Emergency lighting shall be supplied from
the DC distribution board in case of AC supply failure.
- An emergency lighting system shall be
automatically supplied in the event of:
·
AC supply failure of substation's main AC.
·
AC supply failure of main Lighting board.
·
Lighting's miniature circuit breaker failure
for any one of the lighting circuits.
-
Emergency lighting should be installed in
all the substation rooms, switchyard, main roads, access roads, guard room and
main gate and operated as follows:.
ØEmergency outdoor lighting the system shall be manually operated.
ØEmergency indoor lighting the system shall be:
Directly
operated automatically in the following mentioned areas:
·
control room
·
PLC room
·
11/ 22 KV hall
·
AC / DC room
·
Corridors and entrance
·
66 KV switchgear
building (in indoor
s/s)
Manually operated
by means of DC switches which shall be installed in the following
places:
·
Offices
·
Workshop / store
·
Kitchen / WC
·
Auxiliaries
trnsformers rooms
·
Fire fighting room
·
Battery room / Rectifier room .
-
Emergency lighting shall be designed to give
lux level not less than 5% of the normal lighting lux level with minimum level
of 10 lux.
-
Only incandescent lamps with a porcelain
holders are allowed to be used.
-
Emergency exit signs are required at all
exist and along escape routes.
-
The control room is also to be
fitted with a portable emergency lantern which will automatically light a pilot
lamp in the event of an A.C power failure.
-
Light fittings are to be
provided at all exit door and along catwalk (switchgear building).