3.7
DISTRIBUTION AND LIGHTING
PANEL BOARDS DISTRIBUTION
PART
1 GENERAL
3.7.1
.1
DESCRIPTION OF WORK
Installation comprise panel boards for
distribution and lighting for protection of circuits, including fixing and
supporting materials and materials for termination of feeders, sub circuits and
branch circuits.
3.7.1.2 STANDARDS
Panel
boards generally are to comply with the requirements of IEC 439-1 Factory Built
Assemblies for LV Switchgear and Control Gear for voltages up to and including
1000 V a.c. And 1200 V d.c.
DESIGNATIONS:
Panel
boards are designated on Drawings and in Schedules, as follows:
3.7.1.3
SCHEDULES
Indicate
the designation and required type of panel board using the following criteria:
- Type of construction (MCB or MCCB),
referring to type of branch circuit-breakers.
- Voltage,
number of phases and wires
- Branch circuit-breaker, trip rating and
wire size
- Main
circuit breaker, trip rating and frame size (maximum continuous rating) for
MCCB.
- Short-circuit
interrupting capacity (IC) in kA at point of application
- Special
arrangement or provisions
3.7.1.4 EQUIPMENT DATA :
Submit
for approval comprehensive data including, but not limited to, the
Following:
- Manufacturers' catalogues indicating
specific equipment selected.
- Types
of panel boards and circuit breaker characteristics include duties and ratings
compensation at and above 40 deg. C
ambient conditions and corresponding
temperatures within the enclosures
- Dimensions of panels and specific
contents of each panel board
- Integrated
equipment tabulations for coordinated short-circuit series combinations of
circuit breakers.
3.7.1.5
TESTS AND CERTIFICATES
Provide
complete certified manufacturer's type test and routine test records in
compliance with the Standards.
3.7.1.6
SHOP AND CONSTRUCTION DRAWINGS
Submit
drawings for approval including, but not limited to, the following:
- exact composition of each panel board,
indicating busbar rating frame or continuous rating and trip ratings of all
circuit breakers
- Typical
installation details of panel boards, indicating main feeder ,branch circuit conduit
connections, terminal provisions, tags,
labels, mounting methods and materials
used.
3.7.1.7 APPROVED MANUFACTURERS:
Obtain
panel boards from one of the following:
Shnider
group (EGYPT )
ABB (EGYPT)
Or
other equal and approved.
PART
2 PRODUCTS AND SYSTEM
3.7.2.1
DISTRIBUTION AND LIGHTING PANELBOARDS
RATED INSULATION VOLTAGE:
To
be in accordance with the respective Standards specified.
3.7.2.1.1 PANEL BOARDS:
To
be totally enclosed, dead front type, protection code IP 31 for indoor installations and IP 55 for
outdoor installations, in accordance with IEC 144 all interiors with expansion
of main incoming and the branching C.B's shall be completely factory assembled
with neutral bar, connection busbars and
earth bar connector.
3.7.2.1.2
EARTHING BAR:
To
be provided in every panel board.
3.7.2.1.3
PROTECTION:
Is
to be fully rated throughout the systems.
3.7.2.1.4
SERIES (CASCADE) COORDINATED PACKUP PROTECTION:
Will
only be acceptable within final branch circuit panel boards, between branch
circuit breakers and the main incoming circuit breaker, in accordance with an
integrated series combination chart prepared by the manufacturer, tested
and certified in the country of origin
by an internationally authorized
organization, where short-circuit ratings are
beyond available fully rated types specified and upon Engineer's approval.
3.7.2.1.5 CIRCUIT BREAKERS:
Are
to be non-fused type.
3.7.2.1.6 CIRCUIT BREAKER ARRANGEMENT:
Panel
boards are to have one main incoming circuit breaker and the number of branch
circuit breakers arranged as shown on the Schedules including spare
circuit-breakers and not less than spare spaces for future expansion.
Three-phase
panel boards are to be designed for sequence phase connection of branch circuit
devices.
3.7.2.1.7 BRANCH CIRCUIT NUMBERING:
On
3-phase panel board schedules, circuits 1 and 4 are to be connected to red (R) phase, 2 and 5 to yellow
(Y) phase, 3 and 6 to blue (B) phase
etc., to conform with branch circuit
wiring numbering shown on the Drawings.
3.7.2.1.8 PANELBOARD ENCLOSURES
TYPE:
General
purpose type suitable for relevant ambient conditions, flush or surface
mounting as shown on the Drawings,
comprising box, trim, or trim and door to approved manufacturer's standards and sizes.
CONSTRUCTION:
Box,
trim and doors where required, are to be electro- galvanized sheet steel of
gauges not less than specified and in accordance with the Standards. Welded
joints are to be galvanized after manufacture.
Gutter spaces are to conform to the Standards, but are not to be less
than 100 mm on all sides. Enclosure is
to have pre-designed angles or threaded end studs to support and adjust
mounting of interior panel board assembly.
TRIMS:
Are
to cover and overlap front shield, covering all terminals and bus compartments,
to form a dead front panel. Trims are
to be fixed to cabinet/box by quarter-turn clamps engaging flange of box (use
of screws engaging holes in flange of box is not acceptable). Screws where used are to be oval-head,
countersunk and flush. Trims for flush
mounted panel boards are to overlap box and front shields by at least 20
mm. Trims for surface mounted panel
boards are to be exactly sized to form a
flush fit to box.
DOORS:
Are
to have concealed hinges integral with trim and flush combination cylinder lock
and catch. Doors over 1000 mm high are
to have vault-type handle and multiple point latch mechanism. Locks are to be keyed alike.
FINISH
:
Inner
and outer surfaces of cabinet/boxes, trims, doors etc. are to be cleaned, phosphatized, chrome
passivated and treated with a final
thermosetting epoxy powder modified by
polyester resins providing high resistance to mechanical in jury, heat,
acid and alkali solvents, grease, ageing and
corrosion and of standard grey color to Engineer's approval.
DIRECTORIES:
Under
glassine, or an approved alternative durable arrangement, are to be provided on
inside face of doors, or in metal label holders when trim without doors is
specified. Directories are to be typed
to identify panel boards and clearly indicate circuit number and description of
load.
OUTDOOR ENCLOSURES:
Are
to be heavy duty sheet steel cabinets, minimum 2 mm thick, fully weatherproofed
(IP55), without knockouts, but with removable sealed/gasketed bottom gland plates
and gasketed doors.
3.7.2.1.9 BUSBARS
TYPE:
One piece, 98% pure
electrolytic copper, based on maximum
total temperature rise of 40 deg. C over an ambient of 50 deg. C at full continuous rating, and maximum
current density of 1.25 A/mm2. Bolted or
clamped contact surfaces are to have maximum current density of 0.25
A/mm2. Aluminum is not to be used for
busbars or panelboard parts.
DESIGN:
Busbars
are to be shrouded/insulated and rigidly designed so that branch circuit
devices can be removed without disturbing adjacent units or changed without
additional machining, drilling or tapping.
Busing is to be full size without reduction. Busing and blank plates are to allow
installation of future circuit devices, where indicated on the Drawings.
RATING:
Busbar
rating is to be at least equal to main-circuit- breaker frame size. Where no
main circuit breaker is required, busbars are to be provided with main lugs or
a disconnect switch, with a nominal rating equal to standard circuit-breaker
frame sizes, and as shown on the single line
diagrams and panels schedule.
SHORT-CIRCUIT
DUTY:
Bus
bars are to carry maximum short-circuit duty of main protective device, which is to be at least
maximum short- circuit at point of application for a period of one second, without showing any signs of degradation.
TERMINALS AND CONNECTIONS:
Are
to be of the anti-turn, solder less screw-pressure type. Screws and bolts used for making
copper/copper connections are to be hard copper alloy with lock washers
(riveted bus connections are not acceptable).
NEUTRAL BAR:
Is
to be solid and fully insulated from cabinet or box. One solder less box type set-screw connector
is to be provided for neutral wire of each branch circuit and one bolted clamp-type
connector or anti-turn lug with set-screw for main incoming neutral wire. Neutral is to be fully sized and rated as for
phase busbars.
EARTHING BAR:
Is
to be copper, brazed to panelboard cabinet, with bolted pressure connector for
main conductor and one set-screw-type tunnel terminal for each outgoing
conductor, to provide a secure and reliable contact with all metal parts and
enclosure.
3.7.2.1.10 MOULDED CASE CIRCUIT BREAKERS (MCCB
TYPE:
Totally
enclosed, molded case, constructed from high quality, high temperature
tropicalized molded insulating materials, for continuous normal operation at
100% rated current at ambient temp 40 oC
inside the enclosure. For within
enclosures and provided with front operated single toggle
type handle mechanism for manual operation of main contacts in addition to automatic operation
under over current conditions.
Multi-pole breakers are to have a common integral trip bar for
Simultaneous
operation of all poles. Ampere rating is to be clearly visible. All terminals are to be box lug or clamp type
with set screws.
CIRCUIT BREAKER TRIP UNITS:
Unless
otherwise specified or shown on the Drawings, circuit breakers up to and including 250 A frame
size, are to be electronic
thermal-magnetic type, having bi-metallic inverse time delay over current element for small
overloads and in stantaneous magnetic over current trip element for
operation under short-circuit conditions
on each pole. Circuit breakers 250amp and larger are to have adjustable
instantaneous trips.
SWITCHING MECHANISM:
Quick-make,
quick-break type, with positive trip-free operation so that contacts cannot be
held closed against excess currents under manual or automatic operation. Contacts are
to be non-welding silver alloy provided with approved arc quenching
devices of metallic grid construction.
TRIP CURRENT RATING (AMPS):
Indicates
nominal maximum rating at which the overload element is set to operate.
FRAME SIZE:
Is
defined as the maximum continuous current rating of a circuit breaker which corresponds with the
maximum of its trip range listed below
and which is to be related to minimum acceptable short-circuit interrupting
ratings, based on fully rated
interrupting duties; normal duty (N), high break (H), or current limiter (L), as specified
hereunder.
TRIPPED POSITION:
When
tripped automatically by over current condition, operating mechanism of circuit
breaker is to assume an intermediate position clearly indicated by the handle
between ON and OFF positions.
INTERCHANGEABLE
TRIPS:
All
circuit breakers have interchangeable trip units.
COMPENSATION:
Thermal
over current trips are to be ambient temperature compensated between 25 and 50
deg. C.
ELECTRONIC TRIP UNIT:
Applicable
to circuit breakers 800 A frame size and larger, are to be solid state trip
units with long time delay settings, between 0.4 to 1 times maximum trip
rating, short time delay range of 3 to 10 times maximum trip rating with a
maximum clearing time of 0.2 seconds, and instantaneous protection adjustable
from 2 to 10 times continuous rating.
Solid state trip units are to be insensitive to changes in ambient
temperature between -20 and +55 deg.C.
Earth fault protection is to be built into trip unit where specified,
and is to be suitable for connection to an external current sensor. Push-to-trip button is to be provided on
cover for testing the trip unit.
ACCESSORIES:
Circuit-breakers
are to be designed to accommodate standard
attachments, including shunt-trip, under-voltage release, combined auxiliary and alarm switches, and
electrical operator to any circuit breaker of rating (frame size)
100 A and over. Padlocking devices are to be provided as
additional accessories, where shown on the Drawings.
3.7.2.1.11 OPERATED EARTH RESIDUAL CURRENT LEAKAGE TRIP DEVICES (RCDs):
Are
provided as add-on where required and as shown on the Drawings. Protection
against earth fault current, in addition to over current and short- circuit
protection, is to be in accordance with the Regulations. Trip current sensitivity on breakers for
branch circuits is to be 30 mA. Circuit
breakers are to include current transformer with tripping coil assembly, test
button and trip free mechanism to ensure circuit breaker cannot be held closed
against earth faults.
3.7.2.1.12
CURRENT LIMITING CIRCUIT BREAKERS:
Molded case type
without fusible elements. When operating
within current limiting range, the I2t of let-through current is to be less
than that of 1/2 cycle wave of symmetrical protective short- circuit current as
compatible with breaker construction.
3.7.2.1.12
.1 CURRENT LIMITING CIRCUIT BREAKERS:
Are to have, on
each pole, adjustable inverse time-delay over-current characteristics for
overload protection and instantaneous trip for short-circuit protection. Operation of main contacts is to be based on
electro-magnetic repulsion forces between contacts created by fault
current. Ratings are specified at rated
voltage for an rms value of prospective short circuit current.
3.7.2.1.13 MINIATURE CIRCUIT BREAKERS (MCBS )
TYPE:
Thermal magnetic
non-adjustable type tested in accordance with IEC-157-1, IEC 947-2.
MINIMUM SHORT-CIRCUIT BREAKING CAPACITIES:
Are
to be as follows:
10 - 100 A MCB: 10 or 16 kA at 220 V . A . C .
CONSTRUCTION:
MCBs
are to be tropicalized for continuous normal operation at 100% rated current at
ambient temp 40oC
outside the enclosure. and humidity to 95%, and are to be constructed from high
quality, high temperature, molded insulating materials. Guaranteed duties and characteristics are to
be submitted for temperatures above 40 deg. C.
MCBs and combinational devices are to be modular, of unified profile and
mounted to standard DIN rail.
OPERATION:
Under
overload conditions, thermal tripping is to provide close protection of
insulated conductors. Under
short-circuit conditions, the magnetic trip is to operate at 5 - 10 times
normal rated current (type 3 characteristic).
Magnetic operation is to be in the current limiting region and opening
time is not to exceed 5 milli-seconds.
RATINGS:
Preferred rated
currents are to be 10, 16, 20, 25, 32, 40, 50, 60, 80 and 100A, calibrated at
40 deg. C, available as 1p, 2p, 3p and 4-pole circuit breakers. Derating above 40 deg. C is not to exceed 1%
per deg. C, and loading is not to exceed 80% of circuit breaker rating.
RESIDUAL CURRENT DEVICES:
For
earth leakage protective circuit breakers are to be add-on devices or built-in
and integral with the standard circuit breaker.
Non-adjustable sensitivities of 30 mA, 100 mA and 300 mA are to be
available for all ratings of 2-pole and 4-pole circuit breakers.
AUXILIARIES:
Where
required or shown on single line diagram are to include alarm switch, auxiliary
switch, shunt trip, under voltage trip and similar units which are to be
modular additions to the circuit breakers.
3.7.2.1.14 MOULDED CASE SWITCH (MCS )
MOULDED CASE SWITCH:
Is
to be a non-automatic on-off switching device of equal construction to an equivalent circuit-
breaker, having no over current or fault protective elements, but marked with
a maximum current withstand and voltage rating.
SHORT
CIRCUIT RATINGS:
Circuit
breakers are to be rated for symmetrical r.m.s service short current breaking
capacity 100% of the ultimate short circuit current breaking capacity as per
IEC 947-2.
3.7.2.15 PANELBOARD ASSEMBLIES
DISTRIBUTION PANELBOARDS ( D P )
Distribution
panelboard is to have an insulation grade of 600 V a.c., 240 V. d.c. conforming
to IEC 439 and BS 5486: Part 1 class 3
surface mounted to wall, with doors, unless otherwise shown on the Drawings,
suitable for ratings of main circuit breaker and busbars 3-phase, 4-wire as shown
in schedules, suitably and orderly arranged for any selected combination of
branch MCCBs ranging and short-circuit interrupting ratings as shown on the
schedules.
CONSTRUCTION:
Cabinet/box
is to be minimum 2 mm thick sheet steel suitable for mounting relevant
C.B's. Trim or trim and door are to be
of minimum 2 mm thick sheet steel.
Fronts are to be single or twin covers to shield circuit breakers,
terminals and live ends.
INTERIOR:
Of
panelboard is to be a pan assembly consisting of chassis of minimum 2mm thick
folded galvanized sheet steel, flanged and reinforced, with busbars vertically
arranged and fixed mounted on molded insulators. Assembly is to be removable, fixed to four
threaded studs or similar arrangement, and is to allow in and out adjustment
inside the cabinet.
MOULDED INSULATORS:
Are
to have minimum temperature rating of 130 deg. C and insulation grade of 3.5 kV
for one minute.
CIRCUIT
BREAKERS:
Are
to be mounted in suitable arrangement (except for larger circuit breakers) and
bolted rigidly to copper cross and centre bus connectors.
3.7.2.16 LIGHTING PANEL BOARDS
ARRANGEMENT:
Panelboard
is to comprise a set of homogeneous branch circuit-breakers with unified
profile and base, and one main circuit breaker.
Single and multi-pole circuit breakers or other devices are to occupy
modular spaces.
Accommodation
of contactors and split-bus arrangement or other devices is not to change
regularity of standard box width.
INDOOR
ENCLOSURE:
To
be of minimum 1.0 mm thick sheet steel (suitable for mounting the C.B as shown
in schedules) for box/cabinet and minimum 1.5 mm thick sheet steel for front
shield, trim and door. Fixings for flush
trim are to be adjustable to allow for misalignment between box and wall
surface. Wiring spaces (gutters), at
least 100 mm wide. Larger gutters are to
be provided where tap-off insulated split connectors are required. Knockouts are to be provided in top or bottom
sides of enclosures and are to provide a neat and uniform conduit/cable
terminal arrangement.
TYPE:
Panelboard
for 220 V. a.c. or up to 380 V a.c. service voltage, lighting type single-phase
and neutral (SPN) or 3-phase and neutral (TPN), 2-pole or 3-pole MCCBs on
branch circuits and 2-pole or 3-pole MCCB on main incoming, or as shown in schedules.
BRANCH CIRCUIT BREAKERS:
Are
to be 1p, 2p or 3p, rated 100A frame size with trip ratings between 10 A and
100 A, and compatible ICs, selected from normal (N), high-break (H) or current-limiter
(L) range are to din rail mounted.
MAIN CIRCUIT BREAKER:
Is to be 2p, 3p or
4p, rated as shown in schedules, 225/250
A or 400 A continuous rating (frame size) with trip ratings and fully rated non-current limiting ICs of
the normal (N) or high-break (H) ranges,
with or without residual current device
(RCD) as indicated on schedules.
INTERNAL
ASSEMBLY:
To consist of
removable back plate or back pan of rigid construction, attached to enclosure
by four captive screws through keyhole fixings, and provided with DIN rails in
horizontal arrangement for SPN panels and in vertical arrangement for TPN
panels. Assembly is to be complete with
neutral terminal block, earthing bar and one piece insulated bolt-on/comb- type
phase busbar. Busbars are to be single-
phase or 3-phase with spare connectors for fixing by tightening a single screw
on circuit breaker.
Insulation
is to be of high thermal rating, capable
of carrying maximum short-circuit current for one second without overheating beyond acceptable limits required by the
Standards.
3.7.2.17 SPN TYPE PANELBOARDS:
Are
to be suitable for 220 V maximum service voltages, single-phase and neutral,
with MCBs on branch circuits and main incoming.
3.7.2.18 TPN TYPE PANELBOARDS:
Are
to be suitable for up to 380 V a.c. maximum service voltage, 3-phase and
neutral, with MCBs on branch circuits and 3-pole or 4-pole MCB or MCCB main
incoming, as shown in the Schedules or on the Drawings.
3.7.2.19 CONTACTORS:
2-pole
or 3-pole, electro-magnetic type, class AC 3 to IEC 947-4, designed to withstand large initial
currents of tungsten lamp loads or
discharge lamp loads and rated not less than the overload setting of the
protective device upstream. Contacts are
to be double break silver cadmium plated, having self-cleaning wiping
action. Control is to be provided by
means of phase-neutral (maximum 220V) split coil, for on-off activation by
local and/or by remote direct-wired on-off push-buttons. Contactor is to be mechanically latched. Control circuit is to be fused. Auxiliaries are to include local pilot
light, parallel remote indicating circuit, two N.O. and two N.C. auxiliary
contacts.
PART
3 FIELD AND INSTALLATION WORK
3.7.3.1 FIXING GENERLLY :
- Align, level and securely fasten panel
boards to structure
- Fix surface mounted outdoor panel boards
at least 25 mm from wall ensuring
supporting members do not prevent flow
of air
- do not use connecting conduits to
support panel boards.
- Close
unused openings in panelboard cabinets.
3.7.3.2 PANELBOARD INTERIORS:
Do not install in cabinets until all conduit
connections to cabinet have been completed.
3.7.3.3 WIRING INSIDE PANELBOARDS:
Shall be factory made.
3.7.3.4 TRIM:
Fix
plumb and square prior to painting. Fix
trim for flush mounted cabinets flush with wall surface finish.
3.7.3.5 PROTECTION:
Treat
concealed surfaces of recessed cabinets with heavy field application of
water-proof compound prior to installation.
3.7.3.5
INSPECTION
AND TESTS ON SITE
GENERALLY:
Carry
out sample tests, as required by the Engineer, on panel boards after
installation, to verify short-circuit capability of circuit breakers and
busbars. Inspect conditions within panel boards and verify insulation
conditions by use of a megger
CIRCUIT
BREAKERS:
Tests
are to include operation of every circuit breaker manually. Check automatic operation of selected
circuit breakers, as required by the
Engineer, by applying necessary
short-circuit, overload, and/or earth leakage current for tripping circuit breaker, and compare with
manufacturer's data/characteristic
curves. Measure and report ambient temperature inside enclosure.
INSULATION
TESTS:
Carry
out insulation tests on all busbars between phases, between phases and
earth/cabinet, and between neutral and earth.
Record all readings, using a 500 V megger for equipment used on 240 V systems
and a 1000 V megger for equipment used on systems up to 600 V.
Labeling:
to be engraved type for all incoming C.B and outgoing C.B
No comments:
Post a Comment