GROUNDING SYSTEMS - consulting

Breaking

Breaking News

Monday, 20 June 2022

GROUNDING SYSTEMS

Earthing system for substations

 

1. scope

 

            This specification covers the design, manufacturing, testing, delivery, commissioning, and guarantee of the Grounding system used in 500 kV & 220 kV, and 66 kV substations.
 

2. definitions

 

2.1       ground grid – substation

 

            The complete mesh of copper conductors is laid in the earth to provide a common ground for electrical devices or metallic structures.

 

2.2       ground rods - substations

 

            Copper rods and extensions are driven into the earth and connected to the ground grid to lower its resistance and also to dissipate ground current into the earth.

 

2.3       connectors

 

            Copper or a copper alloy including bimetallic devices, of suitable electric conductance and mechanical strength for connecting conductor to conductor, conductor to the ground rod, and conductor to metalwork.

 

2.4       ground resistance

 

            The ground resistance is the ohmic resistance of the grounding system to remote earth.

 

2.5       ground

 

            A conducting connection by which any steelwork, equipment, and the electric circuit are connected to the earth.

 

2.6       ground potential rise (gpr):-

 

            The maximum voltage that a substation grounding grid may attain to a distant point is assumed to be at the potential of remote earth.

 

2.7       exothermal weld

 

            This is a process whereby a suitable graphite mold is placed around conducting pieces to be connected (i.e. ground electrodes and grounding leads).

 

2.8       touch voltage

 

            The potential difference between the ground potential rise (GPR) and the surface potential at the point where a person is standing while at the same time having a hand in contact with a grounded structure.

 

2.9       step voltage

 

            The difference in surface potential experienced by a person bridging
a distance of 1 m with the feet without contacting any grounded object.

 

2.10     ground mat

 

            A solid metallic plate or a system of closely spaced bare conductors that are connected to and often placed in shallow depths above a ground grid or elsewhere at the earth's surface, in order to obtain an extra protective measure minimizing the danger of the exposure to high step or touch voltages in a critical operating area or places that are frequently used by people.

  

3. Classification

 

            The grounding materials covered by this specification are:-

 

3.1       copper conductor

            Stranded copper conductor used to form ground grids and provide the connection from equipment to ground grid.

 

3.2       flexible ground leads

 

            Multi-stranded insulated copper conductor used for temporary grounding of HV equipment.

 

3.3       ground rods, extensions and the connections for attachement of copper conductor.

 

3.4       bimetallic connectors

 

3.5       shield wire.

 

            Conductors consisting of galvanized steel wire, hard/soft drawn copper clad steel wire, or soft annealed copper clad steel wire and installed in counterpoise or crowfoot arrangement.

 

3.6       connector cable

 

            Connector cables consist of hard-drawn stranded copper conductors. These connectors shall be used for connections between all above-ground conductive metal ports.

 

4. requirements

 

4.1       environmental Conditions:

 

4.1.1   The Environmental conditions listed in the table (1) shall apply.


 
Table (1) Standard Environmental Conditions

 

Clause

Description

 

Value

1-

 

Pressure MB-annual means.

1013

2-

Atmospheric Temperature °C:-

Maximum mean daily

Minimum mean daily

Yearly mean

 

 

47*

-5

30

3-

Relative humidity %

Maximum relative humidity

Minimum relative humidity

Average relative humidity

Daily mean

 

 

100

20

75

95

4-

Rainfall mean-annual total (mm)

 

65

5-

Maximum wind speed (m/sec.) at 10m above ground level.

 

35

6-

Soil temperature at a depth of 1.5 m.

25°C

 

7-

Solar energy radiation W/m²

 

>1100

 

8-

Wind pressure N/m²

766

 

9-

Absolute black bulb °C max. recorded

75.7

 

10-

Thunderstorms

Occasional

 

11-

Sand storms

Occur occasionally, especially in the desert.

 

12-

Pollution

Heavy pollution >50 mS

 

13-

Seismic load

 

According to the Egyptian Code and the attached map.

 

Note:                         This table is valid altitude (0-1000m)

            The maximum temperature shall be in accordance with the substation location in Egypt.

*          For Cairo Zone


4.1.2   All outdoor locations are subject to sand storms. Consequently, all equipment shall be proof against ingress of sand.

 

4.2       System Parameters

 

4.2.1   The system parameters listed in tables (2,3,4) shall apply.

 

Table (2)         500 kV System Parameters

 

 

 

Item

Parameter

Value

1-

Frequency                                                                  Hz

50

2-

Configuration

3phase

3-

Neutral arrangement

solidly earthed

4-

Service system voltage                                               kV r.m.s

500

5-

Rated system voltage for equipment                          kV r.m.s

550

6-

Duration of max. temporary over voltage.                 sec.

0.5

7-

Rated short-time withstands current.                           KA  r.m.s

40/50

8-

Rated duration of short circuit .                                   sec.

1

9-

Rated peak withstand current.                                     KA

100/125

10-

Lightning impulse withstand voltage 1.2/50 ms (LIWL)    kV peak

1550

11-

Switching impulse withstand voltage 250/2500

1175

 

ms to earth (SIWL).                                                     kV peak

 

12-

One minute  power frequency withstand voltage

680

 

to earth.                                                                       kV r.m.s

 

13-

Min. specific leakage path cm/kV service voltage

 

 

 For equipment                                                           cm/KV

3.5

 

 For surge arrester                                                      cm/KV

4.5

14-

Allowable Minimum Clearance (mm):

 

 

For the receiving steel structure :

 

 

 - Between live conductors and earth.                        mm

4500

 

 - Between phases in air phase to phase                     mm

6000

 

For Equipment :

 

 

 - Between live conductors and earthed parts            mm

3700

 

 - Between phases in air phase to phase                     mm

4500

15-

Radio interference level.                                         micro. volt.

Max. 2500

 


 

Table (3)         220 kV System Parameters

 

 

 

Item

Parameter

Value

1-

Frequency                                                                     Hz

50

2-

Configuration

3phase

3-

Neutral arrangement

solidly earthed

4-

Service system voltage                                                kV r.m.s

220

5-

Rated system voltage for equipment                        kV r.m.s

245

6-

Duration of max. temporary over voltage.                  sec.

0.5

7-

Rated short-time withstands current.                           KA  r.m.s

40/50

8-

Rated duration of short circuit.                                 sec.

1

9-

Rated peak withstand current.                                    kA

100/125

10-

Lightning impulse withstand voltage 1.2/50 ms (LIWL)  kV peak

1050

11-

One minute  power frequency withstands voltage       

460

 

to earth.                                                                       kV r.m.s

 

12-

Min. specific leakage path cm/kV service voltage for :

 

 

Equipment                                                                    cm/KV

3.5

 

For surge arrester                                                         cm/KV

4.5

13-

Allowable Minimum Clearance (mm):

 

 

 For the receiving steel structure

 

 

- Between live conductors and earthed parts                mm

2500

 

- Between phases in air                                                 mm

3750

 

 For the equipment

 

 

- Between live conductors and earthed parts                mm

2100

 

- Between phases in air                                                 mm

2400

14-

Radio interference level.                                         micro. volt.

Max. 2500

 


 

Table (4)  66 kV System Parameters

 

 

 

Item

Parameter

Value

1-

Frequency                                                              Hz

50

2-

Configuration

3phase

3-

Neutral arrangement

solidly earthed

4-

Service system voltage                                 KV r.m.s

66

5-

Rate system voltage for equipment              kV r.m.s

72.5

6-

Duration of max. temporary over voltage.     Sec.

0.5

7-

Rated short-time withstands current.               KV r.m.s

31.5

8-

Rated duration of short circuit.                      sec.

1

9-

Rated peak withstand current.                         KA

80

10-

Lightning impulse withstand voltage 1.2/50 ms (LIWL) KV

325

11-

One minute  power frequency withstand voltage

140

 

to earth.                                                            KV r.m.s

 

12-

Min. specific leakage path cm/kV service voltage

 

 

For surge arrester

4.5cm/KV

 

For equipment:  outdoor

3.5 cm/KV

 

                         :   indoor

2.5 cm/KV

13-

Allowable Minimum Clearance (mm)

 

 

 For the receiving steel structure

 

 

- Between live conductors and earthed parts

900

 

- Between phases in air

1120

 

 For the equipment (indoor/outdoor)

 

 

- Between live conductors and earthed parts

800/900

 

- Between phases in air

800/1120

 

 

 

 


 

4.3       Quality Assurance:

 

4.3.1   Applicable Codes and Standards

 

The earthing system for substations provided under this specification shall conform to the applicable codes and standards of:

           

EUS – Electricity Utility Specifications:

American Society For Testing And Material

ASTM B227-70

Hard-drawn cold steel wire

 

International Electrotechnical  Commission

IEC 60364

Electrical installation of buildings

IEC 61089

Round wire concentric lay overhead electrical stranded conductors.

 

IEEE – Institute of Electrical And Electronics Engineers

IEEE 80-2000

Guide for safety in substation grounding.

IEEE 81-1983

Guide for measuring earth resistivity, ground impedance, and earth surface potentials of a ground system.

IEEE 837-2002

Standard for qualifying permanent connections used in substation grounding.

 

4.3.2   Alternative Codes and Standards

 

            The tenderer may propose alternative codes and standards provided it is demonstrated that they give an equivalent or better degree of quality than the referenced codes and standards. Acceptability of any alternative code or standard is at the discretion of the purchaser.

 

4.4.3   Precedence of Codes and Standards

 

            In case of conflict between this specification and any of the referenced codes and standards, the following order of precedence shall apply:

 

-         This specification.

-         EUS specification.

-         IEC recommendation and publications.

-         Other referenced codes and standards.

-         Acceptable alternative codes and standards.

 

4.4       DESIGN

 

4.4.1   General

 

            The grounding system shall be designed to meet the parameters stipulated for operation on the system specified.

            The first step in the practical design of a grid or mat consists of inspecting the layout plan of equipment and structures. A continuous grounding conductor shall surround the grid perimeter to avoid current concentration and hence high gradients at projecting ground conductor ends. Within the grid, conductors shall be laid in parallel lines, and at reasonably uniform spacing. They shall be located, where practical, along rows of structures or equipment to facilitate the making of ground connections. The preliminary design shall be adjusted so that the total length of the buried conductor, including cross-connections and rods, is at least equal to that required to keep local potential differences within acceptable limits.

 

4.4.2   Soil Investigation

 

            The resistivity is extremely variable from one spot to another according to the nature of the soil, degree of humidity, and temperature. If the resistivity varies appreciably with depth, a greater number of readings should be taken. It is often desirable to use in increased range or probe spacing for a reasonably accurate estimate of the soil resistivity.

 

            For substation design, soil resistivity readings shall normally be taken under dry conditions, during the summer months, provided it does not cause delays to the project schedule.

 

            Backfilled material shall have the same soil resistivity or better than that of the original soil.

 

            A number of measuring techniques are described in detail in ANSI/IEEE 80-2000. The Winner’s four-pin method is the most commonly used technique. Winner’s method is based on the assumption that soil resistivity is uniform.

 

In case the soil resistivity readings are within +10% of mean value, manual calculations shall be done by taking the mean value.

 

            In case of wide variations in field readings, computer software shall be used to simulate multilayers soil conditions consistent with the varied field readings for determining the applicable value of soil resistivity for calculation purposes.

 

4.4.3   Grounding system Layout/Arrangement

 

1.         The grounding grid shall consist of a network of interconnected horizontally buried conductors and vertically buried ground rods into the ground to provide for grounding connections to grounded neutrals, equipment ground terminals, equipment housings, and structures, and to limit the maximum possible shock voltage to safe values during ground fault conditions.

 

2.         The grounding grid shall encompass all of the areas within the fence, and shall extend at least 1.5 meters outside the substation fence on all sides (if space permits), including all gates in any position (open or closed) to enclose as much ground as practicable and to avoid current concentration and hence high gradients at the grid periphery. A perimeter grid conductor shall also surround the substation control building, at a distance of 0.5-1.5 meters.

            The grounding grid shall be installed beneath the 66 KV building (if applicable).

 

3.         Grounding grid shall be buried at a depth ranging from 0.5 to 1.5 m below the final earth grade (excluding asphalt covering).

 

4.         The grounding grid conductors shall preferably be laid at reasonable uniform spacing. Depending upon site conditions, the typical spacing of the main conductors generally ranges between 3 meters to 15 meters. In congested areas, reduced intervals may be desirable. Grid spacing should be halved around the perimeter of the grid to reduce periphery voltage gradients. It may also be desirable to subdivide the corner meshes into quarter areas to reduce normally higher mesh voltages at such locations.

 

5.         Main conductors and secondary conductors shall be bonded at points of crossover by thermo weld process.

 

6.         The ground rods shall have minimum dimensions of 16f mm x 3.0 meter However, for other space-limited installations extra long rods may be considered.

 

            It is recommended that rods be installed in the tops 50 cm minimum below grade and bonded to the grounding grid by thermo weld process.

 

            The rods shall, in general, be installed at all points in the grid as defined above, in particular near surge arrester connections and transformer neutral where large ground currents may be expected. The rods installed mainly along the grid perimeter will considerably moderate the steep increase of the surface gradient near the peripheral meshes.

 

7.         Specified values of some parameters having a substantial impact on the grid design are summarized in table 5 for ready reference.

 

8.         Test links arrangement must be done so that the opening of one link does not interface with ground connections other than the one under test at least four links test shall be provided.

 

9.         A (0.15 m) layer of high resistivity surface material such as crushed stone shall be spread on the earth's surface above the ground grid in the switchyard are to provide a high resistance surface treatment to reduce the hazard from step/touch potential to persons during a severe fault.

            In some location such as in indoor substation it is not reasonable to be able to use crushed stone, so other means to increase the safety of person may be required by providing an insulated floor covering indoors, such as plastic tiles, rubber mats, etc… .

 

Table 5 : Grounding Grid Design Parameters to be Considered

 

Description

Specified Values

Grid current that flows between ground grid and surrounding earth (Ig).

Up to design

calculations.

Surface layer resistivity gravel.

3000, ohm meter (min)

Current projection factor for future system growth.

1.0

Maximum possible fault clearing time.

1.0 sec.

Duration of fault current for determining allowable body current.

1.0 sec. Or back up clearing time.

Depth of ground grid conductors.

0.5 to 1.5 meters.

Typical spacing between parallel conductors.

3 to 15 meters

Resistance of ground system during summer.

< 0.5 W

Standard stranded copper conductor sizes for grounding.

95 mm2, 120 mm2

150 mm2, 185 mm2

and 240 mm2.

 

4.4.4   Selection of Grounding Conductor Material, Size And Joints

 

            Soft/ hard drawn, stranded copper shall be used for the ground grid conductors and grounding leads. The conductor shall be round shaped for maximum cross-sectional contact with the ground. Copper shall be used for ground rods.

 

            Each element of the ground system (including grid proper, connecting ground leads, and electrodes) shall be so designed that it will:-

 

1.         Resist fusing and deterioration of electric joints under the most adverse combination of fault-current magnitude and fault duration to which it might be subjected.

 

2.         Minimum size of the grounding conductor

            The following equation shall be used to evaluate the minimum conductor size (in mm2) as a function of conductor current.

 

 

                                

 

            Where:

            I           is the r.m.s current in kA

            Amm2  is  the  conductor cross section in mm2

            Tm       is the maximum allowable temperature in °C.

            Ta        is the ambient temperature in °C.

            Tr         is the reference temperature for material constants in °C.

            a0       is the thermal coefficient of resistivety at 0°C in 1/C°.

ar        is the thermal coefficient of resistivity at reference temperature Tr in 1/C°,

rr         is the resistivity of the ground conductor at referenced temperature Tr in micro ohms-cm.

            K0        =          

            tc          is the duration of fault current in sec.

 

TCAP is the thermal capacity factor per unit volume (from material

constant table 6) in J/cm3/°C.

 

            Note that ar and rr are both to be found for the same reference temperature.

            Table 6 provides the material constants for stranded, annealed, soft copper wire at 20° C.

 

Table 6: Material constants for stranded,

Annealed, Soft Copper Wire

 

Material conductivity (%)

100.00

ar @ 20°

0.00393

K0 = (1/a0) @ 0° C

234

Fusing Temperature (°C)

1083

rr @ 20° C (mW/cm)

1.7241

TCAP Factor Effective Value (J/cm3/°C)

3.422

 

 


Table 7: Recommended Ground conductor Sizes

 

Conductor size for equipment grounding leads mm2

 

Conductor size for main ground grid, embedded or exposed grounding system mm2

95

 

120

120

 

150

185

 

185

240

 

30x6/40x5

2x240

 

2 x 240

 

            The recommended standard grounding copper conductor sizes are shown in table 7. The conductor size shall be calculated per formula indicated in item 4.4.4 and then the final choice of the conductor size shall be made from the nearest higher sizes shown in table 7.

 

            The designer should take precautions to ensure that the temperature of any conductor will not exceed the maximum allowable temperature of the lowest rated component.

 

            The following design parameter shall be taken into account while calculating the conductor size.

 

a.      Maximum temperature (Melting/fusing) of the grid copper conductor is 1083° C , taking into account the exclusive use of exothermic connectors on the buried ground grid.

 

b.      Maximum temperature for the above-grade joints for equipment grounds, system neutral and ground buses shall be within a 250- 350° C.

 

c.      The fault clearing time (tc) shall be taken as one second.

 

d.      The fault current shall be regarded as highest specified switchgear symmetrical short circuit rating in a particular substation.

 

e.      Maximum allowable conductor temperature during short circuit 300° C.

 

3.         Selection of joints

 

            All joints should be evaluated in terms of conductivity, thermal capacity, mechanical strength and reliability.

 

            Exothermic welded joints shall be used on buried ground grid (cross-over points, etc.) which make the connections and internal part of the homogenous conductor.

 

 

            Exothermic welding connection kits will also be used for connecting, all earthing material. Unless otherwise supplied by contractor, the kit shall consist of:

 

(a)  Graphite moulds for right angle, tee, and straight through connections.

(b)  Handle clamp for the moulds.

(c)  Welding metal powder.

(d)  Starting flint gun.

(e)  Mould scraper.

(f)   Mould cleaning brush.

 

The kit shall contain all the required equipment to form the welded connection. The mould shall be re-usable after cleaning.

 

            The above grade joints of pigtails with the respective connectors shall be compression type, whereas the connector itself shall be bolted to the respective equipment, structures, etc. Equipment installed inside the substation control building shall be connected to the exposed grounding system conductor by means of compression joints, and no bolted connections shall use. All other connections, such as the ground bar routed in indoor substation buildings, shall be exothermic. All bolted and compression joints shall withstand a maximum temperature of 250°C.

 

4.4.5   Ground Rods

 

1.         Substation Ground Rods

 

            The earth rods shall be minimum 3 m long of solid hardened copper rod of 16 mm diameter two parts each 1.5 m length with a screwed connection at each end to allow the fitting of a hardened steel tip on the driven end and the fitting of further lengths of rod and a steel driving cap on the upper end. Each screwed connection shall have a shoulder so that the driving force is transmitted through the body of the rod and not through the threads.

 

            It is intended that the rod/rods would be driven to the required depth then cut at ground grid level and joined to the grid by means of a short length of conductor and a special connector supplied with the rod.

 

2.         Ground Rod Couplings

 

            These shall be of aluminum bronze, counter bored to enclose fully the threads on the rods. The design shall ensure that, when assembled, there will be direct rod to rod contact when the rod driving force is applied.

 

3.         Ground Rod Driving Head

 

            The driving head shall be of high strength steel, threaded to fit the ground rod couplings. The design shall ensure that there is direct driving head to rod contact when the rod driving force is applied. The driving head shall be suitable for re-use.

 

4.4.6   Ground  Electrode Copper Mat

 

            This shall be of copper bars. The overall dimension shall be 1000 mm x 1000 mm.

 

4.4.7   Structure And Equipment Grounding Requirements

 

1.         General

 

            The grounding connections provided to substation equipment and structures fall under two categories, namely.

 

a.      Safety Grounds. (equipment grounds)

b.      System Grounds.

 

The safety grounds is the connection to earth of non current carrying metal parts to protect personnel from hazards whereas the system grounds is to protect the equipment.

 

Certain categories of the substation equipment may require both the “safety” as well as the “system” grounds. As a matter of principle, all non-current carrying conductive parts and all neutrals shall be connected to the grounding grid.

 

2.         Equipment Requiring Only Safety Grounds

 

2.1       Steel Structures and Switch Racks

 

            Switch racks and every steel structure that supports insulators or electrical equipment shall be grounded by means of bolted connection at two (2) diagonally opposite legs. Equipment mounted on steel supporting structures shall have separate grounding conductors. The ground conductor shall be supported on the structure at 1.0-meter intervals by clamps.

 

2.2       Fences / Gates

 

            If space permits a perimeter ground conductor shall be laid which follows the fence line and the gate in any position (open or close) at a distance of 0.5 – 1.5 m beyond (outside) the fencing. The perimeter ground conductor and the fence then shall be bonded electrically at corner posts, gate posts and every alternate line post. The gates shall be bonded to the gate posts with a flexible copper cable or braid.

 

            The barbed wire the top of the SSD (Safety and Security Directive) type fence, if applicable, shall be bonded to the grounding grid.

 

2.3       Cables

 

            Metallic cable sheaths shall be effectively grounded by connecting a flexible braid to the sheath to eliminate dangerous induced voltage to earth.

 

            a.         Control

Shield of control cables shall be grounded at both ends to the grounding grid. In some cases a separate conductor shall be run in parallel with the control cable and connected to the two sheath ground points.

 

            b.         Power Cables

The sheath of single conductor power cables within substation area shall be grounded at one end, preferably at the source end only, in order to reduce the sheath current.

 

For long cables. The sheath should be grounding at both ends and at each splice.

 

Power cable potheads shall be case-grounded via one of the mounting bolts.

 

If ring type CTs are installed on power cables, the grounding of sheath shall be done such that the sheath current to ground will not influence CT secondary current.

 

            c.         Instrument Cables

Instrument cables carrying milliamps, analog or digital signals shall have their metallic screening grounded at one point by means of PVC insulated grounding wire connected to separate instrument ground bar which is insulated from cubicle ground.

 

            d.         signal Cables

All signal cables used in telemetering and communications shall have their shield grounded at one end only to reduce interference from stray sources.

 

2.4       Cable Tray System

 

            Cable tray system shall be grounded with bare copper conductor of
50 mm2 size at both ends and shall be bonded across gaps including expansions gaps.

 

2.5       Control Buildings

 

            Control building(s) shall be treated as a part of the substation, and shall be grounded using the same safety criteria as the substation. The control building shall be encircled by a grounding conductor. Reinforcement of the control building shall not be connected to the main grounding grid. If may therefore be necessary, lay ground grid beneath the control building.

 

All electrical apparatus and metallic doors shall be bonded via two independent connections.

             All air conditioning ducts inside the control building(s) shall be grounded at both ends and cross bonded at all joints. Further, angle irons installed on indoor trenches to support the metallic covers shall also be grounded at both ends.

 

2.6       Control Cabinets, Operating Mechanism Housing, Box , etc.

 

            All the metallic enclosures of these boxes/cabinets shall be connected to the grounding grid through the grounding terminals.

 

            The door(s) of all cabin, junction boxes, etc., shall be bonded to the respective housing with a flexible copper conductor.

 

            A copper ground bus of a minimum of 25 mm x 6 mm size shall be provided inside these cabinets. All grounding connections from individual items including motor frames shall be connected directly, but separately, to this grounding bus.

 

 

2.7       Metallic Conduits

 

            All metallic conduits shall be connected to the grounding grid at each manhole or at terminating points by using a conductor size of 50 mm2. Conduits terminating in metal junction boxes shall be grounded by means of earthing studs or brazed connections.

 

 

 

2.8       circuit Breakers and Disconnect Switches

 

            All circuit breakers and disconnect switches shall be connected to the grounding grid from two opposite points. A good electrical connection shall be maintained between the steel structure and any bolted accessories mounted on it.

 

2.9       Operating Handles for Outdoor Switches

 

            A large percentage of fatal accidents from voltage gradients are in fact associated with manual operating handles of disconnect switches, etc.

            A metal grounding plate or mat (operating platform), shall be placed where the operator must stand to operate the device. The operating handles shall be connected by a ground conductor (preferably flexible wire, braid strap) from the vertical operating pipe to the ground mat and the ground mat is connected directly to the ground grid.

 

2.10    Terminal Transmission Tower Grounding

 

            Terminal transmission towers located adjacent to the substation shall be connected to the substation grounding grid at two diagonally opposite points. The shield wire shall be connected to the grounding grid.

 

2.11    Reclosers

 

            The tank of recloser(s) shall be safety grounded at two locations. The respective control cabinets shall also be connected to the grounding grid.

 

2.12    Oil Tanks and Oil/Water Pipings

 

            All oil tanks shall be grounded at two points with bolted cable connections from two different points to the grounding grid. Oil piping shall be grounded at intervals of 12 m. Runs shorter than 12 m shall be grounded at least at two points. Water piping shall be connected to the grounding system at all service points. In addition, copper conductors of adequate size shall be connected to the main water pipe from two separate points of the grounding grid.

 

2.13 Metal-enclosed Switchgear

 

            Metal enclosed switchgear shall have three safety grounds connected to the switchgear grounding bus. Withdrawable circuit breakers and PTs shall be provided with a reliable connection to the ground bus.

 

 

2.14    Grounding of Lighting Equipment

 

Grounding of the lighting fixtures, lamp holders, lamps, receptacles and metal poles supporting lighting fixtures shall be per IEC standard.




 

 

 

 


No comments:

Post a Comment