EARTHING SYSTEM FOR SUBSTATIONS - consulting

Breaking

Breaking News

Tuesday, 21 June 2022

EARTHING SYSTEM FOR SUBSTATIONS

 3.         Equipment Requiring both Safety and System Grounds

 

3.1       Power Transformer Tanks

 

            Power transformer tanks shall be safety grounded at two points diagonally opposite to each other. These connections shall be made from two different points of the grounding grid.

 

            A separate system ground shall be provided for the neutral of the transformer by means of two stranded copper wires as the ground grid conductor size.

 

            The neutral grounding wires shall be insulated from the transformer tank by support insulators mounted on the tank wall and shall be connected to the grounding grid directly.

 

            Independently mounted radiator bank and XLPE cable termination boxes shall be separately grounded at two diagonally opposite locations.

 

3.2       Instrument Transformers

 

            Potential and current transformers shall have their metal case grounded.

            The grounding terminal of the potential and current transformers shall be connected to the grounding grid. The neutral point of the secondary connection of potential and current transformer shall be grounded to the ground grid in the control/relay room to reduce the transient over-voltages.

 

3.3       Surge Arrestor

 

            For lightning arrestor with operation counter, the insulated lower end of the lightning arrestor shall be connected to the operation counter with an insulated coated copper conductor with cross section area not less then 50 mm2. The surge arrestor ground terminal shall be connected to the ground grid via two stranded copper conductors.

            The system ground conductor shall be as short as possible, free of sharp bends as possible, and shall not be installed in metallic conduit. In addition, ground rods shall be driven adjacent to the arrester connection to the grounding grid to provide the lowest ground grid resistance at this point.

 

3.4       Station Auxiliary Transformer

 

            Station auxiliary transformer tank shall be safety grounded at two locations. One system ground shall be directly connected to the neutral bushing of wye-connected windings that are to be solidly grounded.

 

3.5       Shunt Capacitors and Reactors

 

            Shunt capacitors and reactors are considered safety grounded when mounted on a metal structure that is connected to the grounding grid. One system ground conductor shall be connected to the grounding grid when the capacitors are to be connected in a grounded star configuration.

 

3.6       Coupling Capacitor Voltage Transformers (CCVTs)

 

            CCVTs shall be safety grounded at two locations.

 

4.         Lightning Protection

 

-           The substation shall be protected against direct lightning strokes by shield wires or lightning masts.

-           The lightning protection system must be designed to provide a sufficiently low impedance that the lightning energy will follow the required route.

-           Lightning masts with a suitable height shall be located on the top of the substation metal structure to provide the required protection zones for circuits and apparatus in the whole switchyard (i.e all structures and buildings).

-           The control building shall be protected against direct lightning strokes by lightning masts, down conductor, driven rod, etc..

-           Masts or overhead wires (shield wires), or both, may be used. Combination of overhead wires and lightning masts must be evaluated during the design work.

-           Down conductors shall be connected to each lightning mast/ overhead wire (shield wire) with ground terminals (at least in two points).

-           Down conductors shall be copper 240/185 mm2.

-           The lightning masts shall be copper, the overhead wires (shield wires) shall be 75 mm2 st.

 

 

5. Marking

 

5.1       language

 

            All markings shall be in Arabic and English and shall be legible and indelible.

 

5.2       marking on conductor drums

 

-         Size of conductor.

-         Exact length in meters.

-         Stranding.

-         Net weight in kg.

-         Gross weight in kg.

-         Arrow showing correct direction for rolling (which is the opposite to the direction of unwinding) with instruction “ROLL THIS WAY”.

-         Drum number.

-         Manufacturer’s name and country of origin.

-         Year of manufacture.

-         Purchaser’s order number.

-         Purchaser’s name and address.

-         Shipping destination.

-         Stores/site destination.

In addition each end of conductor on a drum shall bear a non-corroding tag written in English and Arabic with the first five items listed above on it.

 

5.3       connectors

            All connectors and moulds for connections shall be clearly stamped with the appropriate conductor size or sizes in the case of “tee” connectors or crossing.

 

5.4       ground rods

            Each rod shall be marked with its diameter, length and manufacturer’s mark.

 

6. testing and inspection

6.1       soil resistivity test

            The soil resistivity shall be measured during summer season before the design of the grounding system, the measuring procedure shall be submitted.

            Measured procedures shall be under the supervision of the purchaser representatives. If there is difference between the value given in the tender soil investigation report and that measured by the contractor, the system shall be designed under the worst one.

            In case of backfilling, measurement shall be taken to ensure that the backfilled soil resistivity is the same as, or better than before backfilling.

 

6.2       ground resistance

            Tests shall be made on the effectiveness of the bonding and grounding, which will include conductivity tests on selected joints on the main grounding system, and at the connections to equipment and structures. Checks shall also be made on precautions taken to avoid corrosion attach on the grounding system.

 

            The ground resistance shall be measured during the installation and on the completion as follows for:

 

a)     Each ground rods after driving.

b)     The ground grid after completion and backfilling of the trenches.

c)     Each group of ground rods or test point after completion of the connection from the test link terminal.

d)     The completed installation without any connections outside the substation.

Facilities for measuring the ground grid resistance shall be provided from at least four points, access to these points and connections with measuring instruments should be easy and approved by purchaser engineers.

 

The tests shall be carried out by a method and with equipment approved by the purchaser . All tests to be witnessed and the equipment and method used recorded with the test results.

The correct functioning of all isolation links shall also be checked.

 

6.3       Testing of material

 

6.3.1   All grounding materials shall be tested in accordance with the latest edition of the referenced standards and as specified herein. Following completion of the tests, two certified copies of the test reports shall be submitted for approval. No grounding materials shall be shipped until the test reports have been approved by the purchaser. The purchaser, at his discretion, may waive type test requirements, where type tests have previously been carried out and where acceptable type test certificates are provide by the supplier.

 

            The acceptance of such type test certificates shall be based on the stated requirements for type testing contained in this specification.

 

6.3.2   Validity of Test Certificates

 

            Test certificates are considered valid if the tests have been carried out within the last ten years on equipment identical to that on offer using test methods outlined in this specification.

 

6.3.3   Location of Tests

 

            Routine and/or special tests shall be carried out at the supplier’s factory.

 

            Type tests shall be carried out at an approved independent testing laboratory or at the supplier’s laboratory and be witnessed by a representative of an approved independent testing laboratory or other representative acceptable to the purchaser.

 

6.4       inspection

 

            The purchaser may wish to witness tests or to visit the factory during manufacture of any or all items covered by this specification. Accordingly, the supplier shall give the purchaser adequate notice of manufacturing schedules and one month’s notice of test schedules.

 

            The inspector(s) shall have free access during normal working hours to the shop and testing laboratories in connection with the inspection and testing materials.

 

 

6.5       tests

 

6.5.1   Tests on copper clad steel wire:

 

            According to ASTM B227-70 clauses as listed hereunder:

-         Twist test in accordance with clause 9.

-         Elongation test in accordance with clause 4.4.

-         Resistance test in accordance with ASTM method B 193.

 

6.5.2   Test on Soft-Drawn Stranded Copper conductors

 

6.5.2.1            Before Stranding

 

            According to IEC 61089 clauses as listed hereunder:

 

-         Tensile test in accordance with clause 11.1.

-         Elongation test in accordance with clause 11.2.

-         Wrapping test in accordance with clause 11.3.1 and 11.3.3.

-         Electrical resistance test in accordance with clause 12.

 

Table (9): Soft Drawn Stranded Copper

Physical And Electrical Properties

 

 

Size sq. mm.

No. of Stranding and diameter of wire (mm)

Approx. overall diameter mm

Weight of wire kg/km

Theoretical breaking load KN

35

7/2.5

7.5

310

13.77

50

19/1.8

9.0

437

19.38

95

19/2.5

12.5

845

37.89

150

37/2.25

15.80

1337

58.98

240

61/2.25

20.2

2209

97.23

 

 

 

-           Diameter measurement and the results compared with those in table 9. The wrapping test, for durability, shall consist of warping the copper wire 6 times around a wire of its own diameter, unwrapping and rewrapping without breakage of the wire.

 

 

6.5.2.2  Tests on Copper Wires After Stranding

 

            These tests which are the same as those listed in item 6.5.2.1 shall be carried out on samples of the finished conductor.

 

6.5.2.3 Tests on Complete Conductor

 

            These tests shall consist of:

 

            Measurement of lay ratio of each layer.

 

            Tensile strength calculated from the results of the individual wire tests as in IEC 61089.

 

            Measurement of weight.

 

            Measurement of resistance.

 

6.5.3 Tests on Connectors

 

            Proof of current rating and mechanical pull-out strength shall be provided by the manufacturer for each type of connector offered.

 

6.5.4   Test on Copper Ground Rods

 

6.5.4.1            Testing of Bond Between Copper And Steel.

 

            A 150 mm length of rod with one end cut to 45 degree point shall be driven between two steel clamping jaws of a vice set at mm less than the diameter of the rod so as to shear off sufficient metal to expose the joint between the jacket and the rod.

 

6.5.4.2 Bending

 

            There shall be no evidence of cracking of the copper jacket if at room temperature a length of the rod is rigidly held in a vice and the free end bent by applying force normal to the rod at a distance from the clamping device equal to 40 times the diameter of the rod. The magnitude of the force and the direction of application shall be such that the rod is permanently bent through a 30 degree angle.

 

7. sampling

 

7.1       tests on wires before stranding

 

            According to IEC 61089.

            Tests shall be carried out on samples of individual wires taken from not less than 10% of the individual lengths or wire which will be included in any one consignment. Each sample shall be of sufficient length to provide one test specimen for each or the appropriate tests.

 

 

7.2       acceptance tests on wires after stranding

 

            According to IEC 61089.

 

            Tests shall be carried out on wires from samples of finished conductor taken from not less than 10% of the drums included in any one consignment. Each sample shall be of sufficient length to provide, for each wire of the conductor, one test specimen for each of the appropriate tests.

 

7.3       acceptance tests on complete conductor

 

            According to IEC 61089.

 

            Tests shall be carried out on samples of finished conductor taken from not less than 10% of the drums included in any one consignment. Each sample shall be of sufficient length to provide one test specimen for each of the appropriate tests.

 

7.4       acceptance tests on flexible leads

 

            Tests shall be carried out on samples selected according to test schedules mentioned later.

 

7.5  copper-clad steel wire

 

            In accordance with ASTM B227-70 clause 4.

 

8. method of test

 

-           All tests shall be carried out in accordance with the aforementioned specifications as outlined previously.

 

            The attached test schedules specify the relevant clauses.

 

9. acceptance and rejection

 

9.1       general

 

-           The supplier shall forward to the purchaser , three (3) copies of certificates proving that all the required tests have been carried out and that the materials and construction comply with the specified requirements in the attached test schedule. No deliveries of grounding materials shall be made prior to approval by the purchaser of the test certificates.

 

9.2       grounding conductors

 

            If , on testing a sample from any drum, the results do not conform to the requirements, two additional samples shall be taken from the same drum and tested. Both of these samples shall conform to the requirements, otherwise the drum shall be rejected. Samples shall then be taken from all drums comprising the consignment, and tested. If a sample from any drum does not conform to the requirements, then that drum shall be rejected.

 

            If the number of drums rejected exceeds 20% of the the complete number of drums in the consignment, the complete consignment shall be rejected.

 

10. delivery

 

10.1     Packing and shipment :

 

10.1.1             Conductors

 

10.1.1.1 All conductors shall be wound on strong, non-returnable wooden drums suitably treated for outdoor storage and capable of withstanding all normal transportation and handling. All nails and metallic parts on the inner surface must be countersunk so that they cannot damage the conductor. All old nails remaining from previous use of the drum shall be removed. Drums shall not be treated with chemicals injurious to the conductors. A round spindle hold of minimum diameter 80 mm is required at the center of all wooden drums.

 

10.1.1.2 Each drum shall be clearly marked with the supplier’s name, purchaser order no., conductor size and length, drum serial no., and gross weight.

 

10.1.1.3 The drums shall be close lagged after filling. Wooden battens shall be nailed at each end to the drum flange and also secured by two steel straps.

 

10.1.1.4 All drums shall be fitted with steel hubs having a minimum inside diameter of 80 mm. The ratio of the diameter of the inside barrel and the diameter of the flange must not be less than 0.48.

 

10.1.1.5 The timber to be used shall be new, dry, properly seasoned and suitably treated to stand changes in temperature and humidity without deterioration or shrinking.

 

            The timber shall be sufficiently hard and compact to hold the nails and must be treated with a fungicidal and germicidal termite and white ant proof preservative prior to painting.

 

            All drums shall be painted inside and outside with aluminum paint.

 

10.1.1.6 Nails shall be fitted with proper care to avoid any contact with the conductor. Nailing shall be executed from the inside toward the outside. The nail heads shall be embedded into the flange for approximately 6 mm, while their points shall be sufficiently long to allow a proper riveting of about 15 mm. The spacing of the nails shall be approximately 70 mm.

 

10.1.1.7 The inner wrapping of the drum shall be made with a double layer of waterproof paper and another layer shall be placed over the conductor under the lagging.

 

            One layer of waterproof paper must be inserted underneath the last layer of conductor on the drum to avoid sliding against the inner layer. Moreover the conductor shall be tied, at the beginning of the last outer turn, back to one flange with a suitable string and the outer end stapled to the other flange to avoid the conductor moving from the correct position.

 

10.1.1.8 A piece of conductor 45 cm long shall be left sticking out of the flange hole.

 

            The extreme end of the conductor shall be tied, then 25 cm left free and then the remaining 15 to 20 cm shall be tied and taped and covered with cloth (no jute allowed).

 

            The untied section shall be bent as much as possible towards the center of the drum and nailed. Four staples strong enough to withstand transport stresses shall be used; the two outside must clamp the whole conductor, whilst the two inside are fixed through the conductor in order to prevent it sliding.

 

10.1.2 Connectors, ground rods, tools and dies.

 

            All of above items other than copper conductor shall be packed in strong non-returnable cases. The sides and top of each case shall be clearly marked with the supplier’s name, purchaser no., contents, case serial no. and gross weight and shall be accompanied by a detailed packing note in Arabic and English.

 

 

10.2     delivery

 

10.2.1             The tender shall include a guaranteed delivery time from the date of receipt of the official order to arrival designated store.

 

10.2.2             Equipment supplied from outside A.R.E shall be delivered CIF to the designated port of entry.

 

10.2.3 Equipment supplied from within A.R.E shall be delivered to designated stores in A.R.E.

 

11. guarantee

 

The supplier guarantee the delivered equipment against manufacturing, design and material defects for a period as given in the tender documents.

 

 
12 submittals

 

12.1     Submittals Required With Tender:

           

Submittals required with tender are, three copies each of:

 

Tender schedules fully completed.

 

A guaranteed ex-works delivery date and the estimated time required for transport from to the designated stores or site in the A.R.E shall be given.

 

The supplier’s quality assurance program or manual together with a list of international/ national standard specifications covering raw materials, components, processes, tolerances, test procedures, etc. and a list of tests normally carried out one raw materials with a description of test equipment.

 

            A short description of the manufacturing processes and equipment employed in grounding material production shall be provided.

 

            In addition to the specified three copies one set of reproducible drawings showing grounding materials shall be provided.

 

            Detailed drawings of each type of drum that will be used for packing conductors including the constituent material and the method of manufacture shall be supplied.

 

 

12.2     submittals required following award of contract

 

            Submit drawing, calculations, test reports and literature pertaining to the specified items, submittals shall include but not be limited to the following:-

-         Soil resistivity measuring procedure.

-         Resistivity measurement of the surface material used.

-         Calculations of touch and step voltages, station gourd potential rise, and the total calculation of substation grounding system design.

-         Layout drawings of the ground grid.

-         Detailed drawings showing the connections between all equipment and the ground grid.

-         Layout drawings and design calculations of shielding system.

-         Detailed description of shielding system materials.

-         Detailed description of various connectors and connecting processes used to the ground grid.

-         Test reports.

 

No work shall proceed until these calculations and drawings have been approved.

            Final approval of the grounding grid system shall be after site test measurement of the grounding grid resistance.

 

            Details of manufacturing, test and shipping schedules.

 

            Certificates covering raw materials used in the manufacture of conductors.

 

            Certificates covering sample tests carried out on wires before the stranding of conductors.

 

            Certificates covering the routine tests carried out one wires after stranding and on complete conductors before shaping of conductors.

 

            A list giving per drum, the drum number, the size of conductor, the exact length, the net weight, the gross weight, the number of any joints made during stranding and their distance from the outer end.

 

 

13. reference list

 

Tenderer shall submit a reference list that the proposed equipment have been in successful operation in an integrated system for a period of three years minimum on three different substations of same or higher capacity outside the country of the manufacturer and/or in EEHC network for a period not less than three years during the last ten years

 

The experience of the manufacturer and its sub-manufacturers shall be evaluated on the above basis.

  

Test schedules

 

 


Test schedule I

Grounding materials for substations
Tests on copper clad steel wire according
to astm b227-70

 

Test

Method

Conditions for

Acceptance

 

Twist test

 

Clauses 9.1 , 9.2

 

 

The wire shall withstand without fracture, not less than 20 twists.

 

Elongation test

 

 

Clause 4.4

 

Elongation shall be not less than 1.5 per cent.

 

Resistance test

 

 

ASTM method – B193

 

Resistance conforms to standard value.

 

 


 

Test schedule II

Grounding materials for substations
Tests on soft drawn stranded copper

Conductors according to IEC 61089 (except where stated)

(Before and after stranding)

 

 

Test

Method

Conditions for

Acceptance

 

Tensile test

 

 

Clause 6.5.3

 

The tensile values obtained shall comply with the standard requirements of tables 3 and 5 of BS 125.

 

Elongation test

 

Clause 11.2

 

The values obtained shall comply with the appropriate requirements of table 5 in BS 125.

 

Wrapping test

 

 

Clause 11.3.1 and

11.3.3

 

The conductor shall not break.

 

Electrical resistance test

 

Clause 12

 

The values obtained, after correcting to the reference temperature of 20° C, shall not exceed the appropriate minimum values in tables 3 and 6.

Diameter measurement and wrapping tests

 

Clause 6.5.2.1 of this specification

 

The diameter is within 2% of than specified in table 9. Wire shall not break on completion of wrapping test.

 


Test schedule III

Grounding materials for substations
Tests on soft drawn stranded copper conductors
According to IEC 61089 (complete conductor)

 

 

Test

Method

Conditions for

Acceptance

 

Measurement of lay ratio

 

Clause 6.5.2.3

 

Lay ratio shall lie within limits given in table 1.

 

Tensile strength

(calculated)

 

Clause 6.5.2.2

 

Values calculated according to table 2 shall be recorded.

 

Measurement of weight

 

Conductor weight calculated from weight of sample in accordance with table10

 

Conductor weight shall be equal to that specified in table 9 of this specification.

 

Measurement of resistance

 

Conductor resistance calculated from resistance of samples in accordance with table 10.

 

Conductor resistance calculated shall be recorded.

 


 

Test schedule IV

Grounding materials for substations
Test on copper ground rods

 

 

Test

Method

Conditions for

Acceptance

Bond between copper and steel

Clause 6.5.4.1 of this specification

No evidence of separation of the copper jacket from the steel core (peeling of the jacket by the jaws of the vice is acceptable)

Bending

Clause 6.5.4.2 of this specification

 

No evidence of cracking of the copper jacket

 

 

Test schedule V

Grounding materials for substations
Connectors

 

 

Test

Method

Conditions for

Acceptance

Current rating

 

 

 

Mechanical pull-out strength

Manufacturer

 

 

 

Manufacturer

Manufacturer to provide evidence of:

(a)  Current rating of each connector.

(b)  Mechanical pull-out strength for each connector


 

 

  

inquiry schedules

 

 
Inquiry schedule

(To be Completed by Purchaser)

Grounding Materials For Substation

 

1.         Bare Soft Drawn Stranded Copper

            (a) 240 sq.mm           ……………   Length …………………………..km

            (b) 185 sq.mm           ……………   Length …………………………..km

            (c) 150 sq.mm           ……………   Length …………………………..km

            (d) 120 sq.mm           ……………   Length …………………………..km

 

2.         Insulated Soft Drawn Stranded Copper

            (a) 150 sq.mm           ……………   Length …………………………..km

            (b) 95 sq.mm             ……………   Length …………………………..km

            (c) 50 sq.mm             ……………   Length …………………………..km

 

3.         Ground rod equipment

            (a) Ground rods with connectors for        No       . ……………………..

                  240/185 sq. mm copper

 

            (b) Ground rod steel tips                             No.      ……………………….

 

            (c) Ground rods driving heads                   No.      ……………………….

 

4.         Connectors

 

            (a)       Compression ‘Tee’ or parallel connectors

 

                        (as required)

 

            (b)       Bimetallic connectors

 

                        Description …………………………………………………….


Inquiry schedule

(To be Completed by Purchaser)

Grounding Materials For Substations

 

            (c)       Compression lug connectors

 

                        Single lug 240 sq.mm.                     No.      ……………………

                        Single lug 185 sq.mm.                     No.      ……………………

                        Single lug 150 sq.mm.                     No.      ……………………

                        Single lug 120 sq.mm.                     No.      ……………………

                        Single lug 95 sq.mm.                        No.      ……………………

                        Single lug 50 sq.mm.                        No.      ……………………

                        Double lug 95 sq.mm.                      No.      ……………………

 

5.         Copper ground rods                                                 No.      ……………………

 

            Additional Requirements ………………………………………………..

            ……………………………………………………………………………

            ……………………………………………………………………………

            ……………………………………………………………………………

 

6.         Material destination stores/site …………………………………………

 

 

 

tender schedules


tender schedule

(To be Completed by Tenderer)

Grounding Material For Substations

 

 

Ref

Description

Units

 

Offered

1.

Bare Soft Drawn Stranded Copper

………….

 

…………..

 

Manufacturer

………….

 

…………..

 

240 sq.mm. Length per drum

No. of drums

………….

 

…………..

 

185 sq.mm. Length per drum

No. of drums

………….

 

…………..

 

150 sq.mm. Length per drum

No. of drums

………….

 

…………..

 

120 sq.mm. Length per drum

No. of drums

………….

 

…………..

 

 

………….

 

…………..

2.

Insulated Soft Drawn Stranded Copper

………….

 

…………..

 

Manufacturer

………….

 

…………..

 

150 sq.mm. Length per drum

No. of drums

………….

 

…………..

 

Thickness of insulation

………….

 

…………..

 

95 sq.mm Length per drum

………….

 

…………..

 

No. of drums

………….

 

…………..

 

Thickness of insulation

………….

 

…………..

 

50 sq.mm Length per drum

………….

 

…………..

 

No. of drum

………….

 

…………..

 

Thickness of insulation

………….

 

…………..

 

 

………….

 

…………..

 


tender schedule (Cont.)

(To be Completed by Tenderer)

Grounding Material For Substations

 

 

 

Ref

Description

Units

 

Offered

 

 

………….

 

…………..

3.

Ground rods, steel tip and driving head

………….

 

…………..

 

Manufacturer

………….

 

…………..

 

Material of rods

………….

 

…………..

 

Length of rods

m

 

…………..

 

No. of steel tips

………….

 

…………..

 

No. of driving heads

………….

 

…………..

 

 

………….

 

…………..

4.

Compression lug connector

………….

 

…………..

 

Manufacturer

………….

 

…………..

 

Type single/double

………….

 

…………..

 

Conductor size

………….

 

…………..

 

 

Singed : ……………………………………

 

Company : ……………………………….

 

Position in Company : ………………….

 

Date : ………………………..                                            ……………………

                                                                                                   Company Stamp





No comments:

Post a Comment