Cable Trays
- All components, accessories, and supports shall be made of hot-dip- galvanized steel, bordering shall be edge protection. All cable trays shall be earthed with a copper conductor.
- All cables shall be laid in only one
layer & it should be supported with special ribbons.
- Space factor doesn't exceed 50% i.e. the C.S.A for cables does not exceed 50%
from the cable tray section.
- Distance
between every two cables shall be not less than twice the diameter for the biggest one for cable 3.
- The minimum
load capacity shall be :-
200mm - 150
kg/m
300mm - 175
kg/m
400mm - 200
kg/m
500mm - 220
kg/m
600mm - 240
kg/m
- The regular
supporting distance shall be 1500 mm .