Wiring
- Control wiring shall consist of a stranded copper conductor, not less than 1.5 mm2. Wire insulation shall be 750 V class, thermosetting and moisture, heat, oil, and flame retardant.
- Color coding of
all wiring shall be as per the latest codes and standards.
- Equipment shall
be completely wired within their withdrawable unit for control and operation.
- Wiring requiring
external connections shall be brought to terminal blocks for terminations of
external leads. Where they terminate on
terminal blocks, wire shall be identified by permanent markings such as PVC
sleeves.
- Wire
identification shall correspond to the identification used on the wiring
drawings.
. - If the wire ends
have crimped on connectors, these more likely to be pin or spade type for use
in pressure plate type terminals, e.g. Klippon or Phonix.
- The following
starter wiring points shall be brought out to separate terminal block points
for external connections:
Both sides of the
control transformer secondary,
Both sides of the seal
in contact,
Starter operating coil
terminal normally connected to one side of the seal-in-contact,
Both terminals of
auxiliary contacts.
- All power and control cables shall enter
the switchboard & MCCs assembly from the bottom.
- Compression-type terminal connectors shall
be furnished for all power cables.
- Suitable supports shall be provided within
the switchgear/switchboard/MCC housing for the power and control cables.
- Power cables will be solid dielectric
insulated.
- Terminal
Blocks
Terminal blocks shall be provided for all
secondary and control wiring requiring external connections.
Terminal blocks shall be installed in each compartment in a uniformly accessible location.
- Terminal blocks shall be molded
composition type with separate terminals for internal and external
connections.
Terminal shall be of pressure plate type
with only a single conductor per side permitted, e.g. Klippon, Phonix, or equivalent.
Terminal blocks shall have barriers between
terminal points and a terminal-marking strip.
A minimum of 20% spare terminal points
shall be provided on each terminal block.
Grounding
Each switchgear/switchboard & MCC shall
be provided with a main copper ground bus not less than 50X50-mm in cross
section, along the length of the switchboard/MCC.
The ground bus shall be furnished with a mechanical clamp-type connector at each end for ground cable connections.
All framework, metal enclosures, barriers,
and non-current carrying parts of equipment shall be securely grounded and
grounding connections shall be brought to the ground bus. The metal framework
of the assembly may form part of the internal grounding circuit, provided a solid and uninterrupted path is thereby assured; otherwise, grounding
connections shall be furnished.
Painting
All metal sheets and framework shall be
thoroughly cleaned after fabrication, treated with a phosphate coating and
unless otherwise noted, given a prime coat of rust-inhibiting paint.
A finish coat shall be applied overall (stoved
enamel).
Switchgear/Switchboards / MCC
The individual
unit compartments shall be such as to obtain different zones fully insulated
from each other, namely:
The switchgear
compartment
The bus bar section
The power and control
cable compartment.
Special means
shall be provided for connection of the busbar systems between transformers and
boards as specified.
Instrument Transformers
The completely enclosed, dry cast resin type instrument
transformers shall be designed in accordance with the requirements of IEC 60185
& 60186 (latest version).
Remote Indication
All electrical measuring systems with remote indications in the GT
Local Control Room and/or Main Control Room shall be equipped with transducers
and incorporated in the DCS.
Voltage Monitoring
The following voltage monitoring relays shall be installed in the
measuring section of each switchboard & MCC.
Incoming supply voltage
monitoring
Busbar Voltage
Monitoring
Definite time delayed,
two-phase Undervoltage relay (27), adjustable in steps.
Signaling
Each
Circuit breaker or
draw-out unit withdrawn
Circuit breaker or
draw-out unit in the test position
Circuit breaker or
draw-out unit in "ON" (operating position).
Circuit breaker or
draw-out unit in "OFF" position.
In the event of failure of the control voltage
on a Sub-section or in a switchgear
cabinet, a Control Voltage "OFF" signal shall be provided in the GT
Unit Local Control Room and repeated in Main Control Room DCS.
Space Compartments
Each Switchgear/switchboard section and MCC shall be provided with
at least 10 % or a minimum of one (1) empty compartments of each type completely
wired as space.
Spare Feeders
Each switchgear/switchboard section / MCC shall contain 10 % or
minimum of one fully equipped and functional spare outgoing feeder of each
type.
Terminal Boxes and Subsidiary Distributions
Field-installed intermediate or collective terminal boxes as well
as subsidiary distributions comprising collective power and control circuits,
such as for electrically operated
dampers, valves, etc. it shall be of the
cast iron, clad type, consisting of individual and standardized cast iron cases,
of IP-55 protection class according to IEC Standards.
Interlocks
Electrical
ON/OFF interlocks of incoming feeders, transformer feeders, and coupling feeders
shall be realized in the relevant boards.
Electrical
interlocks of motors and valve feeders involved in the main process functions
of the units shall be effected in relay cubicles.
The basic
interlocking principles for the power supply systems are listed below:
All incoming
feeders of a switchgear/switchboard or a section of such board shall be
interlocked against each other and against the bus coupler/interconnector, so
that each distribution board or section thereof shall be fed only by one power
source.
Paralleling of in feeds and overlapped switching shall not be
possible.
Tripping of a protection device in one of two feeder circuits
of any double fed switchboard (for example tripping by 13.8kV transformer
feeder protection, transformer Buchholz or oil temperature protection, but not
the LV incomer protection) shall automatically trip the faulty circuit and
close the second feeder circuit (provided its feeding breaker is closed) via
the second LV incoming breaker or the bus sectionalize, whatever is
applicable. The automatic change over shall be controlled by an under-voltage
function. A manual change over initiation shall be realized for switching back.
Operational
switching-off of any infeed shall not actuate the second infeed. Manual changeover initiation shall be realized by a
separate changeover switch.
Each transformer
feeder shall be interlocked such that the
L.V. Transfer/Change Over Devices and Scheme
Transfer/change-over
devices and scheme shall be provided for all L.V. boards equipped with two
independent in feeds.
In case of fault
on the transformer, the Buchholz or overcurrent relay, etc. shall trip the
transformer’s 13.8kV & 480V circuit breakers.
On the
Manually or
process initiated change-over between two feeding sources shall be provided
without voltage interruption.
TESTS
AND INSPECTIONS
The Low Voltage Switchgears and MCC shall be subject to inspection and
tests by the COMPANY Engineer should they so require, during manufacture,
erection, and after completion. The CONTRACTOR shall give three weeks in advance
notice of scheduled tests.
The inspection and tests shall include but not be limited to the
requirements of Technical Specifications in this bid document.
Each completed low voltage switchgear, motor control center and
individual circuit breakers and motor starters shall be tested in accordance
with IEC recommendations.
Five copies of certified test reports shall be furnished.
Type test reports for the equipment offered shall be submitted with the
tenders.
Tests at Manufacturer’s Works
Specific tests
required by the various items of the plant, parts, materials, and equipment
shall be performed in accordance with the applicable Codes & Standards.
The CONTRACTOR
shall,
at the appropriate time, prove that his material and/or equipment complies with
all the requirements of this Section, such proof being the successful
completion of tests and inspections witnessed by the COMPANY Engineer.
Certified
routine test and type test certificates shall be submitted for each item of
equipment, where applicable.
At least the
following tests shall be performed in the manufacturer's workshop on the
individual apparatus and on the complete installation, respectively, all in
accordance with IEC standards:
Visual
inspection
Power frequency
H.V. tests at the main circuit
Dielectric tests
of the auxiliary circuits
Functional test
of the control circuits
Check of the
operational sequence
Check of the
denominations.
The COMPANY Engineer reserves the right to witness these tests.
The CONTRACTOR shall give
three weeks in advance notice of scheduled tests.
Five copies of
certified test reports shall be furnished.
Type test report
for the equipment offered shall be submitted with the Manufacturer/Vendor
qualification documents.
No comments:
Post a Comment