Air-Insulated, Metal-enclosed
and Metal-clad
Medium-Voltage Switchgear
Loss of Service
Continuity category: LSC
2B
(Metalclad)
Partition Class: PM
Internal Arc Classification: IAC A FL
customer: 36K V TAYBAH EGYPT MELTING SHOP PROJECT
General Technical Description
Contents:
1 Switchgear Description 3
1.1 Switchgear type 3
1.2 Panel design 3
1.3 Enclosure 3
1.4 Busbar compartment 4
1.5 Switching device compartment 4
1.6 Interlocks 4
1.7 Connection compartment 5
1.8 Low voltage compartment 6
2 Benefits and features 7
3 Standards 8
4 Particulars of the system and the installation 9
5 Scope of Supply 10
6 Documentation 11
to 20
1. Switchgear Description
1.1
Switchgear type
The offered switchgear is
air-insulated, metal-enclosed, metal-clad, type-tested, medium voltage
switchgear for indoor installation. The switchgear has been designed and type
tested in line with IEC 62271-200.
The switchgear along with the vacuum
circuit breaker 3AH5 & 3AH3 as switching device offers following benefits
to the buyers/users:
-
Saves Lives
-
Peace of Mind
-
Increases
Productivity
-
Saves Money
1.2
Panel design
The 8BT2 switchgear panel
consists of the following functional compartments:
-
Busbar compartment
-
Switching device
compartment
-
Connection compartment
-
Low-voltage compartment
1.3
Enclosure
The
panel enclosure including
doors and covers
as well as the partition
walls are made of
sheet-steel and are bolted together.
The complete enclosure including all doors, covers, and end walls is powder-coated with resistant epoxy resin, color Standard (RAL 7032). Partition walls and shutters are made of galvanized sheet
metal.
The complete
structure including
partition walls and shutters is metallic
and earthed. This ensures the highest service continuity category
LSC2B and highest operators’ safety with partition class PM in line with IEC 62271-200.
The service continuity category LSC2B allows
access to any functional unit while keeping any
other functional units energized and operated
normally. For example,
it is possible to access
the switching device compartment of a 8BT2 panel while
keeping the respective connection
and busbar compartments, as well as the adjacent panels, live. Thus the category
LSC2B provides the highest service continuity when any functional compartment (exception busbar compartment) is opened for maintenance. This feature
offers the benefit
“Increases Productivity”.
The earthed
metallic shutters and partition walls offer the partition class PM. This ensures
no electrical field in opened compartment due to living parts
in the adjacent compartment and no possible influence on electrical field distribution around
live parts in an adjacent compartment.
The exception is when the shutters are opened intentionally. Thus the partition class PM ensures
the highest operators’ safety during maintenance.
This safety feature offers
the benefit of “Saves Lives”.
In the case of an internal arc fault,
the pressure from the individual compartments is released upwards or backward. The front doors of switching device
compartments, the sidewalls of end
panels, and the busbar compartments are pressure
resistant. The 8BT2 switchgear panels have been typing tested under conditions of arcing due to an internal
fault in line with Annex A
of IEC 62271-200. The offered
switchgear confirms
classification IAC (initials for Internal Arc
Classification) and accessibility “A” for front and lateral
sides. The classification IAC ensures
operators’ safety even during the remote chance
of arcing due to internal fault. This feature offers the benefit
“Saves Lives”.
1.4 Busbar compartment
The busbar compartment houses
the 3 phase main horizontal busbars along with the bus support insulators,
feeder connections and bushings with fixed contacts.
The shutter for visual
inspection of the fixed contacts in bushings can be opened and closed
separately through the switching device compartment. The busbars are made of
round-edged profiles. The busbars are bolted from panel to panel.
The rear, as well as top covers, are bolted and provide access to busbars either from the rear or top during the
installation. Thus making the busbar compartment a “Tool-based accessible
compartment” as per IEC 62271-200.
1.5 Switching device compartment
The switching device compartment has a
possibility to house one of the following switching devices on withdrawable
truck:
-
Vacuum Circuit
Breaker 3AH5
-
Vacuum Circuit
Breaker 3AH3
Each 8BT2 panel with the above-mentioned switching
devices is provided with an integral withdrawable truck. Hence the buyer/user
does not require a handling truck for the replacement of the switching device.
When
moving from the service position to the test position and vice versa, the
withdrawable truck opens or closes the metallic earthed shutters covering the
fixed contacts in the busbar and the connection compartments.
The low voltage wiring between the switching device and the fixed part of the panel is connected by means of a 64-pin plug.
Wiring ducts for control cables are arranged inside the switching device compartment, and they are equipped with removable metallic covers. When viewed from the font, the internal panel wiring for earthing switch, instrument transformers is located in the left-hand wiring duct.
The
external control cables enter from below on the left side of the panel through
openings in the panel floor.
The use of proven vacuum switching devices minimizes the maintenance and shutdown
requirement of switchgear. This increases the availability of switchgear and decreases the maintenance costs compared to other switching dielectric mediums. Also, the use of vacuum as dielectric media prevents the formation of hazardous switching by-products. These features offer the benefits “Saves Lives, Peace of Mind, Increase Productivity and Saves Money”
1.6 Interlocks
The switching device a compartment in combination with vacuum circuit breaker offers the following
mechanical interlocks.
1. Precondition for moving the withdrawable truck from Test to Service position
-
Inserted and locked in the
panel
-
Circuit-breaker in OFF position
-
Feeder-Earthing switch in OFF
position
-
Consistent coding between switching device and switchgear panel through
- Switching device compartment front door closed and interlocked
2. Precondition for moving the withdrawable truck from Service to Test position
-
Circuit-breaker in OFF position
3. Operating the vacuum circuit breaker
-
Withdrawable truck in
interlocked end position (Service or Test position)
4. Operating the feeder earthing switch
- Withdrawable truck in the interlocked Test position
5. Opening the switching device compartment front door
-
Withdrawable truck in
interlocked Test position
Following operations are possible with the switching device
compartment front door closed:
-
Mechanical (emergency manual)
switching ON and OFF of Vacuum circuit breaker
-
Moving the withdrawable truck
from Test to Service position and vice versa.
-
Emergency manual charging of
VCB operating mechanism
-
Manual operation of the feeder
earthing switch
Thus the operators’
safety is completely ensured with the help of the above-mentioned interlocks and
with all operations behind a closed doors. This feature offers the benefit “Saves
Lives”.
In line with IEC
62271-200, the vacuum circuit breaker is type-tested inside the 8BT2 panel,
thus ensuring the performance reliability of the Vacuum circuit breaker inside the
panel.
This feature offers
the benefit “Peace of Mind”.
The door interlock of the switching device, compartment makes it “Interlocked based accessible compartment” as per IEC 62271-200.
1.7 Connection compartment
The
connection compartment can house the following components:
-
Block type current
transformers
-
Voltage
transformers
- Surge arresters
- Earth busbar,
- Earthing switch with making capacity
Cable termination can be accessed from the front by means of removal of the partition plate between the switching device
and cable compartment. Thus, the connection compartment is “Interlock and Tool based accessible” as per IEC 62271-200.
1.8 Low voltage compartment
The low voltage compartment is located at the front above the switching
device compartment. It is completely separated from the rest of the panel and
can be removed.
The electrical connections between the withdrawable unit and the fixed part
of the panel are made with flexible wires and a fixed-mounted 64-pin
low-voltage plug connection.
The secondary equipment is installed flush on the door of the low-voltage
compartment, or on a mounting plate / DIN-rails inside the compartment. The
wires are laid in wiring ducts with a sufficient cross-section.
2. Benefits and features
|
Benefits |
Features |
1 |
Saves Lives |
q
All operations behind closed door |
|
|
q
Front door interlocks |
|
|
q
Internal arc classified switchgear |
|
|
q
Partition class PM |
|
|
q
Use of vacuum switching technology |
2 |
Peace of Mind |
q
Type testing of VCB inside the panel q
Factory assembled type-tested switchgear according to IEC 62271-200 q
Use of standard, worldwide components q
Quality management according to DIN EN ISO-9001 q
Design based on global best practice sharing and excellence |
3 |
Saves Money |
q
Maintenance-free 3AH5 & 3AH3 VCB |
4 |
Increases
Productivity |
q
Service continuity category LSC2B |
|
|
q Maintenance free 3AH5 & 3AH3 VCB |
3. Standards
IEC 62271-200
|
A.C. metal-enclosed switchgear and controlgear for rated
voltages above 1 kV and up to and including 52 kV Metallgekapselte
Wechselstrom-Schaltanlagen für Nennspannungen über 1 kV bis 52 kV |
VDE 0671-200 |
IEC 60694 |
Common clauses for high-voltage switchgear and controlgear
standards Gemeinsame Bestimmungen für
Hochspannungsschaltgeräte |
VDE 0670 - 1000
|
IEC 62271-100 |
High-voltage alternating current circuit-breakers Hochspannungs-Wechselstrom-Leistungsschalter |
VDE 0671-100 |
IEC 60529 |
Degree of protection provided by enclosures (IP-code) Schutzarten durch Gehäuse
(IP-Code) |
VDE 0470 – 1 |
IEC 62271-102 |
Alternating current disconnectors (isolators) and earthing
switches Wechselstromtrennschalter und Erdungsschalter |
VDE 0671-102 |
IEC 61243-5 |
Working under voltage -
Voltage detectors – Part 5: Voltage detection
systems Arbeiten unter Spannung - Spannungsprüfer - Teil 5: Spannungsprüfsysteme |
VDE 0682 – 415 |
IEC 60044 -1 |
Current transformers Stromwandler |
VDE 0414 – 1 |
IEC 60044 -2 |
Voltage transformers Spannungswandler |
VDE 0414 – 2 |
4. Particulars of the system and the installation
Installation...................................................................................................................... Indoor
Number of phases.................................................................................................................. 3
Busbar system....................................................................................... Single
busbar system
Rated (Highest) voltage.................................................................................................. 36 kV
Operating (Nominal) voltage.......................................................................................... 33 kV
Rated short-duration power-frequency withstand voltage............................................. 70 kV
Rated lightning impulse withstand voltage.................................................................... 170 kV
Rated frequency............................................................................................................. 50 Hz
System neutral earthing............................................... Isolated or resonance earthed neutral
Ambient temperature...................................................................................................... 45 °C
Rated normal
current of the busbar............................................................................. 2500
A
Max permissible busbar current
at 45 °C..................................................................... 2500
A
Rated short-time withstand current................................................................................ 25 kA
Rated short-circuit duration................................................................................................. 1 s
Rated peak withstand current......................................................................................... 63 kA
Rated short-circuit breaking current............................................................................... 25 kA
Rated short-circuit making current................................................................................. 63 kA
Degree of protection for
enclosure.................................................................................. IP4X
Degree of protection for
Partitions................................................................................... IP2X
Loss of Service Continuity category ........................................................................... LSC2B
Partition Class .................................................................................................................... PM
Internal arc classification................................................................................................... IAC
Accessibility front / lateral ................................................................................................. AFL
Internal arc fault current
............................................................................................... 25 kA
Arc-fault duration.............................................................................................................. 1.0
s
Type of installation ............................................................................................ Wall-standing
Cable access from ......................................................................................................... Front
Individual panel width................................................................................................ 1550
mm
Panel depth............................................................................................................... 2450
mm
Panel height intermediate panel................................................................................ 2400 mm
Panel height end panel............................................................................................. 2775 mm
Height of switchgear
room ( min. )........................................................................... 3400
mm
Distance of end panel right to the lateral wall (25 kA).............................................. ≥100 mm
Distance to the rear wall............................................................................................. 200 mm
Color of switchgear................................................................................................ RAL 7032
Other
details as per the scope of supply,
single-line diagram and/or constructional data.
5. Scope of Supply:
The switchgear is designed as a single-busbar to the enclosed
Data Sheet.
Overview:
Item |
Quantity |
Typical No. |
Description |
|
1 |
=HZ01 |
Switching
device panel
2500 A |
||
1 |
=HZ02 |
Metering
panel |
||
1 |
=HZ03 |
Switching
device panel
2000 A |
||
1 |
=HZ04 |
Switching
device panel
1250 A |
||
4 |
=HZ05 |
Switching
device panel
2500 A |
||
1 |
=HZ00 |
Accessories |
||
|
|
|
||
In the case of customer-specific design, it might
be possible that individual points of the
switchgear
descriptions are not valid anymore.
The offered scope of supply is equipped in detail as follows::
Item No. |
Quantity |
Description |
Typical No. |
5.1 1 Incoming (2500 A) =HZ01
Max permissible feeder
current at 45 °C: 2417 A
In order to reach the specified
current this typical is equipped with
|
|
forced ventilation. |
5.1.1 |
1 |
Busbar
Compartment |
|
|
Busbar
cross-section Cu 3x80x10
mm |
|
|
with partition wall |
5.1.2 |
1 |
Switching Device
Compartment |
1 |
Circuit breaker truck |
|
Truck for
the circuit breaker |
|
Operating mechanism truck : Hand operated |
|
Auxiliary switch
truck: 4 NC + 4 NO |
1 |
Vacuum circuit breaker, Type 3AH |
|
VACUUM CIRCUIT-BREAKER 36KV POLE-CENTRE DISTANCE 350MM 31.5KA 2500A OPERATG.MECHAN. EK SECONDARY EQUIPMENT: OPERATING CYCLE COUNTER BREAKER TRIPPING SIGNAL 2 POSITION SWITCHES FOR SIGNAL: "CLOSING SPRING CHARGED" CLOSING SOLENOID WITH VARISTOR CIRCUITRY
IN THE SECONDARY CIRCUIT VOLTAGE OF CLOSING SOLENOID
DC 110 V, VOLTAGE OF 1st SHUNT RELEASE DC 110 V, VOLTAGE OF 2nd SHUNT RELEASE DC 110 V, VOLTAGE OF OPERATING MECHANISM
AC 230V, AUXILIARY
SWITCH 12NO+12NC SECONDARY CONNECTION 64 POLE PLUG CONNECTOR,
RATED LIGHTNING
IMPULSE WITHSTAND VOLTAGE 195KV INSTEAD OF 170KV RATED SHORT-TIME FREQUENZ WITHSTAND VOLTAGE UD = 95KV
INSTEAD OF 85KV
RATED POWER FREQUENCY WITHSTAND VOLTAGE 95KV INSTEAD OF 70KV |
5.1.3 1 Connection Compartment
1 |
Panel
connection |
|
|
Cable connection from
bottom |
|
|
Number of cables per
phase 4 cables |
|
|
Single-core cable max. 500 mm2 |
1 |
Capacitive voltage indicator on the connection side |
|
Capacitive voltage
indication system, Type: LRM
(VOIS+) |
3 |
The current transformer in the
connection compartment Designed as block type
current transformer |
|
3 x 2 cores
in L1/L2/L3 |
|
Technical data: 36.0
kV / 25.0 kA / 1 s |
|
Primary current: 2000 A |
|
Secondary current: 1 A / 1
A |
|
Core 1: 15 VA /
Cl. 0.5 / FS5 |
|
Core 2: 15 VA /
Cl. 5P / 10 |
|
with capacitive voltage layer |
5.1.4 |
1 |
Low Voltage Compartment, |
|
1 |
Multifunction Directional Over Current & Earth fault Protective Relay with PROFIBUS
(FMS) Type 7SJ6221 (Siemens –
Germany). |
|
3 |
Analog
Ammeter (0-2000)A , CL 1.5. |
|
2 |
Push-button (ON-OFF). |
|
3 |
Indicating lamps (ON-OFF – TRIP). |
|
1 |
Thermostat 230 VAC, 10 A with 2 CO Contacts. |
5.1.5 |
|
Customer-specific designs |
|
1 |
Extra Isolation For 40.5kv CB |
Item No. |
Quantity |
Description |
Typical No. |
5.2 1
Metering Panel
=HZ02
|
|
|
|
|||
|
5.2.1 1 Busbar Compartment |
Busbar
cross-section Cu 1x80x10
mm with partition wall |
||||
|
|
Current transformer in run of busbar Designed as block type
current transformer assembled on the right-hand side |
|
|||
|
|
3 x 2 cores in L1/L2/L3 |
|
|||
|
|
Technical
data: 36.0
kV / 25.0 kA / 1 s |
|
|||
|
|
Primary
current: 2000 A |
|
|||
|
|
Secondary
current: 1 A /
1 A |
|
|||
|
|
Core 1: 15 VA / Cl.
0.5 / FS5 |
|
|||
|
|
Core 2: 15 VA / Cl.
5P / 10 |
|
|||
5.2.2 1 Switching Device
Compartment
1 |
Metering truck with primary fuses |
|
Metering truck |
|
Operating mechanism truck : Hand operated |
|
Auxiliary switch
truck: 6 NC + 6 NC |
3 |
Voltage
transformer, on truck With primary fuses. |
|
3 x 1-pole with earth-fault winding
and damping resistor |
|
Primary voltage: 33.0
/√3 kV |
|
Voltage of secondary winding: 100 /√3 V: 50 VA /
Cl. 0.5 |
|
Voltage of earth-fault winding: 100 / 3 V: 20 VA /
Cl. 3P |
5.2.3 1 Connection Compartment
5.2.4 |
1 |
Low Voltage Compartment |
|
|||
|
1 |
Digital Multimeter includes (KWH, CL. 0.5 - KVARH, CL.1.0 - P.F. –
Hz,……) Type Elester-Alpha 1800 series. |
||||
|
3 |
Analouge
Ammeter (0-2000)A - CL 1.5. |
||||
|
1 |
Analouge Voltmeter
(0–36) KV, CL 1.5. |
||||
|
1 |
Thermostat 230 VAC, 10 A with 2 CO Contacts. |
|
|||
Item No. |
Quantity |
Description |
Typical No. |
5.3 1 EAF Outgoing (2000 A) =HZ03
Max permissible feeder
current at 45 °C: 1810 A
5.3.1 |
1 |
Busbar
Compartment |
|
|||
|
|
Busbar
cross-section Cu 3x80x10
mm |
|
|||
|
|
with partition wall |
|
|||
5.3.2 |
1 |
Switching Device
Compartment |
|
|||
|
1 |
Circuit breaker truck |
||||
|
|
Truck for
the circuit breaker |
||||
|
|
Operating mechanism truck : Hand operated |
||||
|
|
Auxiliary switch
truck: 4 NC + 4 NO |
||||
|
1 |
Vacuum circuit breaker, Type 3AH |
|
|||
|
|
VACUUM CIRCUIT-BREAKER 36KV F.120.000 MECH.OPERATING CYCLES POLE-CENTRE DISTANCE 350MM 31.5KA 2000A
OPERATG.MECHAN. EK
1 SHUNT RELEASE SECONDARY EQUIPMENT: OPERATING CYCLE COUNTER BREAKER TRIPPING SIGNAL 2 POSITION SWITCHES FOR SIGNAL: "CLOSING SPRING CHARGED" CLOSING SOLENOID WITH VARISTOR CIRCUITRY
IN THE SECONDARY CIRCUIT
VOLTAGE OF CLOSING SOLENOID
DC 110V, VOLTAGE OF 1st SHUNT RELEASE DC 110V, VOLTAGE OF OPERATING MECHANISM
AC 230V, AUXILIARY
SWITCH 12NO+12NC SECONDARY CONNECTION 64 POLE PLUG CONNECTOR,
RATED LIGHTNING
IMPULSE WITHSTAND VOLTAGE 195KV INSTEAD OF 170KV RATED SHORT-TIME FREQUENZ WITHSTAND VOLTAGE UD = 95KV
INSTEAD OF 85KV
RATED POWER FREQUENCY WITHSTAND VOLTAGE 95KV INSTEAD OF 70KV
|
|
|||
5.3.3 1 Connection Compartment
1 |
Panel
connection |
|
Cable connection from
bottom |
|
Number of cables per
phase 3 cables |
|
Single-core cable max. 500 mm2 |
|
3 |
The current transformer in the
connection compartment Designed as block type
current transformer |
|
|||
|
|
3 x 2 cores
in L1/L2/L3 |
|
|||
|
|
Technical data: 36.0
kV / 25.0 kA / 1 s |
|
|||
|
|
Primary current: 2000 A |
|
|||
|
|
Secondary current: 1 A / 1
A |
|
|||
|
|
Core 1: 15 VA /
Cl. 0.5 / FS5 |
|
|||
|
|
Core 2: 15 VA /
Cl. 5P / 10 |
|
|||
|
|
|
|
|||
|
1 |
Earthing switch on the cable connection |
|
|||
|
|
Earthing switch
with short-circuit making capability Short-circuit current and duration: 25 kA / 1
s |
|
|||
|
|
Auxiliary switch:
4 NC + 4 NO |
|
|||
|
|
Operating mechanism: Hand operated |
|
|||
|
|
Electromagnetic interlocking: DC
110 V |
|
|||
|
|
Mechanical padlocking |
|
|||
|
|
|
|
|||
|
3 |
Surge
arrester |
||||
|
|
Type: Siemens / 3EE SPECIAL-PURPOSE
SURGE ARRESTER RATED VOLTAGE 52KV, ENERGY ABSORPTION.CAPACITY 10KJ/KV
SHORT-CIRCUIT CURRENT STRENGTH 50KA VERSION F.FURNACE TRANSFORMERS Max. operating voltage: 36,0 kV |
||||
5.3.4 |
1 |
Low Voltage Compartment, |
||||
|
1 |
Multifunction Directional Over
Current & Earth fault Protective Relay with PROFIBUS (FMS) Type 7SJ6221 (Siemens – Germany). |
||||
|
1 |
Analog Ammeter (0-2000)A , CL 1.5. |
||||
|
2 |
Push-button (ON-OFF). |
||||
|
3 |
Indicating lamps (ON – OFF –
TRIP). |
||||
|
1 |
Thermostat 230 VAC, 10 A with 2 CO
Contacts. |
||||
5.3.5 |
|
Customer-specific designs |
|
1 |
Extra Isolation For 40.5kv
CB |
Item No. |
Quantity |
Description |
Typical No. |
5.4 1 LF Outgoing (1250 A)
=HZ04
Max permissible feeder
current at 45 °C: 1214 A
5.4.1 |
1 |
Busbar
Compartment |
|
|||
|
|
Busbar
cross-section Cu 3x80x10
mm |
|
|||
|
|
with partition wall |
|
|||
5.4.2 |
1 |
Switching Device
Compartment |
|
|||
|
1 |
Circuit breaker truck |
||||
|
|
Truck for
the circuit breaker |
||||
|
|
Operating mechanism truck: Hand operated |
||||
|
|
Auxiliary switch
truck: 4 NC + 4 NO |
||||
|
1 |
Vacuum circuit breaker, Type 3AH |
|
|||
|
|
VACUUM CIRCUIT-BREAKER 36KV F.120.000 MECH.OPERATING CYCLES POLE-CENTRE DISTANCE 350MM 31.5KA 1250A OPERATES.MECHAN. EK
SECONDARY EQUIPMENT: OPERATING CYCLE COUNTER BREAKER TRIPPING SIGNAL 2 POSITION SWITCHES FOR SIGNAL: "CLOSING SPRING CHARGED" CLOSING SOLENOID WITH VARISTOR CIRCUITRY
IN THE SECONDARY CIRCUIT 2 SHUNT
RELEASES VOLTAGE OF CLOSING SOLENOID
DC 110V, VOLTAGE OF 1st SHUNT RELEASE DC 110V, VOLTAGE OF 2nd SHUNT RELEASE DC 110V, VOLTAGE OF OPERATING MECHANISM
AC 230V, AUXILIARY
SWITCH 12NO+12NC SECONDARY CONNECTION 64 POLE
PLUG CONNECTOR,
RATED LIGHTNING
IMPULSE WITHSTAND VOLTAGE 195KV INSTEAD OF 170KV RATED SHORT-TIME FREQUENZ WITHSTAND VOLTAGE UD = 95KV
INSTEAD OF 85KV
RATED POWER FREQUENCY WITHSTAND VOLTAGE 95KV INSTEAD OF 70KV
|
|
|||
5.4.3 1 Connection Compartment
1 |
Panel
connection |
|
Cable connection from
bottom |
|
Number of cables per
phase 2 cables |
|
Single-core cable max. 500 mm2 |
|
3 |
The current transformer in the
connection compartment Designed as block type
current transformer |
|
|||
|
|
3 x 2 cores
in L1/L2/L3 |
|
|||
|
|
Technical data: 36.0
kV / 25.0 kA / 1 s |
|
|||
|
|
Primary current: 400 A |
|
|||
|
|
Secondary current: 1 A / 1
A |
|
|||
|
|
Core 1: 15 VA /
Cl. 0.5 / FS5 |
|
|||
|
|
Core 2: 15 VA /
Cl. 5P / 10 |
|
|||
|
|
|
|
|||
|
1 |
Earthing switch on the cable connection |
|
|||
|
|
Earthing switch
with short-circuit making capability Short-circuit current and duration: 25 kA / 1
s |
|
|||
|
|
Auxiliary switch:
4 NC + 4 NO |
|
|||
|
|
Operating mechanism: Hand operated |
|
|||
|
|
Electromagnetic interlocking: DC
110 V |
|
|||
|
|
Mechanical padlocking |
|
|||
|
|
|
|
|||
|
3 |
Surge
arrester |
||||
|
|
Type: Siemens / 3EK7 SURGE ARRESTER FOR DISTRIBUTION NETWORKS REFERENCE STANDARD: IEC, UR=42KV,
IN=10KA Max. operating voltage: 36,0 kV |
||||
5.4.4 |
1 |
Low Voltage Compartment, |
||||
|
1 |
Multifunction Directional Over
Current & Earth fault Protective Relay with PROFIBUS (FMS) Type 7SJ6221 (Siemens – Germany). |
||||
|
1 |
Analog Ammeter (0-400)A, CL 1.5. |
||||
|
2 |
Push-button (ON-OFF). |
||||
|
3 |
Indicating lamps (ON – OFF –
TRIP). |
||||
|
1 |
Thermostat 230 VAC, 10 A with 2 CO
Contacts. |
||||
5.4.5 |
|
Customer-specific designs |
|
1 |
Extra Isolation For 40.5kv
CB |
Item No. |
Quantity |
Description |
Typical No. |
5.5 2 SVC Feeder (2500 A)
=HZ05
Max permissible feeder
current at 45 °C: 2417 A
In order to reach the specified
current this typical is equipped with
forced ventilation.
5.5.1 |
1 |
Busbar
Compartment |
|
|||
|
|
Busbar
cross-section Cu 3x80x10
mm |
|
|||
|
|
with partition wall |
|
|||
5.5.2 |
1 |
Switching Device
Compartment |
|
|||
|
1 |
Circuit breaker truck |
||||
|
|
Truck for
the circuit breaker |
||||
|
|
Operating mechanism truck : Hand operated |
||||
|
|
Auxiliary switch
truck: 4 NC + 4 NO |
||||
|
1 |
Vacuum circuit breaker, Type 3AH |
|
|||
|
|
VACUUM CIRCUIT-BREAKER 36KV F.120.000 MECH.OPERATING CYCLES POLE-CENTRE DISTANCE 350MM 31.5KA 2500A OPERATG.MECHAN. EK
SECONDARY EQUIPMENT: OPERATING CYCLE COUNTER BREAKER TRIPPING SIGNAL 2 POSITION SWITCHES FOR SIGNAL: "CLOSING SPRING CHARGED" CLOSING SOLENOID WITH VARISTOR CIRCUITRY
IN THE SECONDARY CIRCUIT
2 SHUNT
RELEASES VOLTAGE OF CLOSING SOLENOID
DC 110V, VOLTAGE OF 1st SHUNT RELEASE DC 110V, VOLTAGE OF 2nd SHUNT RELEASE DC 110V, VOLTAGE OF OPERATING MECHANISM
AC 230V, AUXILIARY
SWITCH 12NO+12NC SECONDARY CONNECTION 64 POLE
PLUG CONNECTOR,
RATED LIGHTNING
IMPULSE WITHSTAND VOLTAGE 195KV INSTEAD OF 170KV RATED SHORT-TIME FREQUENZ WITHSTAND VOLTAGE UD = 95KV
INSTEAD OF 85KV
RATED POWER FREQUENCY WITHSTAND VOLTAGE 95KV INSTEAD OF 70KV
|
|
|||
5.5.3 1 Connection Compartment
1 |
Panel
connection |
|
Cable connection from
bottom |
|
Number of cable per
phase 4 cables |
|
Single-core cable
max. 500 mm2 |
|
3 |
Current transformer in the
connection compartment Designed as block type
current transformer |
|
|||
|
|
3 x 2 cores
in L1/L2/L3 |
|
|||
|
|
Technical data: 36.0
kV / 25.0 kA / 1 s |
|
|||
|
|
Primary current: 2500 A |
|
|||
|
|
Secondary current: 1 A / 1
A |
|
|||
|
|
Core 1: 15 VA /
Cl. 0.5 / FS5 |
|
|||
|
|
Core 2: 15 VA /
Cl. 5P / 10 |
|
|||
|
|
|
|
|||
|
1 |
Earthing switch on the cable connection |
|
|||
|
|
Earthing switch
with short-circuit making capability Short-circuit current and duration: 25 kA / 1
s |
|
|||
|
|
Auxiliary switch:
4 NC + 4 NO |
|
|||
|
|
Operating mechanism: Hand operated |
|
|||
|
|
Electromagnetic interlocking: DC
110 V |
|
|||
|
|
Mechanical padlocking |
|
|||
|
|
|
|
|||
|
3 |
Surge
arrester |
||||
|
|
Type: Siemens / 3EK7 SURGE ARRESTER FOR DISTRIBUTION NETWORKS REFERENCE STANDARD:IEC, UR=42KV,
IN=10KA Max. operating voltage: 36,0 kV |
||||
5.5.4 |
1 |
Low Voltage Compartment, |
||||
|
1 |
Multifunction Directional Over
Current & Earth fault Protective Relay with PROFIBUS (FMS) Type 7SJ6221 (Siemens – Germany). |
||||
|
1 |
Analog Ammeter (0-2500)A , CL 1.5. |
||||
|
2 |
Push-button (ON-OFF). |
||||
|
3 |
Indicating lamps (ON – OFF –
TRIP). |
||||
|
1 |
Thermostat 230 VAC, 10 A with 2 CO
Contacts. |
||||
5.5.5 |
|
Customer-specific designs |
|
1 |
Extra Isolation For 40.5kv
CB |
Item No. |
Quantity |
Description |
Typical No. |
5.6 Switchgear accessories
=HZ00
|
1 |
Standard
accessory set consisting of: |
|
|
1 Hand crank
for charging spring of circuit breaker |
|
|
1 Pushrod for actuating the ON/OFF push
buttons |
|
|
1 Hand lever
for moving withdrawable part |
|
|
1 Hand lever
for earthing switch |
|
|
1 Socket spanner for high voltage
and low voltage door |
|
|
1 Instruction manual |
|
2 |
One end wall, IAC 1,0 sec |
No comments: