FIRE FIGHTING SYSTEM FOR OUTDOOR POWER TRANSFORMERS
This specification mainly covers the design, manufacturing, testing, delivery, communication and guarantee for fire fighting systems for outdoor power transformers
Any material not specifically mentioned in this specification or not shown on the drawing but required for proper performance and operation shall be furnished install.
- DEFINITIONS
Water Spray:
Use of water in a form having a predetermined
pattern, particle size, velocity, and density discharged from special nozzles or
devices.
Water
filling pump (Jockey pump)
Vertical pump
is used to fill the main water tank.
Filling system
shall be equipped in addition to the
pump with gate valves, non-return valves, strainers, and devices for preventing pump dry running.
Pressurizing
Unit
Air pressure
over the water inside the tank is maintained by an air compressor with
automatic starting. Air vessels, ball valves, safety relief valves, and pressure
gauges shall be provided. Pressurizing unit shall be sufficient to extinguish
the fire in a time not exceed three minutes
Pneumatic
Remote Control Valve Station
Emergency – Test Release Push Buttons
Emergency push buttons shall be provided to activate the water spray system manually and located at the outside of valve station room.
Test release pushbuttons shall be used to test the system operation and located in transformer area.
Spraying Cage for Transformers
Self-supporting pipes around transformers in the shape of rings and shall be provided with cone nozzles.
Sprinkler
It is a unit for activation water spray system integrated permanently in the pipework that covers the protected area.
Fire the detection system of transformers
Heat detector:
Rate of rising
and fixed temperature electrical detectors providing a double knock system in
concert with the pneumatical sprinkler invitation system to release the water
spray system automatically.