTROL ROOM OF POWER PLANT

 

·         Door monitoring and control system made of hardware, Smart card reader, software, and accessories.

 

·         The quantity of Smart ID Card for COMPANY for employee, contractors, visitors, and students is 500 Smart cards. Also, Smart ID Card for Vehicles   be supplied. The design of the cards will be provided at the later date (the ID badging facility shall be capable of designing the card).

 

·         The CONTRACTOR shall install a vehicle access reader and smart card reader (for driver/passenger) .

   

5.02.3         Security Control Room

 

·         Security Control Center consists of console structure, heavy-duty chairs, computers, printers, monitors, interface units, telephone sets, and plasma display.

·         Separate partition/ room  should be provided for the server and  Rack room. This room should  have a separate temperature control mechanism.

 

 

5.02.4         Remote Administration Terminal

                    The CONTRACTOR shall provide a remote administration terminal with a printer at SEC-WRB Hqs. to provide remote configuration, troubleshooting, and reporting facility for Integrated Security System.

 

5.02.5         The existing fire alarm system shall be integrated to the new security system..

 

5.02.6         Each system shall be capable of future expansion and addition/inclusion to install in parallel or at a later stage throughout COMPANY Plant, and COMPANY Expansion Projects.

 

5.02.7         Uninterruptible power supply units complete with batteries and other accessories. This shall hold the system of up to 4 hours as detailed elsewhere in this document.

 

5.02.8         Wiring tools and any other materials required for installing and commissioning the system.

 

5.02.9       Quantities, general locations, and flow diagrams of all the equipment shall be shown in the drawings. Exact mounting locations shall be such that the equipment is readily accessible during maintenance.

 

5.02.10      All above facilities shall be installed and integrated together to form one complete reliable system.

 

5.02.11      The Integrated Security System for COMPANY shall be installed based on the following:

5.02.12      Road Barriers  

               

                    The CONTRACTOR shall  integrated security system   with the   rising arm barriers  . Any additional materials or modifications necessary for the barriers to be compatible with the new integrated security system shall be done by the CONTRACTOR.

 

 .

5.02.13                   The existing fire alarm system shall be integrated to the new security system.

5.02.14                   New crash-rated linear sliding steel gate shall be provided and installed at Plant’s Main Gate.

502.15                 crash-rated BARRCADE SYSTEM.    

 

5.02.16                 Bidirectional Stainless Steel TURNSTILE

 

 

5.03        Summary of Work

 

5.03.1         The CONTRACTOR shall provide the detail engineering works, including design, materials selection and documentation generation base on this document.

 

5.03.2.        The CONTRACTOR shall furnish all supervision, materials, supplies, labor, construction tools and equipment, listed as described on the drawings or in these specifications, subject to qualifications, conditions, or exceptions as noted to complete the work.

 

5.03.3         Construction of the proposed Integrated Security System and associated facilities shall include, in addition to electrical and civil works, all connected services and systems such as communication system.

 

5.03.4         Rendering all necessary assistance and coordination with other Contractor's selected by the COMPANY for the supply and/or installation of items excluded from the Contractor's scope of work and ensuring that the construction requirements and sequence of execution match with such works by others, shall be the responsibility of the CONTRACTOR.

 

5.03.5         These specifications apply to the entire work covered by the contract drawings and are to provide guidance in the execution of all parts of the construction work under this contract. Compliance with the regulations of the High Commission for Industrial Security for developed planning and Safety Security Codes are essential and shall if required overrides the contents of these specifications.

 

5.03.6         The CONTRACTOR shall provide all supervision, materials, supplies, labor, construction tools, and equipment for temporary structures and facilities.

 

5.03.7         The CONTRACTOR shall carefully examine the premises before submitting his proposals. Before the execution of the work, the CONTRACTOR shall check existing conditions and all dimensions involved in the project to ensure compatibility with the drawings, proper coordination, and interfacing.

 

5.03.8         The CONTRACTOR is assumed to have visited the site to acquaint him with all the conditions relevant to the execution and successful completion of the work No claim shall be entertained on this account except where contract documents make definite provision for the adjustment of cost or extension of time due to conditions not readily foreseeable.

 

5.03.9         Any items of work deemed necessary for the proper execution and completion of the project and which are not covered by the drawings and specifications and for which amendments and change orders are issued, shall be performed by the CONTRACTOR in accordance with the approved standards and specifications and good engineering practices of the trade involved.

 

5.03.10      The CONTRACTOR shall, unless otherwise stipulated, secure and pay for all permits and approvals required to be obtained from any government AGENCIES/COMPANY authorities under whose jurisdiction the work is being performed.

 

 

5.04        Related Work:

 

5.04.1         Coordination:

 

i.          This section covers all the coordination required to execute the project.

 

ii.         Description

 

a.         All works shown in drawings and in specifications shall be coordinated under this contract.

 

b.         Coordinate the efforts of all subcontractors, vendors and individuals. Cooperate and coordinate the work with others operating in areas to or in the vicinity of the construction site.

 

c.         The CONTRACTOR shall be responsible for advance notification for required tests and inspections specified in the technical section for certain items.

 

d.         Inform the COMPANY REPRESENTATIVE about such shutdown well in advance.

 

e.         The CONTRACTOR shall not allow or cause any of his work to be covered up or encased until it has been inspected and approved by the COMPANY REPRESENTATIVE, should any of his work be enclosed or covered up before such inspection, he shall uncover the work for inspection.

 

 

5.04.2         Submittals

 

i.          Description

 

a.         Works specified in this section are all submittals to be made by the CONTRACTOR.

 

b.         The CONTRACTOR shall review submittals for compliance with codes and standards and contract document requirement, before submission to the COMPANY.

 

ii.         Submittals:

 

a.         Construction Schedule

 

            Before the work is started, the CONTRACTOR shall prepare a detailed schedule of all construction operations involved indicating the sequence of work, time of starting and completion of each activity and installation dates of major items of equipment manpower loading, cash flow, etc.

 

b.         Samples

 

            Three samples of all materials proposed for use in works shall be submitted in three (3) sets for approval by the COMPANY REPRESENTATIVE, but limited to the items as specified to be submitted in the individual sections. Acceptance of certifications of test and inspection shall not eliminate the right of the COMPANY to reject any materials not conforming to specification even after delivery and installation.

 

c.         Shop Drawings and Engineering Data

 

            Shop drawings and engineering data covering all products equipment fabricated materials, and all other construction activities to be furnished under this contract shall be submitted to the COMPANY for review and approval. These data shall include drawings and descriptions, in sufficient details to show the kind, size, arrangement and operation of component materials and devices, and also the connections, anchorage, supports with dimensions needed for installation and correlation with other materials and/or equipment

 

5.04.3         Quality Control

 

i.          Description

           

a.         The CONTRACTOR shall be responsible for the quality control conforming to standards set forth for each item and materials.

 

b.         All electronic modules and components used within the system shall be functionally tested and burned-in by the vendor/manufacturer prior to system assembly.

 

c.         The system components shall be assembled as per job requirements and given a complete functional hardware test including a 24 hours burn-in.

 

d.         The entire system including any application software shall be given a complete point-to-point functional test prior to a factory acceptance test (FAT).

 

e.         The CONTRACTOR shall notify the owner of this intention to carry out factory test.

 

f.          The CONTRACTOR shall furnish the COMPANY with a detailed procedure for review and acceptance prior to testing. This procedure shall form a checklist for use during the FAT. The COMPANY shall be provided with a copy of the complete checklist.

 

g.         The test witnessed by the COMPANY REPRESENTATIVE shall include loop-to-loop check of each input, output and control function for proper operation and display.

 

h.         All testing, including requests, reports, etc., are the responsibility of the CONTRACTOR. The COMPANY REPRESENTATIVE reserves the right to verify the test by any testing laboratory or independent agency.

 

i.          If the COMPANY desires that any person or firms appointed by him for his purpose periodically inspect the work, the CONTRACTOR shall provide facilities and access to the work at all time as required to facilitate such inspections.

 

j.          CONTRACTOR shall be responsible for the supervision of the entire work and maintain competent construction management team on the job who is authorized to act in all matters pertaining to this project.

 

ii.         Inspection of Work

 

a.         COMPANY shall at all times have access to the work wherever it is in preparation or progress and the CONTRACTOR shall provide facilities for such access and for inspection.

 

b.         If the specification, Company's instruction, laws, ordinances or any public authority require any work to be specially tested or approved, the CONTRACTOR shall give the COMPANY or any other authority than the COMPANY, timely notice of its readiness for inspection, and date fixes for

 

 

           such inspection. Inspection by the COMPANY REPRESENTATIVE shall be promptly made, and where applicable, at the source of supply. If any work is covered up without approval consent of the COMPANY REPRESENTATIVE, be uncovered for examination at the Contractor's expense.

 

c.         All inspection and test shall be performed in such a manner as not to unnecessarily delay the work. Special, full load and performance test shall be as prescribed in the specification. The CONTRACTOR shall be charged for any additional cost of inspection when materials and workmanship are not ready at the time inspection is requested by the CONTRACTOR.

 

d.         Defective work materials may be condemned by the COMPANY at any time before the final acceptance of the work, and when such work has been condemned, it shall be removed at once by the CONTRACTOR from the line of the work.

 

e.         Failure or neglect on the part of the Engineer to condemn or reject any bad or inferior work or materials shall not be construed to imply an acceptance of the work if such bad or inferior work or materials are discovered at any time prior to the final acceptance of the work by COMPANY and release the CONTRACT.

 

f.          All the safety regulations govern by the COMPANY is to be followed in the site.

 

5.04.4         Construction Facilities and Temporary Controls

 

                    i.          Description of Work

 

a.         The CONTRACTOR shall provide and maintain on-site and off-site temporary facilities and temporary control necessary for the performance of the work.

 

b.         Materials may be new or used, but must be adequate in capacity, safe for the conditions, and in conformance with the requirements of applicable codes and regulations.

 

c.         The CONTRACTOR shall provide a temporary site office at the approved location for the use of the COMPANY REPRESENTATIVE and engineer.

 

5.04.5         Material and Equipment

 

                    i.          Description

 

a.         Specified materials and equipment establish the standard of quality intended.

 

b.         Where available and complying with the requirements, provide standard materials and equipment, which have been used previously and successful in similar applications indicated.

 

                                ii.             Materials

 

a.         All materials and equipment used in the works shall be of the best quality of their respective kinds as specified herein obtained from source and suppliers approved by the COMPANY and shall comply with the test prescribed and requirements stipulated the standard listed Section 2.0 (Applicable Codes and Standard).

 

b.         When reference is made in the specifications to trade names or to the names of the manufacturers such reference are made solely to designate and identify the quality of materials or equipment. The CONTRACTOR shall have the option to elect any materials or equipment, which are considered equal and suitable to those specified with the written approval of the COMPANY.

 

c.         The CONTRACTOR is required to use available in-Kingdom produced materials and equipment and in-Kingdom fabricated materials that meet the specifications as matter of preference and for speedy execution of the work. The CONTRACTOR shall plan and procure long lead items well in advance to meet the scheduled activity and execution completion dates.

 

d.         Samples of all materials proposed for use in the works shall be submitted for approval by the engineer, but limited to the items as specified to be submitted in the individual sections. No materials shall be used in the works without the written approval of the COMPANY.

 

e.         All manufactured articles, materials and equipment shall be applied, installed, connected, erected, used, cleaned and conditioned as directed by the manufacturers, unless herein specified to the contrary.

 

5.05        Electrical Works:

 

5.05.1         General Provision

 

                    5.05.1.1.            General

 

·         The CONTRACTOR shall furnish all labor and materials necessary to install, complete and ready for use, the power, all integrated security system equipment, grounding, control,   and  , including the installation access, excavating, concrete, paint for electrical work and wiring of miscellaneous instrument and devices, as indicated on the drawings and as herein specified.

 

·         The CONTRACTOR shall install the whole of the electrical work in a professional workmanship and substantial manner and in strict conformance with the latest rules and requirements of the United States National Fire Protection Association Standard No. 70 (National Electrical Code) and with the requirements of Local Authorities having jurisdiction.

 

·         Different National or International Standards and Codes that correspond to the American ones may be used, provided that their requirements are not less stringent. All works shall be done according to the same standard.

 

·         All underground cable shall be in conduit, even if the Contractor proposes direct buried armored type cables.

 

·         The system shall interface with local main power supply. The following voltage levels available at COMPANY are:

 

220/380 VAC  or

 

                127/220 VAC 

 

·         An uninterrupted power supply unit shall be provided to support the entire security system.

 

                The unit shall provide power to the following facilities:              

 

 

a.         Fence vibration and microwave   detection system

 

b.         Digital Closed Circuit TV System (DCCTV)

 

c.         Access Control System  

 

d.         Rising Arm Barriers  

 

e.         Door Monitoring/Alarm Units  

 

f.          Turnstile System  

 

h.         Crash-Rated Plant Sliding Gate

 

i.          Crash-Rated Rising Barricade at Plant Inner Gate

 

 

g.         All Facilities installed inside the security control room for integrated security system and covered in the CONTRACTOR Scope of Work.

 

The UPS system design shall comply with SEC Standard requirements.

 

Other security system shall be fed separately with a minimum of one circuit breaker, depends on load size and location.

 

Circuit protecting devices shall be well coordinated for optimum reliability, such as ground fault and overload relays.

 

The CONTRACTOR shall specify lead-acid type batteries for the UPS system.

 

                    5.05.1.2             Basic Materials Section and Methods

 

·         All electrical materials and equipment shall be new and standard product of the latest approved design. Like items for the same service, shall be the products of a single MANUFACTURER in order to provide maximum interchangeability. All items shall be properly stored to prevent deterioration due to rust or entrance of dust.

 

·         All wires and cables shall be new. Cables shall have permanent identifications conforming to NEMA and UL standards. Conductors shall be copper, annealed Class-B standard. Cables shall be multi-core and insulation shall be suitable for permissible conductor temperature of 90 degree centigrade.

 

 

                    5.05.1.3             Nameplates, Identifications, and Markings

 

·         Nameplates shall be installed on all devices or pieces of equipment for which the use of identification may not be readily apparent, such as, but not limited to, relays, contactors, push-button indicating lights and switches.

 

·         The end of all wires cable including splices and joints made in junction boxes and at terminals shall be marked for identification. Instructions and circuit details shall be furnished in Arabic and English with Arabic taking precedence as necessary for operation and safety. All controls shall be also located to permit observation of the equipment controlled and at an effective height for ready accessibility of operation.

 

                    5.05.1.4             Interference and Erroneous Locations

 

·         The location of electrical equipment, devices, outlets, similar items, as indicated on the drawings, are the approximate only. Exact locations shall be determined or accepted during construction.

 

·         The CONTRACTOR shall verify in the field all data and final locations of work, done under sections of specifications, required for the execution of electrical work.

 

·         In case of interference with other work or erroneous locations with respect to equipment or structures, the CONTRACTOR shall be responsible for all labor and materials necessary to arrange and perform the work in an acceptable manner.

 

                    5.05.1.5             Protection of Electrical Equipment

 

·         Electrical equipment shall be protected from weather especially from water dripping or splashing upon it, at all times during shipment, storage, and construction. Any damage or defective item shall be replaced by the CONTRACTOR without additional charge.

 

                    5.05.1.6             Approval and Marking of Equipment

 

·         Electrical devices and materials shall be as listed and/or labeled by the Underwriters Laboratories Inc., or equivalent recognized institution wherever standards have been established.

 

·         All equipment shall have the name or trademark of the manufacturer, the rating in volts and amperes, and other pertinent information clearly marked thereon on a location where they can be observed easily after installation. No work shall proceed until shop drawings and samples have been approved. All works shall conform to the approved shop drawings and

 

5.05.2         Installation

 

                    5.04.2.1             Installation of Panels

 

·         Before installing equipment and devices, the floor shall be cleaned.

 

·         Self standing panels shall be installed carefully checking for level and perpendicularly in all directions, and liners shall be used to correct the level and perpendicularly when necessary.

 

·         When panels are installed in a line, care must be taken to prevent irregularity, especially taking into consideration level and perpendicularly, and joint bolts shall exactly be tightened to prevent looseness and failure.

 

·         When equipment and devices are delivered and installed, care shall be taken to prevent their coatings from damage. When positioning has been determined, equipment and devices shall be fixed to the foundations as soon as possible.

 

 

                    5.05.2.2             Installation of Electrical Equipment and Devices

 

·         When equipment and devices are installed, positioning shall be determined taking into consideration the following items:

a.         Locations, which permit easy access for operation and maintenance.

b.         Locations, which are not significantly affected by vibration.

c.         Locations, which are not affected by stream and exhaust gases and which are not close to high temperature pipes or equipment.

 

·         Bolts having sufficient strength are to be used, and spring washers to be provided to prevent looseness.

 

·         Equipment and devices shall be rigidly installed to resist their weights, and care shall be taken to ensure that they are water proof, moisture proof and heat resistant.

 

·         The standard installation heights of equipment and devices shall be as follows:

 

 

LOCATION

ELECTRICAL

EQUIPMENT AND DEVICES

HAZARDOUS AND ORDINARY OUTDOOR LOCATIONS (m)

ORDINARY INDOOR LOCATIONS (m)

a.   Distribution Boards (top of board)

2.0 above floor

1.8 above floor

b.   Local Push Bottom Station (center of P.B. Station)

1.5 above floor

1.5 above floor

c.   Outlet (center of outlet)

0.8 above floor

0.3 above floor

d.   Tumbler switches (center of switches)

1.2 above floor

1.2 above floor

 

 

 

5.05.2.3     Cable Work

 

·         Cable and wires which are specified in wiring diagrams, connection diagrams or other specifications shall be used for works. Splicing of cables should not be executed in principle. If splicing is unavoidable, it shall only be executed with the approval of COMPANY.

 

·         Cable sheaths shall be black, and identification of power and control cables shall not be performed.

 

·         The cables shall be newly manufactured.

 

·         Color identification of cable conductors shall be as follows:

 

 

 

APPLICATION

No.  Of

CONDUCTORS

COLOR

IDENTIFICATION

Low-Voltage power and for control cable

 

2

 

Black & White

 

3

Red (U), White (V) and Black (W)

 

4

Black, White, Red & Green

 

6

By Numbering from 1 and Over

 

 

 

 

·         Color identification of wires shall be as follows:

 

127 VAC                            :       Red and white (white neutral phase)

 

220 VAC                            :       Red and red

 

Grounding wires              :       Green with yellow stripes

 

·         Cable termination caps to be provided on both cable ends, for Low Voltage and control cables.

 

                Cable number tags, which are specified in design drawing to be attached to cables.

 

·         Underground Pipe System (Duct Bank)

 

a.             Non-metallic pipes of minimum 50 mm (2”) diameter shall be used for underground pipe system.

 

b.             The earth shall be excavated, and then tamped. On locations having weak ground, ballast shall be placed and then tamped, and underground pipe system shall be constructed.

 

c              Pipe connection shall be made by adequate couplings and sealed.

 

d.             Power and control cables must not be laid in the same pipe.

 

e.             The cable shall utilize maximum of the conduit space allowed in accordance with NEC.

 

 

 

·         Laying Cables

 

a.             Before laying cables and conduits, the site (i.e. laying ground) shall always be cleaned and inspected to remove foreign matter. In addition, cables shall carefully be laid to prevent them from damage due to fall of scaffolding plates and nails etc.

 

b.             When leading cables in conduits, cables shall not be coated with hazardous substances such as oil and grease. If coating is unavoidable, paraffin or mica powder shall be used.

 

c.             In principle, cables to be laid on cable rollers to prevent unreasonable force on cables, and tensile strength, which the cable manufacturer recommends, shall be observed.

 

d.             Cables shall be laid with minimum bends. When cables require bending, it shall conform to the standard stated elsewhere in this specification.

 

e.             Cable from cable pit or duct to equipment shall be installed in conduit pipe.

 

f.              After cables have been laid, adequate measures shall be taken to protect them from damage until permanent protective devices are provided.

 

·         Cable Gland on Terminal Box

 

a.             The lead-in method of cables to terminal boxes to be as follows:

 

                Flameproof packing type cable gland shall be used for flameproof terminal boxes.

 

                Flameproof packing type cable gland shall be used for safety-increased terminal boxes.

 

·                     Cable Termination

 

a.             When termination is done by taping, self adhesive tape and rubber tape shall be used.

 

5.05.2.4     Conduit Works

 

·         Conduits and Accessories

 

a.             Rigid hot dip galvanized steel conduits of minimum size 25 mm diameter and their accessories shall be used for conduit works.

 

·         Installation of Boxes

 

a.             Where pipes are longer than 30 m. Pull boxes shall be provided.

 

b.             Where there are more than 2-90 degree pipe bend requirements, pull boxes shall be provided.

 

c.             Where there are more than four (4) branches, joint boxes shall be provided.

 

d.             The boxes shall be rigidly fixed to buildings or supports.

 

e.             The boxes covers, which are located two meters above ground, shall be faced to platforms or stages.

               

·         Joint of Conduits and Accessories

 

a.             Joints of conduits and accessories in hazardous locations shall be executed as following:

 

                Screw thread shall be ISO parallel thread, and shall fit each other by more than 5 threads.

 

                Conduits transitions shall be jointed by couplings and explosion-proof union couplings shall be used at the one end of conduit run.

 

                Conduit joints shall be coated with sealant.

 

b.             Joint of conduits and accessories in non-hazardous locations shall be executed as follows:

 

                Screw thread shall be ISO parallel thread and shall be fit each other firmly.

 

                Conduits transitions shall be jointed by couplings, and union coupling shall be used in one end of conduit run.

 

                When conduit is jointed with box, conduit shall be tightened to the box by lock nuts and bushing shall be provided.

 

                When boxes or cabinets are coated with paint, paint shall be completely removed, and lock nuts shall be tightened to perform electrical connection.

 

·         Installation of Conduits

 

a.             Support of conduit shall be provided in every 1.5 m on hazardous locations and every 2 m on non-hazardous locations.

 

b.             Conduit support shall be welded to steel structure.

 

c.             Conduits shall be installed avoiding unnecessary bends, and measures to prevent condensation shall be provided.

 

d.             Normal bends shall be installed avoiding unnecessary bends, and measures to prevent condensation shall be provided.

 

e.             Bending radius of the conduits shall be more than 6 times of the conduit inside diameter.

 

f.              U shape piping shall not be performed for conduit runs to avoid water condensation.

 

g.             Conduit shall not be installed at locations, which are exposed to the high temperatures equipment or piping.

 

h.             Conduits shall be provided with bushings, at the cable pit or duct side to prevent cables from damage during installation of cables into conduits.

 

i.              Grounding resistance of conduits to be less than 100 ohm.

 

·         Wiring

 

a.             Before installing cables into conduits, the inside surfaces of conduits shall be cleaned to prevent cables or wires from damage.

 

b.             Wires in boxes shall have enough spare length for maintenance.

 

c.             Connections of wires to boxes and equipment shall be performed by solder less sleeves or terminals, and tape shall be sufficiently lapped on the connections.

 

d.             Connection must not be done in conduits.

 

e.             When cables or wires are extended to conduit etc., wiring works should be executed to ensure that cabling or wires should not have abnormal stress.

 

·         Sealing Fitting.

 

a.             Explosion Proof sealing fittings shall be provided at the following points of division 1 locations.

 

                Boundary of hazardous location and non-hazardous locations.

 

                Within 45 cm from terminal boxes or boxes.

 

                Every 15 m. when conduit length exceeds 15 m. and conduit sizes are 54 mm and over.

 

b.             Connection and branching of wires must not be performed in sealing fittings.

 

c.             Drain type sealing fittings shall be provided to remove drips from the conduits, which come down to boxes or devices.

 

d.             Sealing compound shall be filled exactly, and thickness will be more than the inside diameter of a conduit and minimum 20 mm.

 

e.             Sealing compound shall be filled after wiring check and operation test have, completed. After that, the filling part shall be completely plugged.

 

·         Flexible Fitting Connection

 

a.             Flexible fittings shall be provided for conduit jointing to motors and devices where the adjustment of position or angle is required.

 

b.             Flexible fittings shall be provided to release the stress of conduit runs.

 

c.             Length of flexible fittings shall be 1 m for the 42 mm diameter and above, 0.5 m for the 36 mm diameter and less.

 

d.             Flame proof type flexible fittings shall be used in division 2 locations and water-proof types flexible fittings shall be used on outdoor locations.

 

                When bending flexible fitting, radius shall be more than 5 times of outside diameter of flexible fittings. Flexible fittings must not be twisted.

 

·         Grounding

 

a.             Grounding Conductor:

 

                Bonding and grounding conductors shall be insulated stranded annealed copper wire.

 

                Grounding conductors within cable assemblies shall be insulated and shall be of the same materials and stranding as the line conductors.

 

b.             Grounding Methods:

 

                Burial depth of grounding conductor shall be more than 60 cm.

 

                Where the wiring method is buried cable, grounding conductors shall be laid in cable trench as far as routing permits.

 

                In case the wiring method is underground pipe, grounding conductors shall be laid in the pipe as far as routing permits.

 

                Where grounding wire passes under the main roads, paved roads, or paved areas they shall be run in rigid metal conduit pipe sleeves or duct bank.

 

                In case grounding wire pass under the roads which are not paved, burial depth or wire protective cover shall be considered to prevent damage to the wires from anticipated heavy loads such as mobile cranes or equipment transport.

 

c.             Grounding:

 

                Grounding resistance shall be based on the worst season through out the year considering seasonal variations in soil condition (total resistance shall be 10-15 ohms).

 

                Grounding electrodes shall consist of rods and shall be as follows:

 

                Rods shall be copper lad steel.

 

                Tops of rod shall be 75 cm below grade as minimum.

 

                The grounding conductor shall be connected to the rod by silver soldering welding.

 

                Distance between the grounding electrodes shall be more than 3 meters.

 

 

d.             Grounding Connection:

 

                Grounding conductor connection to structures and equipment shall be made above ground and as follows:

 

                Grounding wires shall be connected to grounding piece.

 

                If splices or branches are required in underground runs, they shall be made using compression connectors.

 

                Screw-type solder less connectors or similar mechanical connectors shall be used in underground runs.

 

                Bolt and nut (with washer and spring washer) for grounding connection shall be stainless steel.

 

e.             Enclosure Grounding:

 

                Metal enclosure for wire and cable such as conduits, cable tray and raceway shall be grounded.

 

                Grounding wire connection to metal enclosure it be made by solder less terminal.

 

f.              Grounding wire stub up points to the ground shall be as follows:

 

                Conductors shall be protected by non-metallic conduct pipe or sleeves.

 

                Sleeves shall be extending a minimum of 0.3 m below grade and 2 m above grade.

 

                Non-metallic pipe or sleeves shall be rigid polyvinyl chloride or high density polyethylene.

 

*** END OF SECTION 5.0 ***


 6.0      SYSTEM SPECIFICATION

 

6.01        General

 

6.01.1         Overall system configuration drawing shall be submitted indicating the following as a minimum for the, fence intrusion, ID/Access Control, DCCTV, Door Monitoring,, UPS System  :

 

·         Signal flow diagram from sensors/field devices up to the security control room, indicating all interface equipment.

 

·         Cable configuration indicating number of cores used and spare.

 

·         Integration/networking in control room indicating all the subsystem - alarm management system, DCCTV system, ID/Access control system), hardwire semi-graphic mimic and etc.

 

6.01.2         All the system components including hardware and software shall be fully interchangeable.

 

6.01.3         The entire security system shall be “fail safe”, i.e. any failure in the system component/cabling shall be enunciated in control room.

 

6.01.4         The entire security system shall be equipped with state-of-the-art components diagnostic system and shall be presented in a manner that is easily deciphered, and equipped with an automatic diagnostic subroutine that can be set at a predetermined time to automatically interrogate and check/evaluate the status of the processor, communication lines, and equipment, critical devices and all power sources.

 

6.01.5         A 25% spare capacity shall be installed (or built) into the system for following as minimum

 

·         All type of main cables (fiber, power, signal, etc.)

·         All type of   cables connection for all camera are fiber

·         Input/output hardwired points for monitoring and controlling units. The actual/spare numbers for the proposed cable and input/output devices shall be indicated.

·         System database and storage capacity.

 

6.01.6         All major components of the system (i.e. Computer Hardware, Controls, Signaling and Data Communication Network etc.) shall be fully redundant.

 

6.01.7         The overall system shall be designed for high degree of availability considering mean time to repair of 2 hours and 24 hours for minor faults and major faults respectively.

 

 

6.01.8         All hardware particularly planned to be installed in the field shall be proven for similar environment and the vendor shall provide installation references in KSA/Gulf countries.

 

6.01.9         All box enclosures utilized in the system shall have a tamper monitoring device that will activate the alarm at Security Control Room in case of box tamper.

 

6.01.10      A list of various international standards according to which the proposed hardware is designed shall be provided.

 

6.01.11      Tentative requirements for preventive maintenance schedule of all components shall be provided                 .

 

6.02        Fence Detection System    

 

                6.02.1         Vibration Detectors

 

                    The intruder alarm and indication methods shall comply with the regulation set out in HCIS SSD-15. “Intruder Detection System” and Section 5.0 of HCIS specification pertaining to perimeter intruder detection and shall meet or exceed the following specification. Inspection of the condition of current fence will be the responsibility of each CONTRACTOR prior to quotation.

 

i.              Intruder alarms shall be displayed on consoles in main control room and recorded in the system event logger.

               

ii.             Audible indication alarms shall be made available. An option for sound suppression shall be included.

 

iii.            The fence detection system shall be linked to the DCCTV cameras, so that when an alarm is activated, the video events of the point of intrusion can be recorded (both pre-alarm and post-alarm) and observed on monitors within the control room and guard houses. This event shall occur automatically or manually, depending on the preference as configured on the system by the operator at the Security Control Room.

 

iv.            Detectors shall have a very low false and nuisance alarm rate. The detection method shall prevent alarms resulting from small animals entering the perimeter detection zones and those caused by weather effects such as sand drifts, flying birds, papers, and other debris. A rate of one (1) false alarm per month per zone is acceptable.

 

v.             The detection method shall be secure against radio frequency and electromagnetic interference and acoustic effects.

 

vi.                  The detection field shall cover the entire fence, including the fence height being a minimum of 2.9 m. The CONTRACTOR shall confirm full compliance with this minimum requirement.

                The digital signal processing shall enable detection and analysis of sensor cable stimulation. The digital signal Processor (DSP) also provides discrimination between natural phenomena and intrusion attempts. Using a pre – programmed algorithm senses wind effects and continuously adjusts the system sensitivity to components.

 

vii.           The detector shall withstand the environmental and climatic conditions as detailed on Section 2.0 of this document.

 

viii.          The detector shall be easy to maintain and repair. The system diagnostics shall include detector faults and malfunctions.

 

ix.            An alarm shall be activated if attempts are made to climb the perimeter security fence.

 

x.             An alarm shall be activated if attempts are made to cut the perimeter security fence.

 

xi.            The total fence areas shall be divided, possibly in equal length not exceeding 250 meters.

 

xii            The cable outer sheath shall be of the polyethylene group of sheathing grade polymers and must be resistant to environmental degradation with and anticipated life of not less than twenty years.

 

xiii           The design of the sensor cable should be such that any electromagnetic interference shall not cause  any degradation of system performance.

 

xiv.          The cable shall have uniform sensitivity along its entire length.

 

xv.           Sensor cable shall be terminated in an end of line resistor to provide tamper alarms in the event of any attempt to short circuit or cut the sensor cable.

 

xvi           Signal analysis can be performed  at the control center or locally at each zone location, incorporating  individual zone setting for sensitivity, actuation time delay (minimum of zero) and count.

 

xvii          The fence mounted interface unit shall be  remotely relocated in the control room and shall withstand local environment mentioned elsewhere in this document.

 

The fiber alarm processing unit should be advanced next – generation alarm processor compatible with insensitive lead – in fiber optic cable. The use of intensive lead – in fiber allows the APU to be mounted up to 20 Kilometers away from the protected zone, leaving only the inert fiber optic sensor cable deployed in the zone

The APU can connect to and support sensor cable from two detection zones regardless of their applications. Both channels support up to 5 Km, of senor cable

.

xviii         The interface shall convert the sensor cable signal into a medium for transmission to the central console and provide zone tamper monitoring  and activation to the control room. The internal calibration drifts of the interface units shall be kept to a minimum and CONTRACTOR shall explicitly state the frequency of calibration on yearly basis.

 

xix           Sensor cable and feeder cable connections shall be made via a multi-way terminal block within the interface enclosure. Cable entry into enclosure shall be via appropriately sized weatherproof glands. Surge suppressors shall be fitted to all connections.

 

xx.           Power Supply: All system electronics shall be supplied from UPS located at ISD Building adjacent to security control room and must be fitted with over voltage protection. Short circuit and ground voltage protection shall be as per standards.

 

 

xxi           The control system shall provide visual and audio indications of activity on the perimeter for each zone on a hardware semi-graphic panel and PC console/GUI Interactive Map in the security control room.

 

xxii          The equipment in each zone shall be tampered-free.

 

xxiii         Indicators: Audio and visual indications shall be provided on PC console as follows:

 

                Alarm for each zone (Vibration Detection System)

                Alarm at each Zone (Microwave Detection System)

                Full Alarm Condition

                Sensor cable fault

 

xxiv         Perimeter

                Pre alarm

                Full Alarm (when both detection system coincide)

                Zone failure

                UPS failure

 

                Access System:                Equipment failure

                Duress Alarm

                Reject entry

 

               

xxv          All gates installed on perimeter fence shall be possible to open and respective zone protection shall be isolated or blocked whenever required by the console operator.

 

xxvi         Operating Temperature     :           The System shall operate correctly in ambient temperatures as detailed in this document.

 

xxvii        Humidity                                :           The system shall operate correctly in relative humidity levels as detailed in this documents.

 

                6.02.2         Microwave Detectors

 

                    The microwave intrusion system shall be installed as an independent fence protection system based on Digital Technology and fuzzy logic. However, the output from fence intruder (vibration detection - section 6.02.1), and microwave detection system shall be combined in the central processor and full alarms rose only for coincident events registered by both systems    Microwave detection system shall meet or exceed the following specification:

 

i.                     The system shall utilize an effective antenna patterns to achieve an optimum detection. This antenna range shall cover a zone length of max. 200 meters with height coverage of 6 meter from ground level.

                                                                    The system should be able to detect belly crawl.

 

ii.             Microwave transmitters and receivers shall be designed and installed such that those will not cause any interference to surroundings or being interfered by others sources of same kind and shall be environmentally safe.

 

iii.            Zone overlapping shall be considered for optimum coverage of the perimeter areas.

 

iv.            Transmitters and receivers shall be installed on properly designed 4” pole mountings with concrete foundation meeting COMPANY’S standards.

 

v.             Microwave antennas and other equipment shall have an anticipated life span of not less than fifteen (15) years.

 

vi.                  All cabling to and from the transmitter and receivers shall be from the bottom side.

Vii               Technical Data Required:

 

Frequency           X  – Band Certified

 

Target Speed       From 0cm / sec to 15 m/sec.

 

Probability of detection:    0.99 minimum based on S/N Ratio.

               

MODULATION CHANNELS:      16 CRYSTAL CONTROLLED.

 

TEMPERATURE:        -5°C / + 65°C

 

                ALARM OUTPUTS:   ALARM, FAULT, TAMPER

 

6.03        Digital Circuit Television Monitoring System (DCCTV)

 

                6.03.1         The DCCTV system shall conform to all clauses of HCIS standard section 5.0 pertaining to DCCTV system. The DCCTV system in general shall serve the following functions:

 

·         Shall be capable of monitoring the overall view of the entire plant area  

 

·         Shall be capable of monitoring the entire perimeter fenced area (through the camera installed on camera poles near the fence).

 

·         Shall provide accurate view of the alarmed area.

 

·         Shall be capable to have a continuous monitoring of the affected areas.

 

·         Shall provide high reliable  Video Motion Detection  System.

 

·         Shall be capable of archiving and playback video events and images (through DVR).

 

·         Shall be a Central Video  Management System for security surveillance and video control  – both analogue and digital networks 

The control software component  shall base on a client / server software         architecture using TCP / IP addressing. Which makes it suitable for use    on distributed hardware interconnected via standard LAN/WAN systems.

-       The set – up client software is used to define all user specific functions either locally or remotely:

                                                                                               

 

§  Matrix hardware control

§  Outdoor video motion

§  Alarm signal processing.

§  Display and recording of  video alarm events.

 

 

 

 

Note:       All other installation materials, suitable camera lenses for cameras, video controllers etc., shall be proposed by the CONTRACTOR for an approval by COMPANY.

 

 

                6.03.2         DCCTV Day/Night Color Cameras:

                                    The below listed specification are the general guidelines for designing and selection of Day/Night type color cameras as being referenced under scope of work, scope of supply and design details elsewhere in this document.

 

 

·         Cameras shall be of a suitable image format that will satisfy the requirements, high-resolution Day/Night type color video cameras for use in environmental enclosures, pan/tilt/zoom (mobile/dynamic), and static (fixed) mounts.

 

·         Camera shall feature enhanced sensitivity, low power consumption, wide environmental operating range, making this camera suitable for a wide variety of surveillance applications.

 

·         The Camera must perform well under range of lighting conditions. To enhance sensitivity when night falls, the Day/Night camera shall be able to automatically or manually (i.e. depends on configuration) switch from color to monochrome (B/W) and adjust its shutter to a lower speed to increase its sensitivity.

 

·         The minimum sensitivity of the day/night camera to create usable video shall be as follows:

 

                Day Mode (Color)                                                            : .5 lux

                Night Mode (Monochrome/Black & White)                 : 0.002 lux  

 

·         The camera feature shall include “image stabilization” which filters out vibrations to compensate for camera movements caused by environmental conditions such as wind, ensuring a steady picture, especially when camera is zoomed to its maximum range.

 

·         Primary features shall include intelligent backlight compensation, automatic shutter, selectable electronic shutter, and automatic with manual override focus and iris control.

 

·         Camera design shall incorporate digital adjustment control in place of conventional color setup potentiometers and most other potentiometers. Alignment parameters shall be permanently stored in non-volatile memory for increased stability and consistency.

 

·         Camera shall incorporate an interline transfer CCD suitable image format imager with 752 horizontal and 582 vertical active picture elements. Horizontal resolution shall be 540color ,600monochrome lines  or better.

 

·         Design shall include a built-in ground insulation transformer, which shall inhibit ground fault conditions.

 

·         Power shall be supplied to the camera by means of screw terminals located on the camera back panel in a weatherproof junction box.

 

·         Design shall feature an all-metal housing.

 

·         All controls shall be located on the side of the camera and shall be concealed by a cover. Control and their function shall include:

 

                White balance                          :       Fixed or Auto

                Phase Adjust                            :       0-360

                Auto shutter control                 :       Level and ALC

                Back light compensation        :       On/Off

                Synchronization Mode           :       Internal crystal reference or line-lock

                AGC                                           :       On/Off

                Focus Control                          :       Auto Focus with Manual Override

                Iris Control                                :       Auto Focus with Manual Override

               

·         Shutter speed operation shall reduce camera light sensitivity by one (1) fc -stop for each additional shutter speed.

 

·         If required, cameras shall be fitted with lights, which shall give white illumination to assist in night surveillance.

 

·         The Camera and its enclosure shall be designed to handle the site environmental conditions as detailed on Section 3.0 of this document as well as the actual plant area classification.

 

·         ALL CAMERAS SHALL BE DIGITAL PROCESSOR.

·         ALL CAMERAS SHALL BE BUILD IN FIBER OPTIC.

·         Operation temperature  (  60oC).

 

6.03.3         PTZ Units:

 

·         Pan travel shall be 0-360 continuous and tilt shall be ± 90o for cylindrical or rectangular tube mounting type.

 

·         Pan travel shall be 360o continuous and tilt shall be –5o ± 90o from horizontal plane for dome type camera mounting.

 

·         Pan tilt speed shall be 60o/sec minimum.

 

·         PTZ units shall be industrial type, heavy duty for outdoor use and shall meet the area classification requirements.

 

·         Optical and digital zoom range of the cameras shall be designed and selected to successfully meet the monitoring requirement of each camera per assigned area and to provide accurate and clear video events and images of the area it covers.

 

·         PTZ units shall be capable of having a minimum of 16- configurable preset positions and respond to control commands from a matrix system, and can be set automatically, including the dwell time duration per position to simulate guard tours activity.

 

·         Pan/tilt shall have a feed through style wiring harness providing for pan/tilt and lens control, camera power enclosure power and video design of harness shall allow for all connection to be made at a single input connector.

 

·         Pan and tilt movement shall be driven by worm gears to minimize backlash and prevent wind drift. Worm gear assembly shall allow for wear adjustment.

 

·         All PTZ units shall be equipped with duty continuous scanning operation controllable by the operator in security control room.

 

·         Grease nipple shall be provided wherever necessary.

 

·         When the operator stops manual control of the camera, the “inactivity” option determines what the camera should do next, (as configured). The options are:

 

·         128 PRE- SET

 

 

 

6.03.4         TFT - LCD Video Monitors:

 

                Video monitors which shall be installed in control console in security control room, gatehouses, plant control buildings, and SEC-WRB Hqs. shall meet or exceed the following specification:

 

·         LCD Panel shall be 21” (diagonal) SXGA TFT LCD

 

·         16.7 Million Color Display

 

·         Television standard shall be EIA 525 lines, 4:3 aspect ratio.

 

·         376.32 mm x 301.056 mm display area.

 

·         Resolution of 1280 x 1024  .

               

·         Linearity shall be less than 2% of raster height.

 

·         The monitor shall be flicker and static free.

 

·         Video input shall be 1.0 V, pp / 75 ohms unbalanced.

 

·         Video Interface shall be compatible with the video matrix, workstations, and servers. The CONTRACTOR shall provide any video interface converter/adapter as necessary.

 

·         All panel controls shall be located in the front.

 

·         Monitor shall operate on a 127/220 VAC, 60 Hz power supply.

 

·         Monitor shall be capable of desktop or rack mounting installation.

·         SHALL DISPLAY UP TO 64 CAMERAS ON ONE Monitor

 

 

6.03,5         Outdoor Camera Enclosures:

 

·         Design of this enclosure shall allow easy and convenient access to camera for installation or maintenance.

 

·         The Lid design shall be such that it extends over the front of the enclosure to obstruct direct exposure to sunlight.

 

·         Cable/wiring shall enter the enclosure through appropriate cable gland as per the area classification requirements located on the bottom of the enclosure.

 

·         Enclosure shall be designed according to area classification requirement as mentioned in this document and shall be sealed and pressurized, and capable of withstanding the site ambient temperatures.

 

·         Sunshields shall be provided for all outdoor enclosure.

 

·         The metallic materials of the enclosure shall comply with the site conditions as mentioned in this document.

 

·         The mounting pole for the camera should be securely fixed so that excessive movement of the camera by wind or general climatic condition is prevented. The camera in the perimeter fence should be installed at a height of approximately 4.5 to 5.0 meters above ground level.

 

·         The camera shall possess an automatic cleaning mechanism for the glass-shield such as wiper and washer that is controllable from the security control center.

 

·         The camera should be installed at a height of approximately:

               

                4.5 to 5.0 meters above ground level - For perimeter fenced camera.

 

    The  PTZ cameras housing shall be nitrogen pressurized.

The  outdoor Fixed camera housing with bracket  should be IP 67   stainless steel 316  suitable for marine time  type and industrial application with heater.

 

 6.03.6                    Digital Video Recorder (DVR)

           The below listed specification are the general  guidelines for designing and selection of DVR system for the DCCTV system as being referenced under scope of work, scope of supply and design details elsewhere in this document.

 

 

·          The Digital Video Recorder/Software (DVR)

·          designed as a single system   

 

·         Monitor shall automatically display camera ID, time and date information, as well as 56 programmable alphanumeric characters, and system generated status prompts.

 

·         System shall be controllable with up to … independent keyboard controllers and/or through GUI intuitive software and using mouse.

 

·         Programming capabilities shall allow for assignment of any or all camera inputs to any or all monitor outputs based on individual user(s) and keyboard-to monitor lockout software programs.

 

·         The system shall allow user to view live and recorded video from multiple camera utilizing easy to use GUI software. User can choose from single, 2x2, 3x3, 4x4,4X8, 4X16 display modes.

 

·         The GUI software can be displayed on Two computer monitors, one dedicated for multiple camera views and one for the Camera layout maps.

            Map allows the user to click on camera, monitor or other security system icons on a screen, causing the relevant reactions on any subsystems. Vice versa, any alarm event can cause Multi-Map to pop up a certain map.

·         Programming shall be done from any system keyboard utilizing any system monitor without the need for any external PC. Programming shall be menu-driven. Pull-down menus shall be displayed on any system monitor and through the aid of intuitive GUI software/map. Cursor movement, menu selection, and data input shall be made directly from any system keyboard.

 

·         Programming capability as well as any keyboard operations shall be restricted to specific user(s) based on user password. (4-Digit user number plus 5-digit ID code)..

 

·          Keyboard to monitor lockout shall be programmable by authorized  user(s).

  ·         Time and data information shall be programmable by authorized user(s)

 

·         Sequences, tours, alarm definitions, and events shall be programmable by authorized user(s).:

 

                Manual and internally interlock latch type buttons for 16 preset PTZ positions shall be provided in the security control room keyboard for call-up of any camera to any monitor. 

 

                “Next camera” and “Previous cameras” ”  and by number  selection  .

 

                Control function shall include pan/tilt, motorized zoom lens, cameras power, preset position call-up, and auxiliary functions.

 

                  control the PTZ Day/Night cameras and correlated through intuitive GUI software.

 ·          Design/Configuration

                 Modular build-up design shall be utilized to accommodate system expansion.

                 Card cage shall contain CPU and power supply and support all video input, video output, alarm input and relay output cards.

                 CPU card shall contain as a minimum of eight (8) keyboard ports (expandable to 16 keyboard ports), one (1) parallel printer port, and two (2) serial ports.

                 Keyboard controllers shall be available in both desktop and rack mount versions.

 ·          Electrical Specifications:

                 Electrical input power shall be 127/220 VAC, 60 Hz from UPS Panel mentioned in this document.

                 Input power cord to CPU/card shall be detachable.

                 Video connections for all video inputs and outputs shall be standard BNC type connectors.

                Video input level: 1V p-p nominal

                  ·         The Digital Video Recorder (DVR) )  WILL be designed AS     independent systems. 

 ·          Design shall be state-of-the-art, powerful, reliable, and intelligent Digital Video Recorder (DVR)   system   and access control systems to complete the new integrated security system 

 ·           Video Motion Detection Software suite

 ·         Camera Mapping.

 ·          FULL VEW OF THE SITE SHOWING   INTRUTION DETECATION SYSTEM AND SHOWING THE INTRUTION LOCATION.

 ·         View live and recorded video from any camera on the network

 ·         The new Digital Video Recorder (DVR)   system is a combination of powerful and high reliability computer/processor with enough hard disk storage capacity   and an intuitive user friendly GUI based video recorder management software, running on either Windows 2000 or Windows XP platform, and shall be designed to support and manage video events and image files of the DCCTV system …. Plant integrated security system.

 ·         The system operates as a virtual matrix proving camera switching and selection and shall support simultaneous records, display live video, plays back recorded video, and   archiving, and control

 ·         DVR   system features shall include but not limited to the following:

                 Processor, hardware, and peripherals shall be the latest available in the market. The COMPANY shall approve specification during the base design stage.

                 Shall have hard disk storage capacity of not less than 3TB to be used for saving video events, where it is available for immediate playback and/or can be archived/saved  .

                 Running on either Windows 2000, or Windows XP platform. These OS shall be preloaded on the DVR computer. The CONTRACTOR may propose newer Windows OS platform such as Windows XP if supported by the proposed DVR software and hardware.

 

                Shall be equipped and preloaded with the advanced, intuitive, user-friendly GUI based video recorder management software for controlling and programming.

                                Shall support multi-camera view. The operator can choose from single, 2x2, 3x3, and 4x4 4X8,4X16 display modes.

                 Shall support multiple recording operations and features  .

                               SHALL playback features shall include normal motion, slow motion, freeze frame, forward and reverse frame and intelligent alarm/event or file searches or retrieval.

              DVR system shall be capable of assigning or tagging an organized and easy to identify filenames for all recorded video events and images.       :

 

                Scheduled Recording:

                DVR can be configured to record only during specific hours of the day and days of the week.

 

                On-demand Recording:

                DVR can be configured to record at the request or activation of the operator.

               

                Alarm-triggered Recording:

                Recorders can be configured to record only when an alarm condition occurs (e.g. from motion detection  , access control system, fire alarm system, etc.), providing pre, and post event recording.

 

                As a minimum:

                Pre-alarm video events may be set to 0 – 2 minutes.

                Post-alarm video events may be set to 0 – up to end of alarm (i.e. until the acknowledgement/clearing of alarm).

               

                Continuous Recording:

                DVR can be configured to record 24 hours, 7 days a week.

               

                Activity or Motion Detection Recording:

                DVR can be configured to record video events (both pre-alarm and post-alarm)  ) as a component of the DCCTV system. 

    

·         The  system shall provide high performance and reliable detection of intruders under a wide range of changing environmental conditions.

 

·         The system shall minimize the occurrences of false and nuisance alarms caused by small animals, blown debris/papers, birds, clouds, sand storms, rain, moving trees, and wind induced camera movements.

·         Intruder alarms shall be displayed on consoles in main control room and recorded in the system event logger.

   

·         DVR recorder/player shall be able to support standard PAL frame rates (100 fps) for both MPEG-1/VCD   and MPEG-2/DVD quality (720 x 576) resolutions

 

·           Cd/rw, dvd,+r/-r , dvd/rw              

 

6.04        Access Control System

 

                The function of the access control system is to monitor and record personnel entry to and exits from the site, and to restrict staff entry in areas of high security.

 

The Access Control system should support Alarm color graphics maps, video badging, and basic time and attendance  provides support for up to 1000 readers (various reader technologies), 255 access levels, 128 time zones per controller with 6 intervals per time zone as standard.

 

  • Multi – user operating environment.
  • TCP/IP protocol / Network support.
  • Time activated reader modes.
  • 2 Card control /2 man control.
  • Integrated graphic map display included.
  • Integrated badging included
  • Basic time and attendance included.
  • Alarm zone grouping / group arming / disarming.
  • Inputs to Outputs Linkages.
  • Database segmentation.
  • On Screen reader control in alarm mode.

 

 

6.04.1                     Turnstile

                    Turnstiles shall be supplied at main gate   of the plant entrance used by personnel who are largely on foot.

 

                    Turnstiles shall be fitted with card readers. The turnstiles and readers shall have the following minimum requirements.

 

·         The turnstiles installed shall conform to SSD-16-23-24.

 

·         Turnstiles shall have a proximity card reader on both sides. The card reader shall be fitted with a keypad for entering personal identification number (PIN). It should be bi-directional movement and shall be automatically and manually selected from the central processing unit.

 

·         Entry to (and exit from) the site shall be gained by verification of the card through the reader and entering a PIN in the keypad.

 

                                During rush hours PIN number punching may be suppressed/disabled, i.e. card verification shall be means of entry/exit in order to avoid long queues at the turnstiles.

 

·         Turnstiles shall be heavy-duty, and made of stainless steel, and of full height not less than two (2) meters and be installed side by side to minimize the required space.

 

·         Cable entry point shall be at the bottom side from the underground.

 

                                                Construction:    Portal frame: steel construction, Anti Tamper upper housing locked              

                                 with cylinders

 

Surface:               Steel parts: hot-galvanised (portal frame, entry/exit enclosure, barrier element)

                                Column: stainless steel glossy (AISI 304) (electro-polished)

Function:            Servo-positioning (motor) drive in 1 or 2 directions electrical controlled.

Operation:          After a release pulse for entry or exit direction, passage is given

                                free to the chosen direction. After a slight hand push, the servo

                                positioning drive moves the turnstile column gently into the next rest position.

                                If there is no passage through within an adjustable time, the release is cancelled

                                automatically. (TIME OUT).

 

Electrical Equipment:            Control unit integrated in the upper portal housing

                                                      Power supply: 115V to 230V AC / 60 Hz / 95VA

                                                      Control voltage: 24 Volt DC

Installation:         Floor fixing on finish floor.  .

 

Power failure:    In the event of power failure entry or exit directions are free or locked or combination

Remote control panel for the turnstile with the following functions  shall be  provided :

·         Single release entry

·         Single release exit

·         Permanent release entry

·         Permanent release exit

·         Blocking

 

6.04,1                     Card Readers

 

·         Re-entry to the site shall be gained only after first leaving the site having used the card reader.

 

·         Card readers shall raise an alarm if attempt are made to use a damaged card or a card that has been tampered with or a card that has been blocked.

 

·         An alarm shall also be raised if card pass-back is attempted or more than one person uses the same card. In these circumstances the turnstiles shall deny access to the site.

 

·         An alarm shall be raised in case of entry attempted by force (Duress Alarm). The system must also be able to initiate other responses that have been setup for the Duress Alarm State.  

 

·         Alarms raised and events logged by the card readers shall be displayed and printed at the workstations and printer in the Security Control Room.

 

 

·         Security personnel shall be able to generate (i.e. ID Badging facilities) and program the card an access privileges for varying levels of security on site. Security shall also be able to program cards for predetermined expiry dates and times, e.g. for visitors and temporary staff.

 

·         Three lights red, green and amber should be on the card readers and operate after verifying as follows:

 

                                Red                :       Reject Entry

                                Green            :       Accepted Entry (Normally No Indication)

                                Amber            :       Reader Fault Indication

 

·         The bottom bearing shall be dust and waterproof with thrust bearing.

 

·         System Unit:

 

                                The latest hardware speed and capacity available in the market at the time of equipment delivery.

 

                                19” diagonal LCD-TFT flat color monitor

 

                                PC-DOS and Window-NT or Windows 2000 software (supplied preloaded and original). The CONTRACTOR may propose newer Windows OS version, such as Windows XP, if supported by the proposed Access Control System.

 

                                Card access control software (including a flexible, customizable report generator).

 

                                Multiplexer card or similar adapter to control access card network.

 

                                Remote terminal support software and hardware.

 

                                Connection interface to DCCTV controller. (This could be RS-232, RS-485, ethernet, or as appropriate).

 

                                Connection interface to fence protection system. (This could be RS-232, RS-485, ethernet, or as appropriate).

 

                                The two (2) processor must be linked and under software control to operate as a main and “hot standby” with full disk mirroring to ensure continuous operation of the security system.

 

                                Continuous feed, heavy-duty matrix printer, shared by main and backup (1 pc).

 

                                The system will draw electrical power from the security system UPS (1 set).

 

                                Display panel located in the security control room (1 pc).

 

                                Loop controllers or wiring connectors (4 pcs).

 

6.04.2         System Software Capacity (Minimum)

 

                  Simultaneous users                   10

                    Card Readers                              1000   

                    Card in Database                        10,000

                     

6.04.3         Card Issuing (ID Badging) Facility

 

                    PC based image system and ID card printer (4 complete sets)

                   

                    PC Windows 2000 or Windows XP Software. The CONTRACTOR may propose newer Windows OS version, such as Windows XP, if supported by the proposed Access Control System.

 

                    High quality Color Digital Video Camera.

 

                    Professional quality camera tripod.

 

                    Video interface card

 

                    High quality ID card printer (color) Dual side English/ Arabic

 

                    Image management software

 

                    Laser Color printer for reports.

 

                    19” diagonal LCD-TFT flat color monitor

 

                    Cabling and connectors (as required).

 

                    Card encoding facility

 

6.04.4         ID Cards:

 

                    Access card (Smart type)

 

                    Smart Card reader with keypad

 

                    An internal power supply of 127/220 VAC at 60 Hz should be fed to provide the system from the UPS panel.

 

 

6.05        Door Monitoring System  

 

6.05.1         Sensing Units:

 

                    All doors are to be provided with a tamperproof magnetic door contract switch assembly, which shall give a contact change over in case of OPEN door.

 

                    CONTRACTOR shall check the construction of existing doors and provide the necessary hardware suitable to the existing doors. Any modification of existing doors required to install door-monitoring components shall be in the scope of the CONTRACTOR.

 

                    Suitable door monitor strikes are to be provided for remote door monitoring through the use of a signal switch 9 (DPDT) mounted in the strike to monitor the latch - bolt. Monitor strike shall be of stainless steel construction.

 

                    Signal switch shall be magnetic type, hermetically sealed dry contact switch Material of casing shall be aluminum.

 

                    Local LED indication at sensor is to be provided to display the status of the door.

 

                    Green                :               Door Closed

                    Red    :               Door Open

 

6 .5.2          Control Units:

 

                    All door monitoring sensor contacts shall be connected to the control unit located at security control room.

 

                    It is preferred to install control unit at security control room. All door status contacts are to be hardwired to individually to the weatherproof junction box to be installed close to the area of monitoring.

 

                    A multi-core shall be laid from this junction box to control unit to be installed in security control room.

 

                    Monitoring and control unit shall have provision to configure the unit or by downloading the configuration database from the central access control system terminal.

 

                    Control Unit shall have LED displays for the status of each door and also diagnostics LED’s for easy troubleshooting.

 

                    Control unit hardware shall be of modular design for easy and quick maintenance.

 

                    System shall be freely expandable.

 

                    In case of failure of control unit, control unit shall generate a “fault” status alarm, which shall be displayed on the main system terminal.

 

                    Control unit shall be housed in a weatherproof enclosure (minimum class IP 1) suitable for indoor installation.

 

                    Additional buzzer/hooter is to be connected to the system and is to be installed locally near the area to be monitored.

 

6.05.3         Alarm and Display Function:

 

                    Control unit shall be connected to the central access control system and all the doors status information shall be communicated to the main system.

 

                    A dedicated alarm panel is to be provided at security control center to display audio-visual alarm of individual door. Each door is to be identified by a door number and a location on to this panel.

 

                    Audio alarm shall have acknowledged push button to mute the buzzer.

 

                    A reset push button is to be provided to reset the alarm indication lamp once alarm condition has become normal.

 

                    A dynamic graphic display shall be provided on access control system terminal to display status of all doors being monitored.

 

                    Alarm information such as location, door no., date, and time of alarm, etc. Shall be automatically logged on to the system terminal and a printer.

 

                    Minimum 10,000 alarm messages shall be stored in the hard disk of the system terminal as historical data for minimum three months with a provision to retrieve the same as and when required.

 

                    In case of failure of control unit or main system hardware, all status indications on alarm panel and on monitor should flicker with an audio signal.

 

                    “Test” push button shall be provided to test the indication lamps of this panel.

 

                    Additional buzzer/hooter is to be connected to the system and is to be installed locally near the area to be monitored.

 

6.05.4         Power Supply

 

                    Power supply for door monitoring system is to be provided from the UPS, which shall be supplied by the vendor for the entire system power requirement.

 

6.05.5         Cables

 

                    All required cables from individual door sensor to the control unit and from control unit to central system should be in the scope of CONTRACTOR.

 

6.06        Road Arm Barriers:  

 

6.06 .1        General

 

                    i.          CONTRACTOR shall INSTALL Rising Arm Road Barrier  integration to the new Access Control System and compliance issues to HCIS standards. 

 

                    ii.         The CONTRACTOR shall install a vehicle access reader and proximity card reader (for driver/passenger) at:

                               

                            Plant Main Arm Barrier Gate (entry/exit)

 

           iii.        Road barriers shall be painted with reflectorize black and yellow line colors that comply with the security sign international standard.

 

iv.        All road barriers drivers shall be mounted with the manually operated device.

 

v.         A safety loop shall be installed to all road barriers. This is to ensure that safety of the vehicle/personnel passing on any of the barriers.

 

vi.        The control system shall be connected to the UPS system.

 

vii.       The barrier shall have logic module, which is compatible with the card readers, radio control, vehicle loop detectors, key switch, automatic identification system and etc.

 

viii.      The control station include opening and closing push button; opening indicating lamp Red color; closing indication lamp Green color; trouble indication lamp Amber color. This control station shall be installed at the location specified in this document.

 

ix.                  Power supply voltage shall be based on load demand and in accordance with the COMPANY standard and preferences.

 

Construction:    Housing of aluminium with reserved space for extra equipment

                                   Lockable opening for maintenance and removable hood.

        Boom: reinforced Aluminum  with below edge rubber protection.

Surface:                  Stove enamel finish.

 

 Function:              Electro mechanical drive 115V. Drive with end position damping of the

                                   barrier boom by means of sinusoidal movement.

 

In case of accident/use of force: boom holder disengages from the main shaft.

 

Power failure:     Barrier can be lifted by hand after manual unlocking behind the lockable maintenance panel.

 Manual  operation:

A  Toggle switch for opening and closing the barrier shall be provided

 

 

                          6.07       Security Control Room Requirements

 

6.07.1         Power Supply

 

                    Power supply for door monitoring system is to be provided from the UPS, which shall be supplied by the vendor for the entire system power requirement.

 

6.07.2         Cables

 

                    All required cables from individual door sensor to the control unit and from control unit to central system should be in the scope of CONTRACTOR.

 

 

                6.07.3         Layout

 

·         Layout of SCR shall be designed and engineered by the CONTRACTOR.

 

·         It should be possible to operate/control all the systems by a single operator while sitting in front of the system.

                

              6.07.4           Work Station Console:

 

·         This shall accommodate hardware for the following systems:

 

            DCCTV monitoring

 

            Digital Video Recorder (DVR). 

 

            Main computer

 

            printers

 

            Access control and door monitoring system

           PLASMA /LCD

·         Main computer shall be 3.5 GHz Pentium 4 pro, 1025mb of ram , 80gb of hard drive space , 52xcd-rom drive + r/w , tcp/ip rs 232 ,rs484 ,graphic 1280x1024 svga, digital lcd 19 in 

 

·         Printer shall be color LaserJet ,22ppm , paper input capacity 850 sheets

 

·         Keyboards are to be installed at convenient orientation and height for easy use by an operator.

 

·         Electronics is to be housed below the console desk and installation shall be engineered such that it is not tampered by the movement of operator. If it cannot be accommodated under the desk, electronics has to be housed in a separate cabinet.

 

·         All video monitors shall be arranged and oriented such that operator can easily watch any of the monitors from his sitting position.

 

·         The tops of various components in a row shall be aligned to give a neat appearance to the finished console.

 

·         All wiring/power supply sockets/cables are to be laid and dressed such that they are properly secured and create no personal hazard of electrical shock etc. to the operator.

 

·         All cables/wiring should be concealed in IMC conduits of suitable size.

 

·         Console shall have modular design to create the exact console to meet the present requirement and for easy expansion in future. The manufacturer of the console shall be Evans Console/Panel Systems or approved equivalent.

 

·         Console shall be ergonomically designed.

 

·         Color of the console shall be decided later.

 

·         Interior cooling, heat dissipation or air purging requirements shall be checked taking into considerations the prevailing conditions and the density of components to be installed.

 

·         Installation arrangement of various components shall be such that it is easy to remove/replace any component/unit.

 

·         Console shall no have any left-out gaps, holes etc. All unused holes, etc., shall be sealed properly to make it dust/waterproof.

 

·         Console shall have spare space/cutout to add one more size monitor in future. Such cutout is to be properly covered with surface to surface matched for elegant look.

 

·         Engraved identification tag numbers and description shall be provided for each component just below the component.

 

·         INTEGRATE ALL THE SYSTEMS.

 

                6.07.5         LCD/Plasma Display

 

                A new state-of-the-art 50” (diagonal size),LCD Color Plasma display unit shall be provided to present a simplified site layout diagram of the area indicating various zones and alarms as well as to view video events of the DCCTV system as desired by the operator and can display all the cameras on one time.

               

The LCD/plasma display unit shall have the following specification as a minimum:

 

                Resolution: 1,048,320 pixel (1365 x 768 dots)

Colors: 16.77 Million colors minimum

Coating: Anti-Reflection Coating

Contrast: 3000:1

Power Supply: 127/220 VAC, 60Hz.

SHALL DISPLY ALL THE CAMERA IN SAME TIME.

SHALL DISPLY ALL THE FENCE DETECTION SYSTEM.

 

6.07.6         Adequate required high quality furniture/console desk (EVANS Console or approved equal) shall be provided to install access control system terminal, printer, DCCTV system terminal printer. Arrangement for these hardware maybe an extension of console or stand-alone separate furniture.

 

6.07.7         The CONTRACTOR shall also provide six (6) Heavy-duty ergonomic chairs (steel case or approved equal) for operator.

 

6.07.8         Any other furniture/panel required to install in the system hardware shall be the scope of the CONTRACTOR. :           Indoor in air-conditioned room

 

 6.08       Fire Alarm System

 

The existing fire alarm system of   Plant shall be integrated/interfaced to the new Security System.

 

CONTRACTOR shall check the construction and configuration of existing Fire Alarm System for compatibility issues in integration to the new Security System and compliance issues to HCIS standards. Any modification, additions, and/or changes of existing Fire Alarm System required to successfully install Access monitoring and control components shall be in the scope of the CONTRACTOR.

 

The Main Fire Alarm Panel located at Fire Station Building shall be interfaced with the new Security System.

 

All interface cables, hardware, software, controllers and accessories shall be provided by the CONTRACTOR under this PROJECT.

 

 

6.09        Crash-Rated Main Plant Linear Sliding Steel Gate

 

        The below listed specification are the general guidelines for designing and selection of Crash-Rated Linear Sliding Steel Gate and its associated components, which to be installed at   Power Plant Main Gate as being referenced under scope of work.

 

                6.09.1         General Specification

 

·         The Gate shall be an above grade assembly consisting of a heavy steel structure capable of being opened and closed in a linear sliding motion. When in the closed position it shall present a formidable obstacle to approaching vehicles. Upon impact, forces shall be first absorbed by the steel structure of the Gate assembly and then transmitted to the end support buttresses and their foundations.

 

·         The design of the Gate system shall have been confirmed by the detailed examination of the structure with a finite structural analysis computer program. A print out of the analysis defining the applied loads at all connections and reaction points, and the induced stresses and moments at each node and element shall be available with the system.

 

·         The lower portion of the Gate shall constitute a composite structure composed of steel structural members. The superstructure of the Gate shall provide a solid framework to which bars, panels and grills.

 

·         The ground track shall be suitable for guiding a V- groove type Gate support wheel. Sufficient track shall be provided to allow full run back of the Gate leaf while in the fully open position. The track base shall be flush with grade.

 

·         The Gate will be supported in the fully closed and open positions by an end support buttress system. These supports will include all necessary guide wheels for the smooth operation of the Gate. The end support buttresses shall absorb the forces received from the Gate leaf during a vehicle collision and transmit them to their foundations.

 

·         The Gate and end support buttresses of the system shall be mechanically and chemically cleaned and painted per SEC-ERB painting standard 78-SMSS-13.

 

·         The gate shall provide excellent security and positive control of normal traffic in both directions by providing insurmountable obstacle to vehicles within the weight and velocity characteristics as defined below (Note: Test Certifications shall be submitted to the Company for review):

 

a. The gate shall be fully operational after successfully stopping vehicle(s) in the priority direction, with weight and speed of:

 

                            66.7 kN at 113 kph. (15,000 lbs at 70 mph)

                            88.9 kN at 100 kph. (20,000 lbs at 60 mph)

 

b. The gate shall be capable of stopping and destroying (immobilize) vehicle(s) with weight and speed of:

 

                            58.7 kN at 137 kph. (13,200 lbs at 85 mph)

                            88.9 kN at 113 kph. (20,000 lbs at 70 mph)

 

o   The gate and its auxiliary components shall be designed to work with various environmental conditions as specified in Section 3.02 of this document.

 

·         The gate system and subsystems shall have a neat and workmanlike appearance.

 

·         The Gate System, (i.e. power, control, drive unit, accessories) for entry and exit bounds shall be independent with each other.

 

·         Installation of the entire gate system shall be in accordance with the Manufacturer’s standard instructions and procedure. The installer must possess a valid installer certification from the Manufacturer.  

 

 

                6.09.2         Drive System Unit

 

·         The Gate shall be positioned and locked in place by hydraulic motor. The drive system shall be designed and constructed in a manner to insure long, trouble free operation and be capable of operating under extreme environmental conditions. Normal servicing and repair work shall be possible with readily available tools and components.

 

·         The power source for the electric motor and control circuits of the Gate system shall come from the new UPS system installed at ISD building for Security System under this PROJECT. Operating voltage shall be 127 VAC, 60 Hz.

 

·         The Drive System Unit shall control the position of the moving Gate by means of heavy-duty sensors. These sensors will interface with the system logic and control circuits and will be sealed from environmental impurities/contaminants.

 

·         In the event of power-off condition, the Drive System Unit can be disengaged from the gate. The gate shall be capable of being pushed open or closed without damage to the drive components.

 

                 6.09.3         Speed of Operation

 

i.          Sliding Gate operating speed (opening and closing) shall be as per 600 mm/second .

 

ii.         The Gate system shall be provided with Emergency Override Close (EOC) System. The emergency override close system shall provide a separate oversize control button on the remote control panel, which when pressed will signal the control and logic circuit to close the gate and ignore any intervening signals from safety detectors or sensors . 

 

                6.09.4         Control and Logic Circuits

 

·         Control circuits and control panels shall be provided to interface between all gate control stations and the drive system unit (operator unit). The control circuits shall contain all relays, timers, and other devices necessary for the Gate operation. Independent Control system shall be installed for the entry and exit gate.

 

·         Two remote control panels (master and slave) to control the Gate operation (separate for entry and exit) shall be supplied and installed at:

           

            Master Control Panel: Security Control Room.

           

            Slave Control Panel: Guard House of Plant Main Gate.

 

·         As a minimum, the control panel shall have the following:

 

a. Key lockable main switch.

 

b. “Main power on” and “panel on” lights.

 

c. Buttons to open, close, and stop the gate.

 

d. Gate “open”, “fully closed”, and “cycling” indicator lights.

 

e. Emergency Override Close (EOC) button, which is larger than the normal control.

f. The EOC shall be furnished with EOC active light and reset button.

 

g. For Master Control Panel Only: Key lockable switch to arm and disarm the slave control panel.  

 

·         The crash-rated linear sliding steel gate shall be integrated to the access control system, in such away that the operational status/condition (i.e. open, close, EOC) of the gate shall be automatically logged on the access control system. EOC status of the crash-rated linear sliding steel gate shall also alert the operator in Security Control Center through the access control system by visual and audible alarms.

 

609.5      Safety Detectors and Accessories

 

·         Flashing Warning Light and Traffic Light shall be installed.

 

·         A vehicle safety loop detector shall be supplied to prevent the gate from being accidentally closed while a vehicle is in the Gate’s path. The detector shall utilize digital logic and have fully automatic tuning for accurate long-term reliability. The output of the detector shall negate the Gate close signal.

 

·         A safety edge sensor system shall be furnished on the leading edge of the gate. Any pressure applied to the Safety Edge should cause the Gate to stop instantly.

 

·         The Emergency Override Close (EOC) feature shall be integrated/associated with an audible alarm system to emphasize that the operation is under emergency condition.

 

·         During power supply interruption, the gate shall be capable of being pushed manually (opening or closing) without damage to the drive components.

 

6.10        Crash-Rated Rising Road Steel Barricade at Plant’s Inner Gate

 

        The below listed specification are the general guidelines for designing and selection of Crash-Rated Rising Road Steel Barricade and its associated components, which to be installed at   Power Plant Inner Gate as being referenced under scope of work, scope of supply and design details elsewhere in this document.

 

                6.10.1         General Specification

 

·         The barricade construction shall be a flush-mount assembly consisting of a heavy steel (made of hot-dip galvanized steel) barricade capable of being raised from the free-pass position to its guard position by means of hydraulic actuators. The guard position shall present a formidable obstacle to approaching vehicles. Upon Impact, forces shall be first absorbed by the barricade assembly and then transmitted to the off-road buttress and foundation of the unit.

 

·         The height of the barricade during guard position state shall be 39-inches/1-meter as measured from the top of the foundation frame to the top of the barrier inclusive of the top road plate. The length of the barricade shall cover the entire passageway of the Plant’s Inner Gate.

 

·         The finish of the roadway plates shall have a non-skid surface. Barricade undersides and roadway plates shall be painted with yellow/black stripes. The buttress assemblies shall be painted yellow.

                                               

·         The barricade system shall use the state-of-the-art shallow foundation and aesthetic design without affecting/degrading its blocking capabilities.

 

·         The barricade shall have a performance evaluation as per U.S.-D.O.S. Specification SD-SDT-0201 of K12/L3.0.

 

·         The barricade shall provide excellent security and positive control of normal traffic in both directions by providing insurmountable obstacle to vehicles within the weight and velocity characteristics as defined below (Note: Test Certifications shall be submitted to the Company for review):

 

a. The barricade shall be fully operational after successfully stopping vehicle(s) in the priority direction, with weight and speed of:

 

                            66.7 kN at 113 kph. (15,000 lbs at 70 mph)

                            88.9 kN at 100 kph. (20,000 lbs at 60 mph)

 

b. The barricade shall be capable of stopping and destroying (immobilize) vehicle(s) with weight and speed of:

 

                            58.7 kN at 137 kph. (13,200 lbs at 85 mph)

                            88.9 kN at 113 kph. (20,000 lbs at 70 mph)

 

·         The barricade and its auxiliary components shall be designed to work with various environmental conditions as specified in Section 3.02 of this document.

 

·         The barricade system and subsystems shall have a neat and workmanlike appearance.

 

·         The barricade system, (i.e. power, control, hydraulic power unit, accessories) for entry and exit bounds shall be independent with each other.

 

·         The barricade system shall be strong enough to bear different types of loads (i.e. small vehicles - heavy trucks) crossing the flush-mounted barricade without affecting the efficiency of operation.

 

·                     Installation of the entire barricade system shall be in accordance with the Manufacturer’s standard instructions and procedure. The installer must possess a valid installer certification from the Manufacturer.

 

                6.10.2         Hydraulic Power Unit

 

i.          The hydraulic circuit unit shall consist of an electronically driven hydraulic pump, which shall pressurize a high-pressure manifold connected to a hydraulic accumulator. Electrically actuated valves shall be installed on the manifold to allow oil to be driven to the up and down side of a double acting hydraulic cylinder to raise and lower the barricade. The hydraulic circuit shall include all necessary control logic devices, interconnect lines and valve(s) for emergency fast operation of the barricade.

 

ii.         The power source for the electric motor and control circuits of the barricade shall come from the new UPS system installed at ISD building for Security System under this PROJECT. Operating voltage shall be 127 VAC, 60 Hz.

 

                610.3          Speed of Operation

 

i.          During Normal Operation, the Barricade shall be capable of being raised or lowered in 2 to 3 seconds (system configurable/programmable). Barricade direction shall be instantly reversible at any point in its cycle from the control stations/panel.

 

ii.         In emergency cases, the barricade system shall have an Emergency Fast Operation (EFO) feature that is capable of raising the barricade to fully guard position from fully down position in 1.5 seconds maximum. This function shall be engaged through an EFO push button at the control station/panel. Barricade shall remain in the up and locked position until the EFO condition is reset.

 

                6.10.4         Control and Logic Circuits

 

·         Control circuits and control panels shall be provided to interface between all barricade control stations and the power unit. The control circuits shall contain all relays, timers, and other devices necessary for the Barricade operation. Independent Control system shall be installed for the entry and exit barricades.

 

·         Three remote control panels (1-master and 2-slaves) to control the Barricade operation (separate for entry and exit) shall be supplied and installed at:

           

            Master Control Panel: Security Control Room.

           

            Slave Control Panel-1: Guard House of Plant Inner Gate.

           

            Slave Control Panel-2: Guard House of Plant Main Gate.

 

·         As a minimum, the control panel shall have the following:

 

a. Key lockable main switch.

 

b. “Main power on” and “panel on” lights.

 

c. Buttons to raise or lower each barricade.

 

d. Barricade “up” and “down” indicator lights.

 

e. Emergency Fast Operate (EFO) button, which is larger than the normal             control. (See Section 6.14.3.ii).

 

f. The EFO shall be furnished with EFO active light and reset button.

 

g. For Master Control Panel Only: Key lockable switch to arm and disarm the slave control panel.

 

·         In addition to control circuits/panels to operate the barricades stated above (6.14.4.ii and iii), the barricade shall also be integrated fully with the access control system. Granting of access (free-pass and guard positions of barricades) may be either automatically (i.e. through access control system) or manually (i.e. through switch buttons by the operator/guard), shall be integral to the system’s software and shall be system’s configurable.

 

·         As part of the integration of the barricade system to the access control system, the operational status/condition (i.e. free-pass, guard position, EFO) of the barricade system shall be automatically logged on the access control system. EFO status of the barricade system shall also alert the operator in Security Control Center through the access control system by visual and audible alarms.

 

6.10.5     Safety Detectors and Accessories

 

·         A vehicle interlock safety detector loop shall be supplied to prevent the Barricade from being accidentally raised under an authorized vehicle. The detector shall utilize digital logic, which has fully automatic tuning for stable and accurate long-term reliability. The output of the detector shall prevent any barricade rise signal, except for EFO command when the vehicle is over the loop.

 

·         A traffic/warning light associated with the rising-road barricades shall also be supplied to indicate the status/position of the barricade.

 

·         The Emergency Fast Operate (EFO) feature shall be integrated/associated with an audible alarm system to emphasize that the operation is under emergency condition.

 

·         A hand pump shall be furnished to allow barricades to be raised manually in the event of prolonged power interruption.

                                                

6.11        UPS System

 

The system shall interface with local main power supply in order to run at time of main power supply failure. The system is an essential service and shall be operational at all times. An uninterruptible power supply unit shall be provided by the CONTRACTOR to support the system in the event of failure of the site power supply. This shall be sized to provide up to four (4) hours support time.

 

 

The UPS Room door shall be provided with Smart card reader (inside and outside) and emergency exit button inside the UPS room.

                               

The UPS system design shall comply with SEC- Standard requirements.

 

The CONTRACTOR shall specify lead-acid type batteries for the UPS system.

                               

UPS System shall be sized to accommodate a minimum of 20% additional power capacity for future expansion.

                                                *** END OF SECTION 6.0 ***


SECTION 7.0       TESTING AND COMMISSIONING

 

7.01        Type Test Report

 

             Two copies of the initial Type Test report shall be provided by the CONTRACTOR to the COMPANY (during the base design stage of the project) for each Major Equipment. The type test report submitted by the CONTRACTOR shall contain all applicable tests and measurements and test methods/procedures, which are required in order to verify Manufacturer's equipment specifications.

 

7.02        Acceptance Test Plan and Procedures

 

             CONTRACTOR shall prepare an acceptance test plan and procedures (which the CONTRACTOR shall use during the field testing, pre-commissioning and commissioning phases of the project), which shall be submitted, to the COMPANY for review and approval at two stages of the project. These stages are as follows:

 

1.          Preliminary Acceptance Test Plan and Procedures for CONTRACTOR installed equipment shall be provided as part of the base design stage of the Project.

 

2.          Detailed Acceptance Test Plan and Procedures (based on the COMPANY approved Preliminary Acceptance Test Plan and Procedures, and Manufacturer's Recommendations), which is to be provided at least six weeks prior to the start of Contractor's pre-commissioning tests.

 

7.03        Pre-commissioning Tests - All Electronic Equipment and Cables

 

             After completing installation of all equipment for the system, CONTRACTOR shall perform all local and end-to-end tests to verify and ensure satisfactory operating condition of the overall system.  CONTRACTOR is required to verify that:

 

1.          All tests (standard manufacturer's equipment tests and special tests required by the COMPANY) are performed and that test results are within manufacturer(s) specified nominal values, and as per applicable COMPANY standards.

 

2.          All test results are recorded and tabulated according to standard on manufacturer's recommended formats, or COMPANY Specified forms/test sheets.  Test title, link/sites name, date and time when test was performed, equations/formulas used to reach calculated or unmeasured figures need to be listed and explained as necessary.

 

3.          The Pre-commissioning tests for the equipment shall follow the same plan and format as required under the final commissioning test procedures (See Section Final Acceptance and Commissioning Tests).

 

4.          The CONTRACTOR must finish the pre-commissioning tests successfully and submit his test results to COMPANY REPRESENTATIVE for evaluation before starting the Final Acceptance and Commissioning Tests.

  

7.04        Final Acceptance and Commissioning Tests

 

1.             Recommended Tests/Measurements

 

                CONTRACTOR, as a minimum, shall be required to perform final acceptance testing of all equipment included in accordance to the COMPANY approved Contractor's Detailed Acceptance Test Plan and Procedures. 

               

2.             Procedures and Other Conditions

 

                The following are general procedures and the order, which is to be followed during the final acceptance and commissioning, tests for the equipment, which is to be provided/installed, by CONTRACTOR:

 

a.             The COMPANY shall designate its Representative(s) to witness the commissioning and acceptance tests prior to putting the system in operation, and commencing the system trial period.

 

b.             CONTRACTOR shall ensure that all mark-up construction documents/drawings pertaining to the Commissioning Acceptance Test are handed over to the COMPANY at least six (6) weeks prior to the commissioning and acceptance test date.

 

c.             CONTRACTOR shall submit 3 copies of pre-commissioning test results, acceptance test schedule, and invite the COMPANY in writing at least two (2) weeks before the proposed date to commence the acceptance and commissioning tests.

 

d.             CONTRACTOR shall demonstrate, by simulation or type test report, that the equipment are operating under maximum design limits and extreme environmental conditions which are specified in the SOW/TS and that results are within the manufacturer's specified nominal values, previously approved by the COMPANY.

 

e.             Equipment tests shall include testing of all wiring for future expansion up to full capacity, by inserting appropriate modules or cards, as required.

 

f.              The Commissioning and Acceptance Tests will be performed according to the following order:

 

Step I - Physical/Mechanical Inspection

 

1.             Physical/Mechanical Inspection for all constructed works and equipment installation.

 

2.             Verification of the physical installation of the equipment with project drawings/documentation.

 

Step II - Local Tests

 

1.             These will include (but may not be limited to) the following:

               

-               Complete local testing of Intruder Detection System, DCCTV, and Access Control System Components.

 

-               Communication Network Components.

 

-               Local testing of Optical components and cabling.

 

-               Tests of UPS System.

 

Step III - End-to-end Test

 

1.             This shall include (but may not be limited to) the following:

 

-               Overall System Performance Tests Intruder Detection System.

 

-               Overall System Performance Tests- DCCTV System.

 

-               Overall System Performance Tests Access Control System

 

-               Overall System Performance Tests - Remote Access and Administration facility.

 

-               Overall System Performance Tests - Alarm/Monitoring facilities

 

g.             The tests shall be performed in sequential order as listed above.

 

h.             CONTRACTOR shall clear all major discrepancies pointed by COMPANY REPRESENTATIVE before resuming all related tests.

 

i.              Final Testing and Commissioning tests shall include detailed testing of Contractor's supplied spare parts.

 

7.05        Test Equipment

 

CONTRACTOR, under the scope of this project, is responsible to provide all standard test equipment (both conventional and special, as recommended by the manufacturer(s)) to be used in testing and commissioning.

 

All test equipment must have updated valid calibration certificate from a recognized calibration-laboratory In or Out-of-Kingdom.  Tests performed using uncalibrated test equipment shall not be accepted by the COMPANY.

 

                                                *** END OF SECTION 7.0 ***


SECTION 8.0     TRAINING PROGRAM

 

8.01        TRAINING PROGRAM

 

                An extensive detailed training program on the operation and maintenance of the system for members of the COMPANY Industrial Security Dept (five-to-six persons). staff shall be offered by the CONTRACTOR.

 

                                                                                *** END OF SECTION 8.0 ***

SECTION 9.0     START-UP AND OPERATION SPARE PARTS

 

9.01        START-UP AND OPERATION SPARE PARTS

 

                Under the scope of this PROJECT the CONTRACTOR shall provide a complete set of start-up spare parts and submit a list of recommended operation and maintenance spare parts and special tools with unit prices as per the requirements outlined below.

 

                The data for the start-up spare parts and recommended operation and maintenance spare parts/special tools shall be prepared in accordance with the requirements of the contract document.

 

                A.            Start-up Spare Parts

 

                The CONTRACTOR shall provide a complete line of start-up spare parts and shall store in his storehouse within the Kingdom.  These spare parts shall be used to replace any defective parts during the warrantee period, and shall be delivered to the COMPANY storehouses upon successful completion of this warrantee period.

 

                B.            Operation and Maintenance Spare Parts and Special Tools

 

                The CONTRACTOR shall submit along with his bid a complete list of recommended spare parts and special tools, to be used by the COMPANY for normal operation and maintenance purposes.  These spare parts and special tools shall be ordered by the COMPANY if deemed necessary.

 

                                                                *** END OF SECTION 9.0***


SECTION 10.0     MAINTENANCE SERVICE

 

10.1        MAINTENANCE SERVICE

 

                 warranty period of one year, the CONTRACTOR shall be obliged to repair and maintain the complete system according to SEC standard, and this shall include all required spare parts, software, and workmanship as part of this project.

 

10.2               PAYMENT:

 

Payment condition will be according to SEC standard.                                                                                                            

 

 

                                                                 *** END OF SECTION 10.0 ***


SECTION 11.0  -  DRAWINGS AND ATTACHMENTS

 

No.

Drawing No.

Sheets

Description

SITE LAYOUT

Note: All attached drawings shall be used by the CONTRACTOR as guidelines and references only for developing its detailed design of the entirely New Integrated Security System for    .

 

             It is the responsibility of the CONTRACTOR to verify and check the accuracy and correctness of the details shown on attached drawings and make the appropriate modifications necessary.

            

             The CONTRACTOR shall bring to the attention of the COMPANY, any erroneous, inferior to HCIS standards, or outdated specification of equipments and materials specified in this document during Bid Clarification Stage for immediate resolution and inclusion of the appropriate changes and modifications as decided by the COMPANY, and shall be part of the Contractor's Technical Proposal Package Submittal.              

 

             All materials either shown or not on the attached reference and conceptual drawings needed for the successful completion of the New Integrated Security System shall be provided and installed by the CONTRACTOR under this PROJECT, unless otherwise stated in the drawings or in this document.

 

*** END OF SECTION 11.0 ***

 

 

 

 

 


No comments:

Post a Comment